| 2017-12-18 14:56:53 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) THE SUBMITTED PLANS INDCATE AN OCCUPANCY LOAD OF |
| | 292, HOWEVER, ACTUAL SQ FT CALCULATINS INDICATE OVER |
| | 300. |
| | |
| | PER NFPA 101, CHAPTER 13, EXISTING ASSEMBLY OCCUPANCIES |
| | A FIRE SPRINKLER SYSTEM IS REQUIRED. |
| | |
| | 13.3.5 EXTINGUISHMENT REQUIREMENTS. SEE ALSO 13.1.6, |
| | 13.2.6, AND 13.3.2. |
| | 13.3.5.1 WHERE THE OCCUPANT LOAD EXCEEDS 100 300, THE |
| | FOLLOWING ASSEMBLY OCCUPANCIES SHALL BE PROTECTED |
| | THROUGHOUT BY AN APPROVED, SUPERVISED AUTOMATIC |
| | SPRINKLER SYSTEM IN ACCORDANCE WITH 9.7.1.1(1): |
| | (1) DANCE HALLS |
| | (2) DISCOTHEQUES |
| | (3) NIGHTCLUBS |
| | (4) ASSEMBLY OCCUPANCIES WITH FESTIVAL SEATING |
| | |
| | PLEASE PROVIDE FOR THE REQUIREMENT OR JUSTIFY SPECIFIC |
| | ALTENRATIVES FOR CONSIDERATION PER: |
| | |
| | |
| | 13.1.1.4 AN EXISTING BUILDING HOUSING AN ASSEMBLY |
| | OCCUPANCY ESTABLISHED PRIOR TO THE EFFECTIVE DATE OF |
| | THIS CODE SHALL BE PERMITTED TO BE APPROVED FOR |
| | CONTINUED USE IF IT CONFORMS TO, OR IS MADE TO CONFORM |
| | TO, THE PROVISIONS OF THIS CODE TO THE EXTENT THAT, IN |
| | THE OPINION OF THE AUTHORITY HAVING JURISDICTION, |
| | REASONABLE LIFE SAFETY AGAINST THE HAZARDS OF FIRE, |
| | EXPLOSION, AND PANIC IS PROVIDED AND MAINTAINED. |
| | 13.1.1.5 ADDITIONS TO EXISTING BUILDINGS SHALL CONFORM |
| | TO THE REQUIREMENTS OF 4.6.7. |
| | 13.1.1.6 EXISTING PORTIONS OF BUILDINGS SHALL BE |
| | UPGRADED IF THE ADDITION RESULTS IN AN INCREASE IN THE |
| | REQUIRED MINIMUM NUMBER OF SEPARATE MEANS OF EGRESS IN |
| | ACCORDANCE WITH 7.4.1.2. |
| | |
| | THE ALTERANTIVES NEED TO BE IN BUILDING DRAWING AND |
| | NARRATIVE FORM FOR CLARIFICATION PURPOSES. |
| | |
| | |
| | |
| | |
| | 2) THE SUBMITTED PLANS INDCATE AN OCCUPANCY LOAD OF |
| | 292, HOWEVER, ACTUAL SQ FT CALCULATINS INDICATE OVER |
| | 300. |
| | |
| | 13.3.4 DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS. |
| | 13.3.4.1 GENERAL. |
| | 13.3.4.1.1 ASSEMBLY OCCUPANCIES WITH OCCUPANT LOADS OF |
| | MORE THAN 300 AND ALL THEATERS WITH MORE THAN ONE |
| | AUDIENCE-VIEWING ROOM SHALL BE PROVIDED WITH AN |
| | APPROVED FIRE ALARM SYSTEM IN ACCORDANCE WITH 9.6.1 AND |
| | 13.3.4, UNLESS OTHERWISE PERMITTED BY 13.3.4.1.2, |
| | 13.3.4.1.3, OR 13.3.4.1.4. |
| | |
| | PLEASE PROVIDE FOR THE REQUIREMENT OR JUSTIFY SPECIFIC |
| | ALTENRATIVES FOR CONSIDERATION PER: |
| | |
| | 13.3.4.1.4 THE REQUIREMENT OF 13.3.4.1.1 SHALL NOT |
| | APPLY TO ASSEMBLY OCCUPANCIES WHERE, IN THE JUDGMENT OF |
| | THE AUTHORITY HAVING JURISDICTION, ADEQUATE ALTERNATIVE |
| | PROVISIONS EXIST OR ARE PROVIDED FOR THE DISCOVERY OF A |
| | FIRE AND FOR ALERTING THE OCCUPANTS PROMPTLY. |
| | |
| | THE ALTERANTIVES NEED TO BE IN BUILDING DRAWING AND |
| | NARRATIVE FORM FOR CLARIFICATION PURPOSES. |
| | |
| | |
| | |
| | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |
| | |