| 2017-12-12 07:04:05 | 2014 FBC- BUILDING PLAN REVIEW |
| | W. P. B. REVISION: 17120154 |
| | W. P. B. PERMIT: 17060297 |
| | ADD: 222 LAKEVIEW AVE. UNIT: 3N |
| | CONT: PUTTITIELLO BUILDERS, LLC / CBCA37998 |
| | TEL: 561-718-4176 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: MON. DEC. 11/2017 |
| | ACTION: DENIED |
| | |
| | 1) PLEASE REVIEW THE ORIGINAL STAMPED CITY SET OF |
| | PLANS. SHEET LS- 1. THE ORIGINAL BUILDING CODE ANALYSIS |
| | INDICATES THIS 20 STORY BUILDING BEING CLASSIFIED AS |
| | BUILDING TYPE I-A. THE SUBMITTED SHEET A-6 DETAIL |
| | INFILL DETAIL FLOOR FRAMING @ FLOOR 20, SHOWS THE USE |
| | OF 2 X 6 PRESSURE TREATED FRAMING MEMBERS, FLOOR |
| | SUBFLOOR NOR FINISH FLOOR DECK IS NOT MENTIONED. THE |
| | 2014 FBC-B TABLE 601 NOR SECTION 603.1 ALLOWABLE |
| | COMBUSTIBLE MATERIALS IN TYPE I BUILDINGS NOR FIRE |
| | RETARDENT TREATED MATERIALS ARE ALLOWED AS FLOOR |
| | FRAMING MEMBERS OR FLOOR CONSTRUCTION OR SECONDARY |
| | MEMBERS. PLEAASE PROVIDE A STRUCTURAL FRAME AND |
| | NON-COMBUSTIBLE FLOOR SYSTEM FOR THE INFILL FLOOR AREA |
| | ON THE 20TH FLOOR. |
| | |
| | 2) THERE IS ANOTHER AREA OF CONCERN, THE PLANS DRAWN BY |
| | BOWDOIN HUTCHINSON INDICATE THIS ELEVATOR WILL REQUIRE |
| | A 1 3/4 INCH RECESS IN THE 18TH FLOOR SLAB, PLEASE |
| | PROVIDE WHAT TYPE OF SLAB THIS IS AND HOW WILL THE |
| | RECESS BE CREATED? WILL THIS ALSO AFFECT THE FLOOR FIRE |
| | RATINGS ON THIS FLOOR? 107.2.1.3 ADDITIONAL INFORMATION |
| | IS REQUIRED. |
| | |
| | 3) THE THIRD AREA OF CONCERN IS THE UNKNOWN WALL SYSTEM |
| | THAT IS BETWEEN THE STAIRS AND THE NEW PROPOSED |
| | ELEVATOR THAT THE ELEVATORS RAIL SYSTEM WILL BE |
| | ANCHORING INTO. THIS WALL SYSTEM APPEARS TO RISE 3 |
| | FLOORS WITHOUT ANY HORIZONTAL SUPPORT. THE INFIL DETAIL |
| | FOUNDL ON SHEET A6 SHOWS JUST A COLUMN SIZE NOT KNOWN, |
| | NOR THE OTHER MEMBERS THAT MAKE UP THIS WALL. 107.2.1.3 |
| | ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | |
| | |
| | 3) PLEASE BE AWARE DEPENDING ON THE COMMENTS LISTED |
| | ABOVE THE CITY MAY ENVOKE THE REQUIREMENTS FOR A |
| | THRESHOLD INSPECTOR. I HAVE TAKEN THIS JOB TO THE |
| | BUILDING OFFICIAL TO SEE IF HE WOULD REQUIRE A |
| | THRESHOLD INSPECTOR FOR THE WORK BEING PREFORMED, THERE |
| | IS NOT ENOUGH INFORMATION CURRENTLY TO MAKE THIS |
| | DETERMINATION. IF REQUIRED THEN SEE THE REQUIREMENTS |
| | LISTED BELOW: |
| | |
| | PLEASE NOTE THIS IS A THRESHOLD BUILDING AND THE |
| | CONTRACTOR THAT IS APPLYING FOR THE REVISION IS A |
| | LICENSED CBC. 2014 FLORIDA BUILDING CODE W 2014 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1, ADMINISTRATION 110.3.7.5 NO ENFORCING AGENCY |
| | MAY ISSUE A BUILDING PERMIT FOR CONSTRUCTION OF ANY |
| | THRESHOLD BUILDING EXCEPT TO A LICENSED GENERAL |
| | CONTRACTOR, AS DEFINED IN SECTION 489.105(3)(A), |
| | FLORIDA STATUTES, OR TO A LICENSED BUILDING CONTRACTOR, |
| | AS DEFINED IN SECTION 489. 105(3)(B), FLORIDA STATUTES, |
| | WITHIN THE SCOPE OF HER OR HIS LICENSE. THE NAMED |
| | CONTRACTOR TO WHOM THE BUILDING PERMIT IS ISSUED SHALL |
| | HAVE THE RESPONSIBILITY FOR SUPERVISION, DIRECTION, |
| | MANAGEMENT AND CONTROL OF THE CONSTRUCTION ACTIVITIES |
| | ON THE PROJECT FOR WHICH THE BUILDING PERMIT WAS |
| | ISSUED. |
| | |
| | THRESHOLD BUILDING / FL S. S. 553.71(7) ?THRESHOLD |
| | BUILDING" MEANING ANY BUILDING WHICH IS GREATER THAN |
| | (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH HAS AN |
| | ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN THE |
| | FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. IN |
| | AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500 |
| | PERSONS. |
| | |
| | 3A) 109.3.6.1 THRESHOLD INSPECTION PLAN. THE ENFORCING |
| | AGENCY SHALL REQUIRE A (WRITTEN/ TYPED) SPECIAL |
| | INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A |
| | THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION |
| | PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL |
| | INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING |
| | AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR |
| | THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE |
| | OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE |
| | SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT |
| | THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE |
| | WITH THE PERMITTED DOCUMENTS. |
| | |
| | 3B) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B. |
| | CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD |
| | BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S S |
| | 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS |
| | REQUIRED BY THIS CODE. THE THRESHOLD INSPECTION FORMS |
| | ARE REQUIRED TO BE FILED OUT BY ALL PARTIES WITH |
| | INTEREST, NOTARIZED AND RETURNED TO THIS OFFICE, AND |
| | REVIEWED AND APPROVED BEFORE PERMIT ISSUANCE WILL TAKE |
| | PLACE. |
| | |
| | 3C) THRESHOLD BLDG., REQUIRED STATEMENT: W.P.B. |
| | AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING WHICH |
| | ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT |
| | OR ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE |
| | BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE |
| | PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE |
| | FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL |
| | AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633 |
| | FLORIDA STATUTE. |
| | |
| | 3D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME' |
| | OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE |
| | RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS |
| | SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE |
| | WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED, |
| | AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES |
| | WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST |
| | MEETING THE ABOVE CRITERIA. |
| | |
| | 3E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR |
| | HISTORY FOR THIS TYPE OF CONSTRUCTION. |
| | |
| | 3F) NOTE FOR PAPER PLANS 3 SETS OF DOCUMENTS ARE |
| | REQUIRED. FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE, |
| | PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE PERMIT BEING |
| | ISSUED, THE PERMIT LIBRARIAN WILL THEN E-MAIL YOU THE |
| | APPROVED AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR |
| | PLANS, TWO SETS OF PLANS WILL NEED TO BE PRINTED IN |
| | COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE OTHER FOR |
| | THE MEP INSPECTORS OTHER PLANS YOU WISH TO PRINT MAYBE |
| | IN BLACK & WHITE.. |
| | 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION, 110.3.7 THRESHOLD |
| | BUILDINGS, GUIDELINES AND POLICIES FOR PROJECTS |
| | CONCERNING SPECIAL INSPECTORS. |
| | |
| | 3G) 110.3.7.4.3 ALL SHORING AND RESHORING PROCEDURES, |
| | PLANS AND DETAILS SHALL BE SUBMITTED TO THE ENFORCEMENT |
| | AGENCY FOR RECORDKEEPING. EACH SHORING AND RESHORING |
| | INSTALLATION SHALL BE SUPERVISED, INSPECTED AND |
| | CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING |
| | DOCUMENTS BY THE CONTRACTOR. |
| | |
| | 3H) PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED |
| | TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR ALL |
| | BUILDING INSPECTIONS FOR AUDITING OF JOBSITE |
| | INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN 6 |
| | MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY. |
| | |
| | 4) THE 8 1/2 X 11 INCH DRAWINGS SUBMITTED FROM |
| | SOUTHEAST ELEVATOR SHOW A 1 3/4 INCH RECESS IN THE |
| | SLAB. THE DESIGNER OF RECORD WILL ALSO NEED TO |
| | ENCORPORATE HOW A 1 3/4 INCH RECESS OR FLOOR TRANSITION |
| | WILL BE MADE. 107.2.1.3 ADDITIONAL INFORMATION IS |
| | REQUIRED. |
| | |
| | 5) THE PLANS SUBMITTED FROM SOUTHEAST ELEVATOR INDICATE |
| | THIS IS A HYDROLIC ELEVATOR, IF SO PLEASE PROVIDE WHAT |
| | TYPE OF UNIT IS TO BE INSTALLED, DOES THIS UNIT WORK ON |
| | A SCREW ACTION? HYDROLIC PISTON? 107.2.1.3. |
| | |
| | 6) THE ARCHITECTS PLANS ON SHEETS A1 AND A6 BOTH SHOW |
| | ON THE 18TH FLOOR IN A STORAGE ROOM UNDER THE STAIRWAY |
| | WHERE THE HYDROLIC PUMP WILL BE LOCATED. PLEASE NOTE |
| | FIRE RATING REQUIRED FOR ENCLOSURES UNDER STAIRS. 2014 |
| | FBC-B 1009.9.4 ENCLOSURES UNDER EXTERIOR STAIRWAYS. |
| | THERE SHALL BE NO ENCLOSED USABLE SPACE UNDER EXTERIOR |
| | EXIT STAIRWAYS UNLESS THE SPACE IS COMPLETELY ENCLOSED |
| | IN 1-HOUR FIRE-RESISTANCE-RATED CONSTRUCTION. PLEASE |
| | ALSO PROVIDE THE DOOR RATING FOR THIS SPACE. 2014 FBC-B |
| | TABLE 716.5. |
| | |
| | 7) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER BN, PX, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |