2017-12-12 11:28:32PERMIT # 17120071
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FAILED COMMENTS:
  
 1) ENGINEERED FIRE ALARM AND FIRE SPRINKLER
 CONSTRUCTION DOCUMENTS ARE REQUIRED FOR A GENERAL
 BUILDING PERMIT. AFTER THE BUILDING PERMIT HAS BEEN
 ISSUED, THE SUBCONTRACTORS CAN THEN SUBMIT SHOP
 DRAWINGS (CONFORMING TO THE ENGINEERED CONSTRUCTION
 DOCUMENTS) FOR A SUB-PERMIT. MASTER PERMIT FAILED WITH
 SAME COMMENTS. ENGINEERED DOCUMENTS MUST FIRST BE
 SUBMITTED UNDER THE MASTER PERMIT. (SEE COMMENTS UNDER
 MASTER PERMIT #17111009).
  
 2) PLANS SUBMITTED INCLUDE FIRE SPRINKLER PLANS AND
 DOCUMENTS (NOT SIGNED AND SEALED). UNCLEAR AS TO WHY
 THESE DOCUMENTS WERE INCLUDED WITH THIS SUBMISSION.
 SPOKE WITH JONATHAN AT FLORIDA STATE SECURITY AND HE
 COULD NOT EXPLAIN.
 A SEPERATE PERMIT IS REQUIRED FOR THE FIRE SPRINKLER
 SYSTEM.
  