| 2017-12-06 07:25:59 | 2014 FBC- BUILDING PLAN REVIEW |
| | W. P. B. REVISION: 17120118 |
| | W. P. B. PERMIT: 17050118 |
| | ADD: 4420 BEACON CIRCLE |
| | CONT: DWW CONSTRUCTION INC. |
| | TEL: 772-215-2794 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: WED. DEC. 06/2017 |
| | ACTION: DENIED |
| | |
| | 1) THE REVISION SHEET, SHEET # 2 DOES NOT HAVE THE |
| | REVISIONS INDICATED WITH BUBBLE OR DELTAS. THE REVISION |
| | REQUEST PLAN REVIEW FORM LIST THE DESCRIPTION OF WORK. |
| | THIS FORM DOES NOT STATE THERE ARE INTERIOR REVISIONS |
| | AS WELL. 107.2.1.3 ADDITIONAL INFORMATION REQUIRED ON |
| | PLANS WHERE THE REVISIONS ARE LOCATED. |
| | |
| | 2) SHEET # 2 SHOWS INTERIOR REVISIONS THAT DELETE A |
| | RESTROOM AND WATER HEATER AND CLOSET. THERE WERE NO |
| | PLUMBING SHEETS OR DEMO SHEETS SHOWING THE REVISION. |
| | 107. 2.1.3. ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 3) SHEET # 2 IN THE HALLWAY BETWEEN THE (2) PROPOSED |
| | CUBICLES NOW SHOWS A NEW DOOR IN A PROPOSED 4 FOOT WIDE |
| | HALLWAY. 2014 EXISTING BUILDING CODE. 801.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, 2014 ACCESS. CODE 404.2.4 |
| | MANEUVERING CLEARANCES. MINIMUM MANEUVERING CLEARANCES |
| | AT DOORS AND GATES SHALL COMPLY WITH 404.2.4. |
| | MANEUVERING CLEARANCES SHALL EXTEND THE FULL WIDTH OF |
| | THE DOORWAY AND THE REQUIRED LATCH SIDE OR HINGE SIDE |
| | CLEARANCE. MISSING THE REQUIRED 18 INCHES LATCH SIDE OF |
| | DOOR FOR MANEUVERING CLEARANCE. |
| | |
| | 4) SHEET # 2 A NEW DOORWAY IN THE CORRIDOR BETWEEN THE |
| | 2 PROPOSED CUBICLES WILL NOW ALSO NEED DIRECTIONAL EXIT |
| | LIGHTING TO BE SHOWN ON SHEET # 3 THE ELECTRICAL PLAN. |
| | 2014 FBC-B 1011.1 WHERE REQUIRED. |
| | |
| | 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |