| Plan Review Notes For Permit 17120055 |
| Permit Number |
17120055 |
|
| Review Stop |
R |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2018-03-19 11:46:23 | 1- DESIGNER OF RECORD TO REVISE ROOF CLAY TILE | | | FASTENING SPECIFIED ON SHEET A-3. IT DOESN'T MEET THE | | | UPLIFT MOMENT FOR FOR PERIMETER AND CORNER AREAS. SEE | | | TABLE 2A OF FRSA 5TH EDITION REVISED AND CLAY TILE NOA | | | 17-0626.03 SUBMITTED.. | | | 2- FLAT ROOF NOA 14-1030.01 SUBMITTED: CLEARLY MARK | | | WHICH APPROVED ASSEMBLY IS GOING TO BE INSTALLED TO | | | VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. | | | R301.1 FBC-RESIDENTIAL. IF THE SELECTED ASSEMBLY | | | DOESN'T MEET THE DESIGN PRESSURES FOR ALL ROOF ZONES, | | | THEN SIGNED AND SEALED RAS 117 CALCULATIONS ARE | | | REQUIRED. | | | | | | | | | APPROVED ROOF TILE NOA 17-0626.03. |
|