| 2018-06-27 11:30:10 | TCO PROPOSED SEPARATION REVIEW |
| | |
| | THE FOLLOWING IS AN UNOFFICIAL REVIEW BASED ON THE |
| | LIMITED PLAN SUBMITTAL SHEET. |
| | |
| | THE FIRE PREVENTION BUREAU DOES NOT HAVE AN OBJECTION |
| | TO A PROPOSED TCO; HOWEVER, THE FOLLOWING COMMENTS WILL |
| | NEED TO BE ADDRESSED AND OFFICIAL PLANS WILL NEED TO BE |
| | SUBMITTED FOR REVIEW AND APPROVAL. |
| | |
| | THIS REVIEW DOES NOT GRANT APPROVAL TO OCCUPY ANY SPACE |
| | OR AREA. |
| | |
| | |
| | 1) SHEET A 13.1 - PROVIDE AN OUT OF SERVICE, OOS, SIGN |
| | AT ELEVATOR # 2. |
| | |
| | |
| | |
| | 2) SHEET 13.1 - THERE ARE TWO STATEMENTS INDICATED AT |
| | EACH SIDE OF THE SHADED CONSTRUCTION AREAS, "CONTROLLED |
| | ACCESS TO CONSTRUCTION AREA. |
| | |
| | PLEASE PROVIDE A DETAILED EXPLANATION/DESCRIPTION OF |
| | WHAT THIS STATMENT MEANS AND HOW WILL COMPLY WITH THE |
| | LIFE SAFETY CODE ON TWO POINTS. |
| | |
| | HOW WILL THE GENERAL PUBLIC/OFFICE STAFF BE PROTECTED |
| | FROM ENETERING THE CONSTRUCTION AREAS? |
| | |
| | HOW WILL THESE AREAS PROVIDE FOR EXITING OF |
| | CONSTRUCTION WORKERS IN THE EVENT OF EMERGENCY? |
| | |
| | |
| | |
| | |
| | 3) SHEET A 13.2 - PROVIDE A DETAILED EXPLANATION ON HOW |
| | EACH STAIRWELL DOOR TO THE CONSTRUCTION AREAS BE |
| | SECURED FROM THE CONSTRUCTION AREA ON TWO POINTS? |
| | |
| | HOW WILL THE GENERAL PUBLIC/OFFICE STAFF BE PROTECTED |
| | FROM ENETERING THE CONSTRUCTION AREAS? |
| | |
| | HOW WILL THESE AREAS PROVIDE FOR EXITING OF |
| | CONSTRUCTION WORKERS IN THE EVENT OF EMERGENCY? |
| | |
| | |
| | |
| | 4) SHEET A 13.2 - PROVIDE A DETAILED EXPLANATION ON HOW |
| | THE ELEVATOR WILL BE CONTROLLED TO NOT LET PEOPLE OFF |
| | AT THE 2ND FLOOR CONSTRUCTION AREA. |
| | |
| | |
| | |
| | 5) SHEET A 13.2 - PROVIDE PROVIDE AN OUT OF SERVICE, |
| | OOS, SIGN AT ELEVATOR # 2. |
| | |
| | |
| | |
| | 6) SHEET A 13.3 - ELEVATOR # 2 IS NOT SHADED AND SHALL |
| | HAVE A OOS SIGN IN PLACE. |
| | |
| | |
| | 7) SHEET A 13.3 - THE IS AN ACCESS STAIR INDICATED TO |
| | THE 4TH FLOOR. THERE IS NO 4TH FLOOR PLAN ATTACHED. |
| | |
| | PROVIDE A DETAILED EXPLANATION REGARDING THE 4TH FLOOR |
| | USE AND PROVIDE ALL APPLICABLE PLAN SHEETS OR |
| | CONTROLLED CONSTRUCTION AREA. |
| | |
| | |
| | 8) ALL LIFE SAFETY SYSTEMS, FIRE ALARM AND FIRE |
| | SPRINKLER, SHALL BE FULLY OPERATIONAL, TESTED AND |
| | APPROVED THROUGH REVISED SHOP DRAWINGS, PRIOR TO ANY |
| | OCCUPANCY. |
| | |
| | THE LIFE SAFETY SYSTEMS SHALL BE MAINTAINED AND |
| | OPERATIONAL ALL ALL TIMES DURING THE TCO PHASE. |
| | |
| | ANY TIME EITHER SYSTEM IS DOWN FOR MORE THAN 4 HOURS |
| | YOU ARE REQUIRED TO CONDUCT A FIRE WATCH UNTIL IT IS |
| | FULLY OPERATIONAL. |
| | |
| | PLEASE REVIEW AND PROVIDE AN NOTE OF COMPLIANCE AND |
| | ACKNOWLEDGEMENT. |
| | |
| | |
| | 9) PROVIDE DETAILED RESPONSES TO ALL OTHER CITY |
| | DISCIPLINE COMMENTS WITH APPROVAL. |
| | |
| | |
| | 10) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | |