Plan Review Notes
Plan Review Notes For Permit 17120118
Permit Number 17120118
Review Stop P
Sequence Number 2
Notes
Date Text
2018-01-04 08:38:212ND REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. YOU ARE ELIMINATING TWO WATER HEATERS AND STATING
 THAT A THIRD EXISTING WATER HEATER WILL BE USED TO
 SUPPLY ALL HOT WATER PLEASE SHOW LOCATION OF EXISTING
 HEATER THAT IS REMAINING. PER WPB AMEND TO FBC 107.2.1
  
 2. IF ANY PLEASE SHOW ANY NEW HOT WATER PIPING PROVIDE
 ISOMETRIC DIAGRAM. . PER WPB AMEND TO FBC
 107.3.5.1.3(13)
  
 3. IF NEW HIT WATER PIPING IS OVER 50' A RECIRCULATION
 HOT WATER SYSTEM IS REQUIRED. PER FBC PL 607.2
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  