| 2017-12-18 07:45:46 | 2014 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 17120096 |
| | ADD: 642 BELVEDERE RD. SUITE # ??? |
| | CONT: RCE GROUP, INC. |
| | TEL: 786-444-7134 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: FRI. DEC. 15/ 2017 |
| | ACTION: DENIED |
| | |
| | 1) THE PLANS DOES NOT PROVIDE A SUITE ADDRESS AND THE |
| | PERMIT APPLICATION INDICATES THE SUITE NUMBER AS 111. |
| | PLEASE NOTE THE SITE ADDRESS IS: 500 BELVEDERE ROAD, |
| | GOOGLE EARTH SHOWS THE TENANT SPACE AS UNIT :624. |
| | PLEASE CORRECT THE ADDRESS ON THE PLANS AS WELL AS THE |
| | PERMIT APPLICATION. |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION 107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF |
| | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| | EXTENT OF THE WORK PROPOSED. |
| | |
| | 2014 FBC-B 01.2 ADDRESS IDENTIFICATION. NEW AND |
| | EXISTING BUILDINGS SHALL BE PROVIDED WITH APPROVED |
| | ADDRESS IDENTIFICATION. |
| | |
| | 2) THE COVERSHEET A-0 UNDER THE HEADING ZONING DATA |
| | LIST THE BUILDING TYPE A TYPE III-UNSPRINKLERED |
| | BUILDING. ON SHEET F-2 THE TYPE OF CONSTRUCTION LISTED |
| | AS II-A FULLY SPRINKLERED. THERE IS A DISCREPANCY IN |
| | THE PLANS AS TO THE TYPE OF CONSTRUCTION AS WELL AS IF |
| | THE BUILDING IS FIRE SPRINKLERED? 107.2.1.3 ADDITIONAL |
| | INFORMATION IS REQUIRED. |
| | |
| | 3) THE COVERSHEET A-0 UNDER THE HEADING OCCUPANCY |
| | SEPARATION LIST FIRE SEPARATION REQUIRED N/A. |
| | SHEET F-2 INDICATES THE EXISTING TENANT SEPARATION |
| | WALLS AS EXISTING 2 HOUR WALLS. THERE IS A TENANT ON |
| | THE EAST SIDE AND PLEASE PROVIDE THE OCCUPANCY, PLEASE |
| | PROVIDE COMPLIANCE WITH THE 2014 FBC-B TABLE 508.4 FOR |
| | HOUR RATING, AND IF THE BUILDING IS SPRINKLERED OR NOT. |
| | |
| | 4) BOTH SHEETS A-0 THE COVERSHEET AND SHEET F-2 BOTH |
| | CLASSIFY THE ALTERATION AS A LEVEL III ALTERATION. |
| | PLEASE REVIEW THE 2014 EXISTING BUILDING CODE SECTION |
| | 505.1 SCOPE. LEVEL 3 ALTERATIONS APPLY WHERE THE WORK |
| | AREA EXCEEDS 50 PERCENT OF THE AGGREGATE AREA OF THE |
| | BUILDING. |
| | THE CODE STATES BUILDING NOT TENANT SPACE. THIS SPACE |
| | WAS A BAR/ RESTAURANT (A-2 OCCUPANCY) AND CONVERTED |
| | INTO A KARATE SCHOOL/ GYM (A-3 GYM). |
| | |
| | 2014 FBC-EXISTING BUILDING CODE 1001.2 CHANGE IN |
| | OCCUPANCY WITH NO CHANGE OF OCCUPANCY CLASSIFICATION. A |
| | CHANGE IN OCCUPANCY, AS DEFINED IN SECTION 202, WITH NO |
| | CHANGE OF OCCUPANCY CLASSIFICATION SHALL NOT BE MADE TO |
| | ANY STRUCTURE THAT WILL SUBJECT THE STRUCTURE TO ANY |
| | SPECIAL PROVISIONS OF THE APPLICABLE FLORIDA BUILDING |
| | CODES, INCLUDING THE PROVISIONS OF SECTIONS 1002 |
| | THROUGH 1011, WITHOUT THE APPROVAL OF THE CODE |
| | OFFICIAL. A CERTIFICATE OF OCCUPANCY SHALL BE ISSUED |
| | WHERE IT HAS BEEN DETERMINED THAT THE REQUIREMENTS FOR |
| | THE CHANGE IN OCCUPANCY HAVE BEEN MET. |
| | |
| | 1001.3.1 PARTIAL CHANGE OF OCCUPANCY CLASSIFICATION. |
| | WHERE A PORTION OF AN EXISTING BUILDING IS CHANGED TO A |
| | NEW OCCUPANCY CLASSIFICATION, SECTION 1012 SHALL APPLY. |
| | |
| | 5) BOTH SHEETS A-0 THE COVERSHEET AND SHEET F-2 HAVE |
| | INTERIOR FINISH SCHEDULE WITH A CLASS B INTERIOR WALL & |
| | CEILING FINISH- FLAME SPREAD OF 26- 75, AND SMOKE |
| | DEVELOPMENT OF 0- 450. PLEASE NOTE THIS IS FOR FIRE |
| | SPRINKLERED BUILDINGS. UNTIL COMMENT # 2 IS SATISFIED |
| | FOR FIRE SPRINKLERS THIS MAY BE CORRECT OR NOT. SEE |
| | 2014 FBC-B TABLE 803.9 |
| | |
| | 6) SHEET F-2 LIST IN THE FLOOR PLAN THE USE OF |
| | NULLIFIRE S606 PAINT TO BE APPLIED TO ALL EXPOSED ROOF |
| | STRUCTURAL SURFACES, BEING THIS IS LISTED AS EITHER |
| | TYPE IIA OR TYPE III UNSPRINKLERED. SEE TABLE 601 ROOF |
| | CONSTRUCTION AND ASSOCIATED SECONDARY MEMBERS. PLEASE |
| | PROVIDE HOW THE FIRE RATING WILL BE ACHIEVED, PROVIDE |
| | THE MANUFACTURERS RATE OF APPLICATION INSTRUCTIONS. |
| | |
| | 7) THE FLOOR PLAN F-2 SHOWS THE OFFICE DOOR AND BOTH |
| | RESTROOMS AS A DOOR LABEL IDENTIFICATION TAG AS TYPE A. |
| | ON THE FLOOR PLAN A-1 WITH THE DOOR SCHEDULE THESE |
| | DOORS ARE LISTED AS NUMBER 3 AND ALL 3 ARE 2 FEET- TEN |
| | INCHES WIDE. |
| | THE 2014 FBC-B SECTION 1008.1.1 SIZE OF DOORS REQUIRES |
| | A 3 FOOT WIDE DOOR. THE MINIMUM WIDTH OF EACH DOOR |
| | OPENING SHALL BE SUFFICIENT FOR THE OCCUPANT LOAD |
| | THEREOF AND SHALL PROVIDE A CLEAR WIDTH OF 32 INCHES. |
| | CLEAR OPENINGS OF DOORWAYS WITH SWINGING DOORS SHALL BE |
| | MEASURED BETWEEN THE FACE OF THE DOOR AND THE STOP WITH |
| | THE DOOR OPEN 90 DEGREES. WHERE THIS SECTION REQUIRES A |
| | MINIMUM CLEAR WIDTH OF 32 INCHES AND A DOOR OPENING |
| | INCLUDES TWO DOOR LEAVES WITHOUT A MULLION, ONE LEAF |
| | SHALL PROVIDE A CLEAR OPENING WIDTH OF 32 INCHES. |
| | |
| | 8) SHEET A-2 DETAIL # 2 SHOWS A WALL OVEN WITH THE |
| | CONTROLS ABOVE THE REACH RANGES FOR OPERABLE PARTS. |
| | WILL THIS OVEN BE USED FOR JUST EMPLOYEES OR EMPLOYEES |
| | AND GUEST? |
| | |
| | 2014 ACCESSIBILITY CODE. 308 REACH RANGES. 308.2 |
| | FORWARD REACH./ 308.2.1 UNOBSTRUCTED/ 308.2.2 |
| | OBSTRUCTED HIGH REACH. 308.3 SIDE REACH. / 308.3.1 |
| | UNOBSTRUCTED/ 308.3.2 OBSTRUCTED HIGH REACH. |
| | |
| | 2014 ACCESSIBILITY CODE. 309 OPERABLE PARTS. 309.3 |
| | HEIGHT. OPERABLE PARTS SHALL BE PLACED WITHIN ONE OR |
| | MORE OF THE REACH RANGES SPECIFIED IN 308. 309.4 |
| | OPERATION. OPERABLE PARTS SHALL BE OPERABLE WITH ONE |
| | HAND AND SHALL NOT REQUIRE TIGHT GRASPING, PINCHING, OR |
| | TWISTING OF THE WRIST. THE FORCE REQUIRED TO ACTIVATE |
| | OPERABLE PARTS SHALL BE 5 POUNDS (22.2 N) MAXIMUM. |
| | |
| | 2014 ACCESSIBILITY CODE ADVISORY 226.1. IN FACILITIES |
| | COVERED BY THE ADA, THIS REQUIREMENT DOES NOT APPLY TO |
| | WORK SURFACES USED ONLY BY EMPLOYEES. HOWEVER, THE ADA |
| | AND, WHERE APPLICABLE, SECTION 504 OF THE |
| | REHABILITATION ACT OF 1973, AS AMENDED, PROVIDE THAT |
| | EMPLOYEES ARE ENTITLED TO ?REASONABLE ACCOMMODATIONS.? |
| | WITH RESPECT TO WORK SURFACES, THIS MEANS THAT |
| | EMPLOYERS MAY NEED TO PROCURE OR ADJUST WORK STATIONS |
| | SUCH AS DESKS, LABORATORY AND WORK BENCHES, FUME HOODS, |
| | RECEPTION COUNTERS, TELLER WINDOWS, STUDY CARRELS, |
| | COMMERCIAL KITCHEN COUNTERS, AND CONFERENCE TABLES TO |
| | ACCOMMODATE THE INDIVIDUAL NEEDS OF EMPLOYEES WITH |
| | DISABILITIES ON AN ?AS NEEDED? BASIS. CONSIDER WORK |
| | SURFACES THAT ARE FLEXIBLE AND PERMIT INSTALLATION AT |
| | VARIABLE HEIGHTS AND CLEARANCES. |
| | |
| | 9) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. ONE SET OF |
| | PLANS WILL HAVE TO BE TAKEN (BY THE CONTRACTOR OR |
| | REPRESENTATIVE) TO THE PALM BEACH COUNTY IMPACT FEE |
| | OFFICE LOCATED AT 2300 N. JOG RD. ROOMS 2W01-2W14 WEST |
| | PALM BEACH, FL. THE ACTUAL PERMIT SET OF PLANS MUST BE |
| | STAMPED BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT |
| | ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL |
| | (561)233-5025 FOR MORE INFORMATION. |
| | |
| | 10) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| | AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |