2018-01-19 09:44:511ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. THE DIGITAL SIGNATURES ON ALL THE PLAN SHEETS ARE
 INVALID. DIGITAL SIGNATURES SHALL NOT BE USED ON PAPER
 PLANS. ALL SIGNATURES SHALL FOR ENGINEERS THEY SHALL
 COMPLY WITH FAC 61G15-23.003 FOR ARCHITECT THEY SHALL
 COMPLY WITH FAC 61G1-16.005
  
 2. THE SHOWER IN BATHROOM 112 SHALL COMPLY WITH ONE OF
 3 DESIGN TYPES IN FBC ACC
  
 A) 608.2.1 TRANSFER TYPE SHOWER COMPARTMENTS.
 TRANSFER TYPE SHOWER COMPARTMENTS SHALL BE 36 INCHES BY
 36 INCHES CLEAR INSIDE DIMENSIONS MEASURED AT THE
 CENTER POINTS OF OPPOSING SIDES AND SHALL HAVE A 36
 INCH WIDE MINIMUM ENTRY ON THE FACE OF THE SHOWER
 COMPARTMENT. CLEARANCE OF 36 INCHES WIDE MINIMUM BY 48
 INCHES LONG MINIMUM MEASURED FROM THE CONTROL WALL
 SHALL BE PROVIDED.
  
 B) 608.2.2 STANDARD ROLL-IN TYPE SHOWER COMPARTMENTS.
 STANDARD ROLL-IN TYPE SHOWER COMPARTMENTS SHALL BE 30
 INCHES WIDE MINIMUM BY 60 INCHES DEEP MINIMUM CLEAR
 INSIDE DIMENSIONS MEASURED AT CENTER POINTS OF OPPOSING
 SIDES AND SHALL HAVE A 60 INCHES WIDE MINIMUM ENTRY ON
 THE FACE OF THE SHOWER COMPARTMENT.
 608.2.2.1 CLEARANCE.
 A 30 INCH WIDE MINIMUM BY 60 INCH LONG MINIMUM
 CLEARANCE SHALL BE PROVIDED ADJACENT TO THE OPEN FACE
 OF THE SHOWER COMPARTMENT.
  
 C) 608.2.3 ALTERNATE ROLL-IN TYPE SHOWER COMPARTMENTS.
 ALTERNATE ROLL-IN TYPE SHOWER COMPARTMENTS SHALL BE 36
 INCHES WIDE AND 60 INCHES DEEP MINIMUM CLEAR INSIDE
 DIMENSIONS MEASURED AT CENTER POINTS OF OPPOSING SIDES.
 A 36 INCH WIDE MINIMUM ENTRY SHALL BE PROVIDED AT ONE
 END OF THE LONG SIDE OF THE COMPARTMENT.
  
 3. PLEASE SHOW THE DIMENSIONS ON THE REQUIRED CLEAR
 FLOOR SPACE AT THE WATER CLOSET'S, LAVATORY'S, WATER
 FOUNTAIN'S AND KITCHEN SINK. PER WPB AMEND TO FBC
 107.2.1
  
 4. PLEASE SHOW DIMENSIONS FOR HEIGHT OF THE TOILET
 PAPER DISPENSER THE OUTLET OF THE DISPENSER SHALL BE 15
 INCHES MINIMUM AND 48 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR AND SHALL NOT BE LOCATED BEHIND GRAB BARS. PER
 FBC ACC 604.7
  
 5. PROVIDE DETAILS FOR GRAB BARS IN THE SHOWER FOR THE
 DESIGN TYPE SHOWN ON PLAN. FBC ACC
 A) 608.3.1 TRANSFER TYPE SHOWER COMPARTMENTS.
 IN TRANSFER TYPE COMPARTMENTS, GRAB BARS SHALL BE
 PROVIDED ACROSS THE CONTROL WALL AND BACK WALL TO A
 POINT 18 INCHES FROM THE CONTROL WALL.
 OR
 B) 608.3.2 STANDARD ROLL-IN TYPE SHOWER COMPARTMENTS.
 WHERE A SEAT IS PROVIDED IN STANDARD ROLL-IN TYPE
 SHOWER COMPARTMENTS, GRAB BARS SHALL BE PROVIDED ON THE
 BACK WALL AND THE SIDE WALL OPPOSITE THE SEAT. GRAB
 BARS SHALL NOT BE PROVIDED ABOVE THE SEAT. WHERE A SEAT
 IS NOT PROVIDED IN STANDARD ROLL-IN TYPE SHOWER
 COMPARTMENTS, GRAB BARS SHALL BE PROVIDED ON THREE
 WALLS. GRAB BARS SHALL BE INSTALLED 6 INCHES MAXIMUM
 FROM ADJACENT WALLS.
 OR
 C) 608.3.3 ALTERNATE ROLL-IN TYPE SHOWER COMPARTMENTS.
 IN ALTERNATE ROLL-IN TYPE SHOWER COMPARTMENTS, GRAB
 BARS SHALL BE PROVIDED ON THE BACK WALL AND THE SIDE
 WALL FARTHEST FROM THE COMPARTMENT ENTRY. GRAB BARS
 SHALL NOT BE PROVIDED ABOVE THE SEAT. GRAB BARS SHALL
 BE INSTALLED 6 INCHES MAXIMUM FROM ADJACENT WALLS.
  
 6. SHOW THE DIMENSION FOR THE SHOWER SPRAY UNITS. PER
 FBC ACC 608.5.1 OR 608.5.2 OR 608.5.3
  
 7. DUE TO THE FACT THAT THERE IS AN OVEN IN THE KITCHEN
 AND COOKING COULD BE DONE A GREASE INTERCEPTOR WILL BE
 REQUIRED ON THE KITCHEN SINK. PER FBC PL 1003.3.1
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  