Plan Review Notes
Plan Review Notes For Permit 17120197
Permit Number 17120197
Review Stop B
Sequence Number 1
Notes
Date Text
2017-12-12 14:40:39BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16050779
 ADD: 2161PALM BEACH LAKES BLVD 1ST FLOOR
 CONT: ALL PHASE CONSTRUCTION
 TEL: 561-723-8246
 E-MAIL:[email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. DEC. 12/2017
 ACTION: DENIED
  
 1) SHEET C-1 THE COVERSHEET HAS A INDEX, MISSING
 SHEETS:
 SHEETS 1.1A EQUIPMENT PLAN & SCHEDULE MISSING IN BOTH
 SETS.
 SHEET 1.5A SECTIONS & DETAILS
 SHEET 1.7A REFLECTED CEILING PLAN
  
 2) SHEET C-1 THE COVERSHEET LIST INTERIOR SEATING AND
 EXTERIOR SEATING AS 292 SEATS. SHEET 1.4A WHEN YOU
 TOTAL UP ALL OF THE SEATING THE COUNT IS 343 SEATS NOT
 COUNTING THE OCCUPANT LOAD IN THE VIDEO GAMES AND
 BILLIARD AREA NOT THE KITCHEN AREA, BEHIND THE BARS(
 WORK AREAS) NOR FOR STORAGE AREAS, PLEASE PROVIDE THE
 SQUARE FEET FOR EACH OF THESE AREAS AND THE OCCUPANT
 LOADS BASED FROM FBC-B TABLE 1004.1.2. SHEET A1.4 THE
 LIFE SAFETY SHEET LIST A OCCUPANT LOAD A LOT LESS THAN
 THE SEATING COUNT FOUND ON THE COVER SHEET. 107.2.1.3
 ADDITIONAL INFORMATION IS REQUIRED.
  
 3) SHEET C-1 THE COVERSHEET ALSO INDICATES THIS IS A
 LEVEL II ALTERATION. THE 2014 FBC-EXISTING BUILDING
 CODE. AUTOMATIC SPRINKLER SYSTEMS SHALL BE PROVIDED IN
 ALL WORK AREAS WHEN REQUIRED BY SECTION 804.2 OR THIS
 SECTION. THE EXISTING BUILDING CODE SECTION 804.2.2
 GROUP A OCCUPANCY. WILL REQUIRE AUTOMATIC SPRINKLER
 PROTECTION WHERE ALL OF THE FOLLOWING CONDITIONS OCCUR:
 1. THE WORK AREA IS REQUIRED TO BE PROVIDED WITH
 AUTOMATIC SPRINKLER PROTECTION IN ACCORDANCE WITH THE
 FLORIDA BUILDING CODE, BUILDING AS APPLICABLE TO NEW
 CONSTRUCTION; AND
 2. THE WORK AREA EXCEEDS 50 PERCENT OF THE FLOOR AREA.
  
 4) SHEET 1.4A THE LIFE SAFETY SHEET:
  
 4A) THE MAIN ENTRY THERE IS EMERGENCY POWERED EXIT
 LIGHTING BUT TO THE LEFT OF THIS AREA THERE IS A LARGE
 DINING AREA AND THE NORTH AND SOUTH EXTERIOR DINING
 AREAS ARE WITHOUT ANY EMERGENCY POWERED BACKUP LIGHTS.
 PLEASE PROVIDE COMPLIANCE WITH FBC-B 1006.1 AND 1011.1
 WHERE EXITS SIGNS ARE REQUIRED.
  
 4B) PLEASE SHOW HOW MANY AND WHICH OF THE EXITS HAVE
 LEVEL EXIT DISCHARGES TO THE PUBLIC WAY. MEANING THERE
 ARE NO DROPS IN ELEVATION OVER 1/4 INCH OR THERE IS
 SLOPED OR RAMPED SIDEWALKS, DROPPED CURB CUTS ETC...
 2014 FBC-ACCESSIBILITY CODE IN ADDITION TO ENTRANCES
 REQUIRED BY 206.4.2 THROUGH 206.4.9, AT LEAST 60
 PERCENT OF ALL PUBLIC ENTRANCES SHALL COMPLY WITH 404.
 BARRIERS AT COMMON OR EMERGENCY ENTRANCES AND EXITS OF
 BUSINESS ESTABLISHMENTS CONDUCTING BUSINESS WITH THE
 GENERAL PUBLIC THAT ARE EXISTING, UNDER CONSTRUCTION,
 OR UNDER CONTRACT FOR CONSTRUCTION WHICH WOULD PREVENT
 A PERSON FROM USING SUCH ENTRANCES OR EXITS SHALL BE
 REMOVED.
  
 4C) THE OCCUPANT LOAD OF THE NORTH EXTERIOR SEATING
 AREA EXCEEDS 50 OCCUPANTS REQUIRING 2 MEANS OF EGRESS.
 2014 EBC-B TABLE 1015.1.
 PLEASE NOTE WITH A NON-SPRINKLERED BUILDING THE EXITS
 NEED TO BE 1/2 THE OVERALL DIAGONAL DISTANCE APART.
 2014 FBC-B 1015.2.1. SPRINKLERED 1/3RD THE DIAGONAL
 DISTANCE APART.
  
 4D) NEITHER SHEET 1.2A NOR 1.4A SHOW COMPLIANCE WITH
 COMPLIANCE WITH 2014 FBC-ACCESS. CODE 226.1. WHERE
 DINING SURFACES ARE PROVIDED FOR THE CONSUMPTION OF
 FOOD OR DRINK, AT LEAST 5 PERCENT OF THE SEATING SPACES
 AND STANDING SPACES AT THE DINING SURFACES SHALL COMPLY
 WITH 902. THE COVERSHEET LIST 292 SEATS X 0.05 = 15
 ACCESSIBLE SEATS.
 ACTUAL SEATING COUNT OF 343 X 0.05 = 18 ACCESSIBLE
 SEATS.
  
 4E) PLEASE NOTE COMPLIANCE WITH ACCESS. CODE 226.2
 DISPERSION. DINING SURFACES AND WORK SURFACES REQUIRED
 TO COMPLY WITH 902 SHALL BE DISPERSED THROUGHOUT THE
 SPACE OR FACILITY CONTAINING DINING SURFACES AND WORK
 SURFACES.
  
 4F)SHOW COMPLIANCE WITH FBC-ACCESS. CODE 902.1DINING
 SURFACES AND WORK SURFACES SHALL COMPLY WITH 902.2 AND
 902.3.
  
 4F)(1) FBC-ACCESS. 902.2 CLEAR FLOOR OR GROUND SPACE. A
 CLEAR FLOOR SPACE COMPLYING WITH 305 POSITIONED FOR A
 FORWARD APPROACH SHALL BE PROVIDED. KNEE AND TOE
 CLEARANCE COMPLYING WITH 306 SHALL BE PROVIDED.
  
 4F)(2) FBC-ACCESS. 902.3 HEIGHT. THE TOPS OF DINING
 SURFACES SHALL BE 28 INCHES AND 34 INCHES MAXIMUM ABOVE
 THE FINISH FLOOR OR GROUND.
  
 5A) SHEET 1.2A NOTE 10 INDICATES THE REMOVAL AND
 REPLACEMENT OF EXTERIOR SLIDING GLASS DOORS. PLEASE
 PROVIDE THE MEAN ROOF HEIGHT FOR THE BUILDING. PLEASE
 ALSO PROVIDE THE PRESSURES IN VASD. PLEASE SHOW
 COMPLIANCE WITH:
  
 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS
 (B) WINDOWS
  
 5B) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 6) PLEASE PROVIDE A LIST HOW UP TO AN ADDITIONAL
 $24,000.00 DOLLARS WILL BE SPENT IN ACCESSIBLE
 UPGRADES. 2014 FBC-ACCESS. CODE 202.4.1
 DISPROPORTIONATE COST.
 ALTERATIONS MADE TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL TO THE ALTERED AREA WILL BE DEEMED
 DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE
 COST EXCEEDS 20% OF THE COST OF THE ALTERATION TO THE
 PRIMARY FUNCTION AREA. COSTS THAT MAY BE COUNTED AS
 EXPENDITURES REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL MAY INCLUDE: (I) COSTS ASSOCIATED WITH PROVIDING
 AN ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUTE TO THE
 ALTERED AREA; (II) COSTS ASSOCIATED WITH MAKING
 RESTROOMS ACCESSIBLE, SUCH AS INSTALLING GRAB BARS,
 ENLARGING TOILET STALLS, INSULATING PIPES, OR
 INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COSTS
 ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH
 AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT,
 INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT
 TELEPHONE (TTY); (IV) COSTS ASSOCIATED WITH RELOCATING
 AN INACCESSIBLE DRINKING FOUNTAIN.
  
 12/ 18/2017
 PLEASE REVIEW E-MAIL SENT TO PETE RUSSO:
 GOOD MORNING PETE,
 I JUST WANTED TO RECAP OUR CONVERSATION TODAY AND THE
 POINTS MR. BROWN WANTED TO SEE IN THE NEXT REVIEW
 CYCLE. THE TENANT ON THE 1ST FLOOR DOES HAVE A OCCUPANT
 LOAD OVER 300. ROBERT WAS OK IN NOT FIRE SPRINKLERING
 THE TENANT SPACE IF THE PLANS SHOW THE OCCUPANTS ON THE
 NORTH AND SOUTH EXTERIOR SPACES & BARS WOULD NOT HAVE
 TO GO BACK INSIDE THE MAIN BUILDING BUT EXIT THROUGH
 THE 2 EXITS DIRECTLY TO THE EXTERIOR OF THE BUILDING
 WITHIN THE NORTH AND SOUTH OPEN AREAS. THAT SINCE THE
 OCCUPANT LOAD ON BOTH SIDES HAD AN OCCUPANT LOAD OF 50
 OR MORE, THAT FOR BOTH SIDES THERE WOULD BE (2) EXITS
 DIRECTLY TO THE EXTERIOR. TO NOTE ON THE PLANS THAT
 BOTH THE NORTH AND SOUTH AREAS ARE OPEN TO THE EXTERIOR
 TO ALLOW PARTICLES OF SMOKE TO DISSIPATE QUICKLY THE
 ONLY BARRIERS ON THE 2 EXTERIOR AREAS BEING GRILLE WORK
 FOR SECURITY. WITH THIS INFORMATION ADDED TO THE PLANS
 BUILDING WOULD BE ABLE TO PASS THE REVIEW WITHOUT THE
 ADDITION OF FIRE SPRINKLERS.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
 202.4.2 ACCESSIBLE FEATURES IN THE EVENT OF
 DISPROPORTIONALITY. WHEN THE COST OF ALTERATIONS
 NECESSARY TO MAKE THE PATH OF TRAVEL TO THE ALTERED
 AREA FULLY ACCESSIBLE IS DISPROPORTIONATE TO THE COST
 OF THE OVERALL ALTERATION, THE PATH OF TRAVEL SHALL BE
 MADE ACCESSIBLE TO THE EXTENT THAT IT CAN BE MADE
 ACCESSIBLE WITHOUT INCURRING DISPROPORTIONATE COSTS. IN
 CHOOSING WHICH ACCESSIBLE ELEMENTS TO PROVIDE, PRIORITY
 SHOULD BE GIVEN TO THOSE ELEMENTS THAT WILL PROVIDE THE
 GREATEST ACCESS, IN THE FOLLOWING ORDER: (I) AN
 ACCESSIBLE ENTRANCE; (II) AN ACCESSIBLE ROUTE TO THE
 ALTERED AREA; (III) AT LEAST ONE ACCESSIBLE RESTROOM
 FOR EACH SEX OR A SINGLE UNISEX RESTROOM; (IV)
 ACCESSIBLE TELEPHONES; (V) ACCESSIBLE DRINKING
 FOUNTAINS; AND (VI) WHEN POSSIBLE, ADDITIONAL
 ACCESSIBLE ELEMENTS SUCH AS PARKING, STORAGE, AND
 ALARMS.
  
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  