2017-12-28 13:00:111ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. PROVIDE ISOMETRIC DRAWINGS FOR SANITARY AND WATER.
 PER WPB AMEND TO FBC 107.3.5.1.3(13)
  
 2. THE KITCHEN SINK IS REQUIRED TO DISCHARGE THROUGH A
 GREASE TRAP OR INTERCEPTOR. PER FBC PL 1003.3.1
  
 3. PLEASE PROVIDE MANUFACTURE SPECS FOR TANKLESS WATER
 HEATER. PER WPB AMEND TO FBC 107.2.1
  
 4. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES
 AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET
 FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND
 VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN
 APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT
 CONFORMS TO ASSE 1070 OR CSA B125.3. PER FBC PL 416.5
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  