Plan Review Notes
Plan Review Notes For Permit 17120050
Permit Number 17120050
Review Stop B
Sequence Number 2
Notes
Date Text
2018-02-26 09:02:31****PLAN REVIEW COMMENTS****
  
 ART LANGE BUILDING PLANS EXAMINER
  
 DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33402
  
 561-805-6718 [email protected]
  
 FBC FLORIDA BUILDING CODE 2014 5TH EDITION W/2010 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 SECOND REVIEW:
  
  
 1) ADDRESSED OK
  
 PLEASE UPDATE DEMO KEY NOTES TO INCLUDE #12 AND #13
 THAT ARE NOT SHOWN ON PAGE AD1.1. ON PAGE A-2.01
 ELEVATION #6 NOTE SHOWN AS NEEDED.
  
 2) SUBMIT SEPARATE PERMIT FOR AWNING WHEN READY
  
 PROVIDE STRUCTURAL SHOP DRAWINGS FOR AWNING SHOWN AS
 KEY NOTE #7 ON A-2.0.1.
  
 FBC 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 THE EXAMINATION OF THE DOCUMENTS BY THE BUILDING
 OFFICIAL SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA
 AND DOCUMENTS: A FLOOR PLAN; SITE PLAN; FOUNDATION
 PLAN; FLOOR/ROOF FRAMING PLAN OR TRUSS LAYOUT; ALL
 FENESTRATION PENETRATIONS; FLASHING; AND ROUGH OPENING
 DIMENSIONS; AND ALL EXTERIOR ELEVATIONS.
  
 3) PARTIALLY ADDRESSED. RECEIVED PRODUCT APPROVAL.
 DESIGNER OF RECORD HAS NOT REVIEWED.
  
 PROVIDE PRODUCT APPROVAL FOR TRULITE DOOR USED WITH THE
 TRULITE STOREFRONT WALL SYSTEM. IT HAS ITS OWN PRODUCT
 APPROVAL.
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
 4) THIS PATH OF TRAVEL IS THROUGH AN EXISTING MOTOR
 VEHICLE REPAIR GARAGE FBC 311.2. AD1.1 SHOWS NO WORK IN
 THIS AREA. ALS1.1 SHOWS TRAVEL THROUGH THIS AREA.
  
 ON LIFE SAFETY ALS.1.1 THE SECOND EXIT SHOWN IS THROUGH
 A STORAGE ROOM.
  
 FBC 1014.2 EGRESS THROUGH INTERVENING SPACES.
  
 EGRESS THROUGH INTERVENING SPACES SHALL COMPLY WITH
 THIS SECTION.
  
 1. EGRESS FROM A ROOM OR SPACE SHALL NOT PASS THROUGH
 ADJOINING OR INTERVENING ROOMS OR AREAS, EXCEPT WHERE
 SUCH ADJOINING ROOMS OR AREAS AND THE AREA SERVED ARE
 ACCESSORY TO ONE OR THE OTHER, ARE NOT A GROUP H
 OCCUPANCY AND PROVIDE A DISCERNIBLE PATH OF EGRESS
 TRAVEL TO AN EXIT.
  
 4. EGRESS SHALL NOT PASS THROUGH KITCHENS, STORAGE
 ROOMS, CLOSETS OR SPACES USED FOR SIMILAR PURPOSES.
 EXCEPTIONS: 2.2. NOT MORE THAN 50 PERCENT OF THE EXIT
 ACCESS IS THROUGH THE STOCKROOM.
 NOTE: THIS EGRESS DOES NOT EXCEED THE 50 PERCENT
 ALLOWED BY EXCEPTION 2.2. BUT SHALL COMPLY WITH FBC
 1014.2 EXCEPTION 2. AN EXIT ACCESS SHALL NOT PASS
 THROUGH A ROOM THAT CAN BE LOCKED TO PREVENT EGRESS.
  
 5) NOT ADDRESSED
 PROVIDE THE STORAGE CLASSIFICATION FOR THE EXISTING
 STORAGE AREA AND ITS COMPLIANCE WITH FBC 311 STORAGE
 GROUP S. BASED ON THIS DETERMINATION. INCLUDE
 INFORMATION ON THE DOOR, RATING AND IF A CLOSURE WILL
 BE PROVIDED AND IF THE WINDOW WILL BE PROVIDED WITH A
 RATING.
  
  
 WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM:
  
 HTTP://WPB.ORG/DEVELOPMENT/WPCONTENT/UPLOADS/SITES/33/2
 013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 THIS FORM IS ALSO AVAILABLE AT THE BUILDING DIVISION.
  
 WHEN RESUBMITTING, SWAP OUT SHEETS WHICH HAVE CHANGED
 SO THAT THERE ARE TWO COMPLETE, COLLATED SETS OF PLANS
 READY FOR PERMIT ISSUANCE. OLD SHEETS ARE TO BE
 RETAINED IN THE PERMIT APPLICATION PACKAGE (SEPARATE
 FROM THE PERMIT SETS) AND MARKED *OLD SHEETS* OR
 *VOID*. PLEASE KEEP BOTH SETS OF OLD VOIDED SHEETS IN
 THE PERMIT PACKAGE.
  
 A RESPONSE LETTER INDICATING HOW EACH ITEM WAS
 ADDRESSED WILL HELP TO EXPEDITE PLAN REVIEW.
  