Plan Review Notes
Plan Review Notes For Permit 17120050
Permit Number 17120050
Review Stop M
Sequence Number 1
Notes
Date Text
2018-01-02 17:16:291ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17120050
 1/2/2018
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE ENGINEER'S ORIGINAL SIGNATURE AND SEAL SHALL BE
 ON THE PLANS AND ENERGY CALCULATIONS AS REQUIRED BY
 SECTION 61G15-23.002 FLORIDA ADMINISTRATIVE CODE.
 ELECTRONIC SIGNATURES AND SEALS ARE NOT ACCEPTED ON THE
 PAPER PLANS UNLESS ALL REQUIREMENTS LISTED UNDER
 SECTION 61G15-23.005 (2) & (3) FLORIDA ADMINISTRATIVE
 CODE ARE MET.
  
 2) M2.1: LABEL THE RETURN GRILLS AT THE OFFICE AND THE
 EXERCISE ROOM.
  
 3) M6.1, O/A CALCULATIONS: A) CORRECT THE OUTDATED
 ASHRAE 62.1-2004 REFERENCE. B) CORRECT THE CLAUCLATIONS
 PER ASHRAE 62.1-2010 OR TABLE 403.3 - CONFERENCE ROOMS
 ARE CALCULATED AT 50 PERSONS PER 1000 SQ. FT; RECEPTION
 AREAS AT 30 PERSONS PER SQ. FT.; LOUNGES OR DINING
 ROOMS AT 70 PERSONS PER SQ. FT. AT 7.5 CFM PER PERSON
 AND 0.18 CFMS PER SQ. FT.; EXERCISE ROOMS ARE
  
 CALCULATED AT 40 PERSONS PER SQ. FT. AT 20 CFMS PER
 PERSON AND 0.06 PER SQ. FT.
  
 4) KITCHEN EXHAUST AT A RATE OF 0.70 CFMS PER SQ. FT.
 IS REQUIRED PER TABLE 403.3. INDICATE HOW THIS
 REQUIREMENT IS BEING MET.
  
 5) A TYPE II EXHAUST HOOD IS REQUIRED FOR THE OVEN PER
 SECTION 507.2.2. A SEPARATE PERMIT IS REQUIRED FOR THE
 HOOD BUT IT SHALL BE INDICATED ON THE MAIN PERMIT
 PLANS.
  
 6) PLEASE PROVIDE THE MAKE AND MODEL OF THE OVEN AND
 SUBMIT MANUFACTURER'S SPECIFICATIONS- SECTION 917.1
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved