| 2017-12-06 11:54:52 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, |
| | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) SHEET A O - THERE IS AN INDICATION THAT THE BUILDING |
| | CONSTRUCTION IS A TYPE III UNSPRINKLED. SHEET F 2 |
| | INDICATES A FULLY SPRINKLED BUIDLING W/FIRE ALARM. |
| | |
| | PLEASE CLARIFY WHICH IS CORRECT AND UPDATE ACCORDINGLY. |
| | |
| | IF A FIRE SPRINKLER SYSTEM IS EXISITNG, PROVIDE A |
| | APPLICABLE CLOUDED NOTE INDICATING THAT "ALL FIRE |
| | SPRINKLER WORK SHALL BE DONE BY CERTIFIED FIRE |
| | SPRINKLER CONTRACTOR UNDER SEPARATE SHOP DRAWINGS". |
| | |
| | |
| | |
| | 2) SHEET F 2 - THERE IS AN INDICATION THAT A FIRE ALARM |
| | SYSTEM IS EXISTING. |
| | |
| | PLEASE CONFIRM WITH EXSITING DEVICES ON THE DEMO SHEET. |
| | |
| | IF A FIRE ALARM SYSTEM IS EXISITNG, PROVIDE A |
| | APPLICABLE CLOUDED NOTE INDICATING THAT "ALL FIRE ALARM |
| | WORK SHALL BE DONE BY CERTIFIED FIRE ALARM CONTRACTOR |
| | UNDER SEPARATE SHOP DRAWINGS". |
| | |
| | |
| | |
| | |
| | 3) SHEET A 1 - THERE IS AN INDICATION OF DBL OVEN IN |
| | THE MULT-IPURPOSE ROOM. |
| | |
| | PLEASE PROVIDE THE MANUFACTURES SPEC SHEETS INCLUDING |
| | ANY REQUIRED VENTING. |
| | |
| | PLEASE BE AWARE THAT PER NFPA 101, CHAPTER 12, NEW |
| | ASSEMBLY OCCUPANCIES: |
| | |
| | 12.3.2.2 COOKING EQUIPMENT. COOKING EQUIPMENT SHALL BE |
| | PROTECTED IN ACCORDANCE WITH 9.2.3, UNLESS THE COOKING |
| | EQUIPMENT IS ONE OF THE FOLLOWING TYPES: |
| | (1) OUTDOOR EQUIPMENT |
| | (2) PORTABLE EQUIPMENT NOT FLUE-CONNECTED |
| | (3) EQUIPMENT USED ONLY FOR FOOD WARMING |
| | |
| | 9.2.3 COMMERCIAL COOKING EQUIPMENT. COMMERCIAL COOKING |
| | EQUIPMENT SHALL BE IN ACCORDANCE WITH NFPA 96, STANDARD |
| | FOR VENTILATION CONTROL AND FIRE PROTECTION OF |
| | COMMERCIAL COOKING OPERATIONS, UNLESS SUCH |
| | INSTALLATIONS ARE APPROVED EXISTING INSTALLATIONS, |
| | WHICH SHALL BE PERMITTED TO BE CONTINUED IN SERVICE. |
| | |
| | PLEASE ALSO PROVIDE A NARRATIVE OF HOW THE MENU WILL BE |
| | CONTROLLED TO COMPLY WITH COMPLIANCE OF THE NOTED CODE |
| | REQUIREMENTS. |
| | |
| | |
| | |
| | |
| | 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |