Plan Review Notes
Plan Review Notes For Permit 17120197
Permit Number 17120197
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2017-12-18 14:56:53THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THE SUBMITTED PLANS INDCATE AN OCCUPANCY LOAD OF
 292, HOWEVER, ACTUAL SQ FT CALCULATINS INDICATE OVER
 300.
  
 PER NFPA 101, CHAPTER 13, EXISTING ASSEMBLY OCCUPANCIES
 A FIRE SPRINKLER SYSTEM IS REQUIRED.
  
 13.3.5 EXTINGUISHMENT REQUIREMENTS. SEE ALSO 13.1.6,
 13.2.6, AND 13.3.2.
 13.3.5.1 WHERE THE OCCUPANT LOAD EXCEEDS 100 300, THE
 FOLLOWING ASSEMBLY OCCUPANCIES SHALL BE PROTECTED
 THROUGHOUT BY AN APPROVED, SUPERVISED AUTOMATIC
 SPRINKLER SYSTEM IN ACCORDANCE WITH 9.7.1.1(1):
 (1) DANCE HALLS
 (2) DISCOTHEQUES
 (3) NIGHTCLUBS
 (4) ASSEMBLY OCCUPANCIES WITH FESTIVAL SEATING
  
 PLEASE PROVIDE FOR THE REQUIREMENT OR JUSTIFY SPECIFIC
 ALTENRATIVES FOR CONSIDERATION PER:
  
  
 13.1.1.4 AN EXISTING BUILDING HOUSING AN ASSEMBLY
 OCCUPANCY ESTABLISHED PRIOR TO THE EFFECTIVE DATE OF
 THIS CODE SHALL BE PERMITTED TO BE APPROVED FOR
 CONTINUED USE IF IT CONFORMS TO, OR IS MADE TO CONFORM
 TO, THE PROVISIONS OF THIS CODE TO THE EXTENT THAT, IN
 THE OPINION OF THE AUTHORITY HAVING JURISDICTION,
 REASONABLE LIFE SAFETY AGAINST THE HAZARDS OF FIRE,
 EXPLOSION, AND PANIC IS PROVIDED AND MAINTAINED.
 13.1.1.5 ADDITIONS TO EXISTING BUILDINGS SHALL CONFORM
 TO THE REQUIREMENTS OF 4.6.7.
 13.1.1.6 EXISTING PORTIONS OF BUILDINGS SHALL BE
 UPGRADED IF THE ADDITION RESULTS IN AN INCREASE IN THE
 REQUIRED MINIMUM NUMBER OF SEPARATE MEANS OF EGRESS IN
 ACCORDANCE WITH 7.4.1.2.
  
 THE ALTERANTIVES NEED TO BE IN BUILDING DRAWING AND
 NARRATIVE FORM FOR CLARIFICATION PURPOSES.
  
  
  
  
 2) THE SUBMITTED PLANS INDCATE AN OCCUPANCY LOAD OF
 292, HOWEVER, ACTUAL SQ FT CALCULATINS INDICATE OVER
 300.
  
 13.3.4 DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS.
 13.3.4.1 GENERAL.
 13.3.4.1.1 ASSEMBLY OCCUPANCIES WITH OCCUPANT LOADS OF
 MORE THAN 300 AND ALL THEATERS WITH MORE THAN ONE
 AUDIENCE-VIEWING ROOM SHALL BE PROVIDED WITH AN
 APPROVED FIRE ALARM SYSTEM IN ACCORDANCE WITH 9.6.1 AND
 13.3.4, UNLESS OTHERWISE PERMITTED BY 13.3.4.1.2,
 13.3.4.1.3, OR 13.3.4.1.4.
  
 PLEASE PROVIDE FOR THE REQUIREMENT OR JUSTIFY SPECIFIC
 ALTENRATIVES FOR CONSIDERATION PER:
  
 13.3.4.1.4 THE REQUIREMENT OF 13.3.4.1.1 SHALL NOT
 APPLY TO ASSEMBLY OCCUPANCIES WHERE, IN THE JUDGMENT OF
 THE AUTHORITY HAVING JURISDICTION, ADEQUATE ALTERNATIVE
 PROVISIONS EXIST OR ARE PROVIDED FOR THE DISCOVERY OF A
 FIRE AND FOR ALERTING THE OCCUPANTS PROMPTLY.
  
 THE ALTERANTIVES NEED TO BE IN BUILDING DRAWING AND
 NARRATIVE FORM FOR CLARIFICATION PURPOSES.
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709