| 2018-03-15 14:54:45 | ****PLAN REVIEW COMMENTS**** |
| | |
| | ART LANGE BUILDING PLANS EXAMINER |
| | |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH, FL 33402 |
| | 561-805-6718 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2014 5TH EDITION W/2010 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | SECOND REVIEW: |
| | |
| | **BUILDING HAS PASSED** |
| | |
| | 1. ADDRESSED. BUILDING IS NOT IN A FLOOD ZONE. |
| | |
| | 3. PERMIT VALUE HAS BEEN UPDATED AS I CALCULATED BELOW. |
| | |
| | PERMIT VALUE |
| | BASED ON ICC BVD , BUILDING VALUATION DATA FOR GROUP S |
| | 1 STORAGE IN TYPE IIA CONSTRUCTION THIS HAS A SQUARE |
| | FOOT COST OF $92.40 PER SQUARE FOOT X 110,433 SQ. FT. |
| | OF STORAGE = $10,204,009 |
| | BUSINESS $173.86 PER SQUARE FOOT X 1069 SQ. FT. = |
| | $185,856 |
| | TOTAL COST = 10,389,865 |
| | |
| | FBC 108.3 BUILDING PERMIT VALUATION. |
| | |
| | 4. OK. RECEIVED GEOTECHNICAL SOILS REPORT. |
| | |
| | 5. PARTIALLY COMPLIED: RESUMES NOT PROVIDED FOR |
| | ENGINEER AND EACH INSPECTOR. SEE PAGE 4 NUMBER 3 OF THE |
| | THRESHOLD AGREEMENT FOR FURTHUR INSTRUCTIONS. |
| | |
| | I WILL MOVE THIS TO A THRESHOLD STOP SO THAT THIS CAN |
| | BE APPROVED. |
| | |
| | D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME' |
| | OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE |
| | RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS |
| | SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE |
| | WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED, |
| | AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES |
| | WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST |
| | MEETING THE ABOVE CRITERIA. |
| | |
| | 6. OK. SUBSTITUTED WITH DENSGLASS. |
| | |
| | FINISHES |
| | SEE PAGE A5.8, WALL SECTION 1 AND DIVISION 9 FINISHES |
| | 9.41 5/8 INCH CDX PLYWOOD USED. |
| | COMBUSTIBLE MATERIALS IN TYPE II CONSTRUCTION FBC 603. |
| | |
| | 7. OK. DEFFERED SUBMITTALS LISTED. |
| | |
| | |