Plan Review Notes
Plan Review Notes For Permit 17120096
Permit Number 17120096
Review Stop E
Sequence Number 1
Notes
Date Text
2017-12-20 15:50:52CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PLAN INCLUDES A BLOCK NOTE REFERENCING THE FBC
 RESIDENTIAL FOR ENERGY COMPLIANCE. THIS PROJECT IS NOT
 RESIDENTIAL, REMOVE ANY INFORMATION NOT RELEVANT TO
 THIS PROJECT. FBC 107.2.1
 2. PLAN INCLUDES A BLOCK NOTE REFERENCING SMOKE ALARMS
 IN DWELLING UNITS. REMOVE ANY INFORMATION NOT RELEVANT
 TO THIS PLAN. FBC 107.2.1
 3. PLAN NOTE STATES THIS INSTALLATION TO COMPLY WITH
 THE NEC 2014, WHICH IS NOT THE CURRENT CODE. PROVIDE
 CORRECTION. FBC PREFACE
 4. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF
 SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE,
 WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO INTERIOR
 PANEL. SHOW GEC SIZE AND SYSTEM, SHOW INTERSYSTEM
 BONDING TERMINATION POINT. NEC 215.5, 230, 250.50,
 250.94, 408.30
 5. PLAN SHOWS EMERGENCY AND EXIT LIGHTS ON CIRCUIT #
 31. EMERGENCY AND EXIT LIGHTS ARE REQUIRED TO BE FED
 FROM THE GENERAL LIGHTING CIRCUIT IN THE AREA. PROVIDE
 CORRECTION. NEC 700.12(F)
 6. PROVIDE SHOW WINDOW OUTLETS PER CODE. NEC 210.62
 7. PROVIDE DEDICATED CIRCUIT AND CONTROL FOR SIGN. NEC
 600.5; FBC EC 405.2.4
 8. PROVIDE GFCI PROTECTION FOR ALL RECEPTACLES LOCATED
 WITHIN 6 FEET OF A SINK. NEC 210.8
 9. PLAN DOES NOT SHOW ANY RECEPTACLE OUTLETS AT POS.
 HOW WILL THE COMPUTERS THERE RECEIVE POWER? FBC 107.2.1
 10. PROVIDE GRAPH/CALCULATION OF INTERIOR LIGHTING
 POWER ALLOWANCES PER THE FBC ENERGY CODE IN RELATION TO
 THE CONNECTED INTERIOR LIGHTING PROPOSED TO COMPLY WITH
 CODE. FBC EC 405.5.2
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  