Plan Review Notes
Plan Review Notes For Permit 17120055
Permit Number 17120055
Review Stop R
Sequence Number 3
Notes
Date Text
2018-03-19 11:46:231- DESIGNER OF RECORD TO REVISE ROOF CLAY TILE
 FASTENING SPECIFIED ON SHEET A-3. IT DOESN'T MEET THE
 UPLIFT MOMENT FOR FOR PERIMETER AND CORNER AREAS. SEE
 TABLE 2A OF FRSA 5TH EDITION REVISED AND CLAY TILE NOA
 17-0626.03 SUBMITTED..
 2- FLAT ROOF NOA 14-1030.01 SUBMITTED: CLEARLY MARK
 WHICH APPROVED ASSEMBLY IS GOING TO BE INSTALLED TO
 VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC.
 R301.1 FBC-RESIDENTIAL. IF THE SELECTED ASSEMBLY
 DOESN'T MEET THE DESIGN PRESSURES FOR ALL ROOF ZONES,
 THEN SIGNED AND SEALED RAS 117 CALCULATIONS ARE
 REQUIRED.
  
  
 APPROVED ROOF TILE NOA 17-0626.03.