| Plan Review Notes For Permit 17120096 |
| Permit Number |
17120096 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2018-02-02 13:07:50 | 2ND REVIEW FBC-2014 MECHANICAL | | | PERMIT #17120096 | | | 2/2/18 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET M-1: THE OUTSIDE AIR CALCULATION IS INDICATING | | | 1204 CFMS REQUIRED FOR THE KARATE STUDIO AREA. BASED ON | | | THAT CALCULATION THE EXISTING 5-TON 2000 CFM SYSTEM | | | WHICH IS SUPPLYING MOST OF THE ROOM WOULD BE UNDERSIZED | | | TO CONDITION THAT HIGH PERCENTAGE OF OUTSIDE AIR. | | | PERCENTAGE OF OUTSIDE AIR TO SUPPLY AIR IS GENERALLY | | | AROUND 20 %. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|