Plan Review Notes
Plan Review Notes For Permit 17120090
Permit Number 17120090
Review Stop B
Sequence Number 1
Notes
Date Text
2017-12-05 15:13:21RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- PROPOSED WORK IS NOT CLEAR. WORK DESCRIPTION ON THE
 PERMIT APPLICATION STATES "REPAIR OF SHINGLE ROOF".
 FLORIDA PRODUCT APPROVAL SUBMITTED IS FOR LOW SLOPE
 ROOFS NOT FOR SHINGLES. SCOPE OF WORK ON PERMIT
 APPLICATION AND PRODUCT APPROVALS NEED TO MATCH. REVISE
 AS REQUIRED. SEC. 107.2.1 CITY AMENDMENTS.
  
 2- IF THE PERCENTAGE OF ROOF AREA IS MORE THAN 25%,
 THEN THE TOTAL ROOF AREA NEEDS TO BE RE-ROOFED AS
 REQUIRED BY SEC. 708.1.1 FBC-EXISTING BUILDING, 5TH
 EDITION (2014). REVISE SCOPE OF WORK ON PERMIT
 APPLICATION TO READ RE-ROOF ENTIRE ROOF AREA.
  
 3- IF THE WORK IS FOR THE LOW SLOPE ROOF AREA, THEN
 CLEARLY MARK WHICH APPROVED ASSEMBLY FROM FLORIDA
 PRODUCT APPROVAL FL9487-R4 SUBMITTED IS GOING TO BE
 INSTALLED TO VERIFY COMPLIANCE WITH THE DESIGN
 PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL.
 NOTE: IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN
 PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED
 RAS 117 CALCULATIONS MAY BE REQUIRED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]