| Date |
Text |
| 2018-03-21 07:35:59 | 2ND REVIEW FBC-2017 MECHANICAL |
| | PERMIT #17120057 |
| | 3/21/18 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET M1.1: PLEASE SEE SECTIONS 404.1 AND 404.2 |
| | FBC-14 MECHANICAL COPIED BELOW . THE USE OF THE TIME |
| | CLOCK TO CONTROL THE OPERATION OF THE GARAGE EXHAUST |
| | SYSTEM IS NOT PERMITTED. |
| | |
| | 404.1 ENCLOSED PARKING GARAGES. |
| | MECHANICAL VENTILATION SYSTEMS FOR ENCLOSED PARKING |
| | GARAGES SHALL BE PERMITTED TO OPERATE INTERMITTENTLY IN |
| | ACCORDANCE WITH ITEM 1, ITEM 2 OR BOTH. |
| | |
| | 1. THE SYSTEM SHALL BE ARRANGED TO OPERATE |
| | AUTOMATICALLY UPON DETECTION OF VEHICLE OPERATION OR |
| | THE PRESENCE OF OCCUPANTS BY APPROVED AUTOMATIC |
| | DETECTION DEVICES. |
| | |
| | 2. THE SYSTEM SHALL BE ARRANGED TO OPERATE |
| | AUTOMATICALLY BY MEANS OF CARBON MONOXIDE DETECTORS |
| | APPLIED IN CONJUNCTION WITH NITROGEN DIOXIDE DETECTORS. |
| | SUCH DETECTORS SHALL BE INSTALLED IN ACCORDANCE WITH |
| | THEIR MANUFACTURERS? RECOMMENDATIONS. |
| | |
| | 404.2 MINIMUM VENTILATION. |
| | AUTOMATIC OPERATION OF THE SYSTEM SHALL NOT REDUCE THE |
| | VENTILATION AIRFLOW RATE BELOW 0.05 CFM PER SQUARE FOOT |
| | (0.00025 M3/S ? M2) OF THE FLOOR AREA AND THE SYSTEM |
| | SHALL BE CAPABLE OF PRODUCING A VENTILATION AIRFLOW |
| | RATE OF 0.75 CFM PER SQUARE FOOT (0.0038 M3/S ? M2) OF |
| | FLOOR AREA. |
| | |
| | REVIEWS ARE COMPLETE; HOWEVER YOUR APPLICATION HAS NOT |
| | BEEN APPROVED. YOU CAN VIEW THE COMMENTS BY SELECTING |
| | THE PLAN REVIEWS TAB AT: HTTP://ONESTOPSHOP.WPBGOV.COM/ |
| | EGOVPLUS/PERMIT/PERM_STATUS.ASPX . |
| | |
| | 2) COMMISSIONING OF THE MECHANICAL SYSTEMS IS REQUIRED- |
| | SEE SECTION C408.2 AND SUBMIT A COMMISSIONING PLAN. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |