| 2018-02-09 12:23:07 | 1ST REVIEW: FBC 2014 5TH EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. SHT. A1.5 NOTE P.33 LIST THE SCUPPER AND EMERGENCY |
| | SCUPPER AT 24" X 8" SHT. A1.5A DETAIL #3 SHOWS THE |
| | SCUPPER AT 16" X 8" AND SHT. P1.5 SHOWS THE SCUPPER AT |
| | 16" X4" PLEASE CLARIFY. PER WPB AMEND TO FBC |
| | |
| | 2. PLEASE PROVIDE A DETAIL OF THE EMERGENCY SCUPPER |
| | SHOWING COMPLIANCE WITH. FBC 1503.4.2.1 OVERFLOW |
| | SCUPPERS. |
| | WHEN OTHER MEANS OF DRAINAGE OF OVERFLOW WATER IS NOT |
| | PROVIDED, OVERFLOW SCUPPERS SHALL BE PLACED IN WALLS OR |
| | PARAPETS NOT LESS THAN 2 INCHES (51 MM) NOR MORE THAN 4 |
| | INCHES (102 MM) ABOVE THE FINISHED ROOF COVERING AND |
| | SHALL BE LOCATED AS CLOSE AS PRACTICAL TO REQUIRED |
| | VERTICAL LEADERS OR DOWNSPOUTS OR WALL AND PARAPET |
| | SCUPPERS. AN OVERFLOW SCUPPER SHALL BE SIZED IN |
| | ACCORDANCE WITH THE FLORIDA BUILDING CODE, PLUMBING. |
| | |
| | 3. GRAB BARS SHALL BE MEASURED TO THE TOP OF THE |
| | GRIPPING SURFACE. PER FBC ACC 609.4 |
| | |
| | 4. SHOW COMPLIANCE WITH FBC ACC: |
| | 604.5.1 SIDE WALL. |
| | THE SIDE WALL GRAB BAR SHALL BE 42 INCHES (1065 MM) |
| | LONG MINIMUM, LOCATED 12 INCHES (305 MM) MAXIMUM FROM |
| | THE REAR WALL AND EXTENDING 54 INCHES (1370 MM) MINIMUM |
| | FROM THE REAR WALL. |
| | 604.5.2 REAR WALL. |
| | THE REAR WALL GRAB BAR SHALL BE 36 INCHES (915 MM) LONG |
| | MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER |
| | CLOSET 12 INCHES (305 MM) MINIMUM ON ONE SIDE AND 24 |
| | INCHES (610 MM) MINIMUM ON THE OTHER SIDE. |
| | |
| | 5. THYE BREAK ROOM SINK SHALL COMPLY WITH FBC ACC 606.2 |
| | + 606.3 |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561-805-6711 |
| | [email protected] |
| | |