Plan Review Notes For Permit 17120096
Permit Number 17120096
Review Stop B
Sequence Number 1
Notes
Date Text
2017-12-18 07:45:462014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17120096
 ADD: 642 BELVEDERE RD. SUITE # ???
 CONT: RCE GROUP, INC.
 TEL: 786-444-7134
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. DEC. 15/ 2017
 ACTION: DENIED
  
 1) THE PLANS DOES NOT PROVIDE A SUITE ADDRESS AND THE
 PERMIT APPLICATION INDICATES THE SUITE NUMBER AS 111.
 PLEASE NOTE THE SITE ADDRESS IS: 500 BELVEDERE ROAD,
 GOOGLE EARTH SHOWS THE TENANT SPACE AS UNIT :624.
 PLEASE CORRECT THE ADDRESS ON THE PLANS AS WELL AS THE
 PERMIT APPLICATION.
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED.
  
 2014 FBC-B 01.2 ADDRESS IDENTIFICATION. NEW AND
 EXISTING BUILDINGS SHALL BE PROVIDED WITH APPROVED
 ADDRESS IDENTIFICATION.
  
 2) THE COVERSHEET A-0 UNDER THE HEADING ZONING DATA
 LIST THE BUILDING TYPE A TYPE III-UNSPRINKLERED
 BUILDING. ON SHEET F-2 THE TYPE OF CONSTRUCTION LISTED
 AS II-A FULLY SPRINKLERED. THERE IS A DISCREPANCY IN
 THE PLANS AS TO THE TYPE OF CONSTRUCTION AS WELL AS IF
 THE BUILDING IS FIRE SPRINKLERED? 107.2.1.3 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 3) THE COVERSHEET A-0 UNDER THE HEADING OCCUPANCY
 SEPARATION LIST FIRE SEPARATION REQUIRED N/A.
 SHEET F-2 INDICATES THE EXISTING TENANT SEPARATION
 WALLS AS EXISTING 2 HOUR WALLS. THERE IS A TENANT ON
 THE EAST SIDE AND PLEASE PROVIDE THE OCCUPANCY, PLEASE
 PROVIDE COMPLIANCE WITH THE 2014 FBC-B TABLE 508.4 FOR
 HOUR RATING, AND IF THE BUILDING IS SPRINKLERED OR NOT.
  
 4) BOTH SHEETS A-0 THE COVERSHEET AND SHEET F-2 BOTH
 CLASSIFY THE ALTERATION AS A LEVEL III ALTERATION.
 PLEASE REVIEW THE 2014 EXISTING BUILDING CODE SECTION
 505.1 SCOPE. LEVEL 3 ALTERATIONS APPLY WHERE THE WORK
 AREA EXCEEDS 50 PERCENT OF THE AGGREGATE AREA OF THE
 BUILDING.
 THE CODE STATES BUILDING NOT TENANT SPACE. THIS SPACE
 WAS A BAR/ RESTAURANT (A-2 OCCUPANCY) AND CONVERTED
 INTO A KARATE SCHOOL/ GYM (A-3 GYM).
  
 2014 FBC-EXISTING BUILDING CODE 1001.2 CHANGE IN
 OCCUPANCY WITH NO CHANGE OF OCCUPANCY CLASSIFICATION. A
 CHANGE IN OCCUPANCY, AS DEFINED IN SECTION 202, WITH NO
 CHANGE OF OCCUPANCY CLASSIFICATION SHALL NOT BE MADE TO
 ANY STRUCTURE THAT WILL SUBJECT THE STRUCTURE TO ANY
 SPECIAL PROVISIONS OF THE APPLICABLE FLORIDA BUILDING
 CODES, INCLUDING THE PROVISIONS OF SECTIONS 1002
 THROUGH 1011, WITHOUT THE APPROVAL OF THE CODE
 OFFICIAL. A CERTIFICATE OF OCCUPANCY SHALL BE ISSUED
 WHERE IT HAS BEEN DETERMINED THAT THE REQUIREMENTS FOR
 THE CHANGE IN OCCUPANCY HAVE BEEN MET.
  
 1001.3.1 PARTIAL CHANGE OF OCCUPANCY CLASSIFICATION.
 WHERE A PORTION OF AN EXISTING BUILDING IS CHANGED TO A
 NEW OCCUPANCY CLASSIFICATION, SECTION 1012 SHALL APPLY.
  
 5) BOTH SHEETS A-0 THE COVERSHEET AND SHEET F-2 HAVE
 INTERIOR FINISH SCHEDULE WITH A CLASS B INTERIOR WALL &
 CEILING FINISH- FLAME SPREAD OF 26- 75, AND SMOKE
 DEVELOPMENT OF 0- 450. PLEASE NOTE THIS IS FOR FIRE
 SPRINKLERED BUILDINGS. UNTIL COMMENT # 2 IS SATISFIED
 FOR FIRE SPRINKLERS THIS MAY BE CORRECT OR NOT. SEE
 2014 FBC-B TABLE 803.9
  
 6) SHEET F-2 LIST IN THE FLOOR PLAN THE USE OF
 NULLIFIRE S606 PAINT TO BE APPLIED TO ALL EXPOSED ROOF
 STRUCTURAL SURFACES, BEING THIS IS LISTED AS EITHER
 TYPE IIA OR TYPE III UNSPRINKLERED. SEE TABLE 601 ROOF
 CONSTRUCTION AND ASSOCIATED SECONDARY MEMBERS. PLEASE
 PROVIDE HOW THE FIRE RATING WILL BE ACHIEVED, PROVIDE
 THE MANUFACTURERS RATE OF APPLICATION INSTRUCTIONS.
  
 7) THE FLOOR PLAN F-2 SHOWS THE OFFICE DOOR AND BOTH
 RESTROOMS AS A DOOR LABEL IDENTIFICATION TAG AS TYPE A.
 ON THE FLOOR PLAN A-1 WITH THE DOOR SCHEDULE THESE
 DOORS ARE LISTED AS NUMBER 3 AND ALL 3 ARE 2 FEET- TEN
 INCHES WIDE.
 THE 2014 FBC-B SECTION 1008.1.1 SIZE OF DOORS REQUIRES
 A 3 FOOT WIDE DOOR. THE MINIMUM WIDTH OF EACH DOOR
 OPENING SHALL BE SUFFICIENT FOR THE OCCUPANT LOAD
 THEREOF AND SHALL PROVIDE A CLEAR WIDTH OF 32 INCHES.
 CLEAR OPENINGS OF DOORWAYS WITH SWINGING DOORS SHALL BE
 MEASURED BETWEEN THE FACE OF THE DOOR AND THE STOP WITH
 THE DOOR OPEN 90 DEGREES. WHERE THIS SECTION REQUIRES A
 MINIMUM CLEAR WIDTH OF 32 INCHES AND A DOOR OPENING
 INCLUDES TWO DOOR LEAVES WITHOUT A MULLION, ONE LEAF
 SHALL PROVIDE A CLEAR OPENING WIDTH OF 32 INCHES.
  
 8) SHEET A-2 DETAIL # 2 SHOWS A WALL OVEN WITH THE
 CONTROLS ABOVE THE REACH RANGES FOR OPERABLE PARTS.
 WILL THIS OVEN BE USED FOR JUST EMPLOYEES OR EMPLOYEES
 AND GUEST?
  
 2014 ACCESSIBILITY CODE. 308 REACH RANGES. 308.2
 FORWARD REACH./ 308.2.1 UNOBSTRUCTED/ 308.2.2
 OBSTRUCTED HIGH REACH. 308.3 SIDE REACH. / 308.3.1
 UNOBSTRUCTED/ 308.3.2 OBSTRUCTED HIGH REACH.
  
 2014 ACCESSIBILITY CODE. 309 OPERABLE PARTS. 309.3
 HEIGHT. OPERABLE PARTS SHALL BE PLACED WITHIN ONE OR
 MORE OF THE REACH RANGES SPECIFIED IN 308. 309.4
 OPERATION. OPERABLE PARTS SHALL BE OPERABLE WITH ONE
 HAND AND SHALL NOT REQUIRE TIGHT GRASPING, PINCHING, OR
 TWISTING OF THE WRIST. THE FORCE REQUIRED TO ACTIVATE
 OPERABLE PARTS SHALL BE 5 POUNDS (22.2 N) MAXIMUM.
  
 2014 ACCESSIBILITY CODE ADVISORY 226.1. IN FACILITIES
 COVERED BY THE ADA, THIS REQUIREMENT DOES NOT APPLY TO
 WORK SURFACES USED ONLY BY EMPLOYEES. HOWEVER, THE ADA
 AND, WHERE APPLICABLE, SECTION 504 OF THE
 REHABILITATION ACT OF 1973, AS AMENDED, PROVIDE THAT
 EMPLOYEES ARE ENTITLED TO ?REASONABLE ACCOMMODATIONS.?
 WITH RESPECT TO WORK SURFACES, THIS MEANS THAT
 EMPLOYERS MAY NEED TO PROCURE OR ADJUST WORK STATIONS
 SUCH AS DESKS, LABORATORY AND WORK BENCHES, FUME HOODS,
 RECEPTION COUNTERS, TELLER WINDOWS, STUDY CARRELS,
 COMMERCIAL KITCHEN COUNTERS, AND CONFERENCE TABLES TO
 ACCOMMODATE THE INDIVIDUAL NEEDS OF EMPLOYEES WITH
 DISABILITIES ON AN ?AS NEEDED? BASIS. CONSIDER WORK
 SURFACES THAT ARE FLEXIBLE AND PERMIT INSTALLATION AT
 VARIABLE HEIGHTS AND CLEARANCES.
  
 9) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. ONE SET OF
 PLANS WILL HAVE TO BE TAKEN (BY THE CONTRACTOR OR
 REPRESENTATIVE) TO THE PALM BEACH COUNTY IMPACT FEE
 OFFICE LOCATED AT 2300 N. JOG RD. ROOMS 2W01-2W14 WEST
 PALM BEACH, FL. THE ACTUAL PERMIT SET OF PLANS MUST BE
 STAMPED BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL
 (561)233-5025 FOR MORE INFORMATION.
  
 10) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER