| 2017-12-05 15:13:21 | RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS. |
| | CODE: FBC 5TH EDITION (2014). |
| | |
| | 1- PROPOSED WORK IS NOT CLEAR. WORK DESCRIPTION ON THE |
| | PERMIT APPLICATION STATES "REPAIR OF SHINGLE ROOF". |
| | FLORIDA PRODUCT APPROVAL SUBMITTED IS FOR LOW SLOPE |
| | ROOFS NOT FOR SHINGLES. SCOPE OF WORK ON PERMIT |
| | APPLICATION AND PRODUCT APPROVALS NEED TO MATCH. REVISE |
| | AS REQUIRED. SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | 2- IF THE PERCENTAGE OF ROOF AREA IS MORE THAN 25%, |
| | THEN THE TOTAL ROOF AREA NEEDS TO BE RE-ROOFED AS |
| | REQUIRED BY SEC. 708.1.1 FBC-EXISTING BUILDING, 5TH |
| | EDITION (2014). REVISE SCOPE OF WORK ON PERMIT |
| | APPLICATION TO READ RE-ROOF ENTIRE ROOF AREA. |
| | |
| | 3- IF THE WORK IS FOR THE LOW SLOPE ROOF AREA, THEN |
| | CLEARLY MARK WHICH APPROVED ASSEMBLY FROM FLORIDA |
| | PRODUCT APPROVAL FL9487-R4 SUBMITTED IS GOING TO BE |
| | INSTALLED TO VERIFY COMPLIANCE WITH THE DESIGN |
| | PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL. |
| | NOTE: IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN |
| | PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED |
| | RAS 117 CALCULATIONS MAY BE REQUIRED. |
| | |