2018-01-26 10:37:411ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17120057
 1/26/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE ENERGYGAUGE REPORT IS MISSING COMPLIANCE DATA
 FOR SYSTEMS 1-6 AND 1-7.
  
 2) SHEET M1.1: CARBON DIOXIDE DETECTORS APPLIED IN
 CONJUNCTION WITH NITROGEN DIOXIDE DETECTORS ARE
 REQUIRED IN THE LOADING BAY AREA- SECTION 404.1(2).
  
 3) M1.1: REVISE THE NOTES TO INDICATE THE EXHAUST
 SYSTEM WILL OPERATE CONTINUOUSLY AND AUTOMATIC
 OPERATION OF THE SYSTEM SHALL NOT REDUCE THE MINIMUM
 AIRFLOW RATE BELOW 0.05 CFMS PER SQ. FT.
  
 4) M1.1: PROVIDE SUPPORT AND HANGING DETAILS FOR
 INSTALLATION OF THE INLINE EXHAUST FANS AND DUCTWORK.
  
 5) SHEETS M1.1, M1.2, M1.3, M1.4, M1.5: PLEASE CLARIFY
 HOW THE AHU'S OR EACH FLOOR WITHOUT THE USE OF DUCTWORK
 WILL BE ABLE TO DISTRIBUTE AIR EVENLY THROUGHOUT THE
 ZONES.
  
 6) M1.1, M1.1, M1.3, M1.4, & M1.5: PROVIDE CONDENSATE
 DISPOSAL PLANS FOR THE AIR HANDLERS
  
 7) PROVIDE THE MIAMI-DADE NOA'S FOR THE EF-8 WALL
 BRACKET, THE CONDENSER STANDS, AND THE O/A LOUVERS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  