| 2018-01-26 10:37:41 | 1ST REVIEW FBC-2014 MECHANICAL |
| | PERMIT #17120057 |
| | 1/26/18 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE ENERGYGAUGE REPORT IS MISSING COMPLIANCE DATA |
| | FOR SYSTEMS 1-6 AND 1-7. |
| | |
| | 2) SHEET M1.1: CARBON DIOXIDE DETECTORS APPLIED IN |
| | CONJUNCTION WITH NITROGEN DIOXIDE DETECTORS ARE |
| | REQUIRED IN THE LOADING BAY AREA- SECTION 404.1(2). |
| | |
| | 3) M1.1: REVISE THE NOTES TO INDICATE THE EXHAUST |
| | SYSTEM WILL OPERATE CONTINUOUSLY AND AUTOMATIC |
| | OPERATION OF THE SYSTEM SHALL NOT REDUCE THE MINIMUM |
| | AIRFLOW RATE BELOW 0.05 CFMS PER SQ. FT. |
| | |
| | 4) M1.1: PROVIDE SUPPORT AND HANGING DETAILS FOR |
| | INSTALLATION OF THE INLINE EXHAUST FANS AND DUCTWORK. |
| | |
| | 5) SHEETS M1.1, M1.2, M1.3, M1.4, M1.5: PLEASE CLARIFY |
| | HOW THE AHU'S OR EACH FLOOR WITHOUT THE USE OF DUCTWORK |
| | WILL BE ABLE TO DISTRIBUTE AIR EVENLY THROUGHOUT THE |
| | ZONES. |
| | |
| | 6) M1.1, M1.1, M1.3, M1.4, & M1.5: PROVIDE CONDENSATE |
| | DISPOSAL PLANS FOR THE AIR HANDLERS |
| | |
| | 7) PROVIDE THE MIAMI-DADE NOA'S FOR THE EF-8 WALL |
| | BRACKET, THE CONDENSER STANDS, AND THE O/A LOUVERS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |