2017-12-18 15:18:361ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17120096
 12/18/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE
 AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL
 ROOMS AND SPACES PER TABLE 403.3 FBC-14 MECHANICAL.
 PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND
 PROVIDED CFMS OF OUTDOOR AIR.
  
 2) PROVIDE OUTDOOR AIR SHUTOFF DAMPER CONTROLS FOR
 PACKAGE UNIT'S #1 & 2 IN COMPLIANCE WITH SECTION
 C403.2.4.4 FBC-14 ENERGY CONSERVATION.
  
 3) PROVIDE A DUCT SMOKE DETECTOR IN THE RETURN AIR
 SYSTEM OF AHU #3- SECTION 606.2.1.
  
 4) SHOW THE TOILET ROOM EXHAUST DUCT RUNS AND
 TERMINATION LOCATIONS- SECTION 501.3.1.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  