| 2017-12-22 07:48:26 | 2014 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 17120042 |
| | ADD: 2410 METROCENTRE BLVD. |
| | CONT: VERDEX CONSTRUCTION LLC |
| | TEL: 561-440-1600 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: FRI. DEC. 22/ 2017 |
| | ACTION: DENIED |
| | |
| | 1) THE COVERSHEET LIST THIS BUILDING AS A BUSINESS |
| | OCCUPANCY, CONSTRUCTION TYPE: III-B, FULLY SPRINKLERED |
| | NFPA-13, 19,951 SQUARE FEET PER FLOOR AND A (4) STORY |
| | BUILDING. |
| | |
| | THE 2014 FBC-B TABLE 503 UNDER HEIGHT AND AREA LIST FOR |
| | A BUSINESS OCCUPANCY FOR A TYPE III-B BUILDING ONLY 3 |
| | STORIES AND AN ALLOWABLE AREA PER FLOOR OF 19,000 |
| | SQUARE FEET. THE PLANS ARE SILENT IF THE DESIGNER OF |
| | RECORD HAS TAKEN ADVANTAGE OF GENERAL EXCEPTIONS TO: |
| | |
| | TABLE 503 SEE FOOTNOTE (A) |
| | A. SEE THE FOLLOWING SECTIONS FOR GENERAL EXCEPTIONS TO |
| | TABLE 503: |
| | 1. SECTION 504.2, ALLOWABLE BUILDING HEIGHT AND STORY |
| | INCREASE DUE TO AUTOMATIC SPRINKLER SYSTEM |
| | INSTALLATION. |
| | 2. SECTION 506.2, ALLOWABLE BUILDING AREA INCREASE DUE |
| | TO STREET FRONTAGE. |
| | 3. SECTION 506.3, ALLOWABLE BUILDING AREA INCREASE DUE |
| | TO AUTOMATIC SPRINKLER SYSTEM INSTALLATION. |
| | |
| | PLEASE PROVIDE AREA INCREASES TAKEN UNDER FBC-B 506.1 |
| | AND EQUATION 5-1. |
| | |
| | 2) THE COVERSHEET LIST THIS BUILDING AS A 4 STORY |
| | THRESHOLD BUILDING. THRESHOLD BUILDING / FL S. S. |
| | 553.71(7) ?THRESHOLD BUILDING" MEANING ANY BUILDING |
| | WHICH IS GREATER THAN (3) STORIES OR 50 FT. IN HEIGHT, |
| | OR WHICH HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS |
| | DENIED IN THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 |
| | SQ. FT. IN AREA AND AN OCCUPANT CONTENT OF GREATER THAN |
| | 500 PERSONS. |
| | |
| | 2A) COMPLIED. 109.3.6.1 THRESHOLD INSPECTION PLAN. THE |
| | ENFORCING AGENCY SHALL REQUIRE A (WRITTEN/ TYPED) |
| | SPECIAL INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON |
| | A THRESHOLD BUILDING PURSUANT TO A STRUCTURAL |
| | INSPECTION PLAN PREPARED BY THE ENGINEER OF RECORD. THE |
| | STRUCTURAL INSPECTION PLAN MUST BE SUBMITTED TO THE |
| | ENFORCING AGENCY PRIOR TO THE ISSUANCE OF A BUILDING |
| | PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING. |
| | THE PURPOSE OF THE STRUCTURAL INSPECTION PLAN IS TO |
| | PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO |
| | THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR |
| | COMPLIANCE WITH THE PERMITTED DOCUMENTS. |
| | |
| | 2B) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B. |
| | CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD |
| | BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S S |
| | 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS |
| | REQUIRED BY THIS CODE. THE THRESHOLD INSPECTION FORMS |
| | ARE REQUIRED TO BE FILED OUT BY ALL PARTIES WITH |
| | INTEREST, NOTARIZED AND RETURNED TO THIS OFFICE, AND |
| | REVIEWED AND APPROVED BEFORE PERMIT ISSUANCE WILL TAKE |
| | PLACE. |
| | FORMS E-MAILED TO: [email protected] 12/22/2017 |
| | 06:48 AM |
| | |
| | 2C) THRESHOLD BLDG., REQUIRED STATEMENT: W.P.B. |
| | AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING WHICH |
| | ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT |
| | OR ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE |
| | BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE |
| | PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE |
| | FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL |
| | AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633 |
| | FLORIDA STATUTE. |
| | |
| | 2D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME' |
| | OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE |
| | RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS |
| | SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE |
| | WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED, |
| | AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES |
| | WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST |
| | MEETING THE ABOVE CRITERIA. |
| | |
| | 2E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR |
| | HISTORY FOR THIS TYPE OF CONSTRUCTION. |
| | |
| | 2F) COMPLIED. NOTE FOR PAPER PLANS 3 SETS OF DOCUMENTS |
| | ARE REQUIRED. FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE, |
| | PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE PERMIT BEING |
| | ISSUED, THE PERMIT LIBRARIAN WILL THEN E-MAIL YOU THE |
| | APPROVED AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR |
| | PLANS, TWO SETS OF PLANS WILL NEED TO BE PRINTED IN |
| | COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE OTHER FOR |
| | THE MEP INSPECTORS OTHER PLANS YOU WISH TO PRINT MAYBE |
| | IN BLACK & WHITE.. |
| | 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION, 110.3.7 THRESHOLD |
| | BUILDINGS, GUIDELINES AND POLICIES FOR PROJECTS |
| | CONCERNING SPECIAL INSPECTORS. |
| | |
| | 2G) 110.3.7.4.3 ALL SHORING AND RESHORING PROCEDURES, |
| | PLANS AND DETAILS SHALL BE SUBMITTED TO THE ENFORCEMENT |
| | AGENCY FOR RECORDKEEPING. EACH SHORING AND RESHORING |
| | INSTALLATION SHALL BE SUPERVISED, INSPECTED AND |
| | CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING |
| | DOCUMENTS BY THE CONTRACTOR. |
| | |
| | 2H) PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED |
| | TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR ALL |
| | BUILDING INSPECTIONS FOR AUDITING OF JOBSITE |
| | INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN 6 |
| | MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY. |
| | |
| | 2I) 109.3.6 THRESHOLD BUILDINGS, OPERATING GUIDELINES |
| | FOR THRESHOLD INSPECTORS #26. ASSURE THAT THE DESIGNER |
| | HAS REQUIRED ON THE PLANS OR SPECIFICATIONS ONE |
| | MATERIAL, APPROVED FOR FIRE STOPPING PENETRATIONS, FOR |
| | WALLS AND CEILINGS. |
| | |
| | 3A) SHEET A6.1 AND DETAIL # 2 THE PLANS WILL NEED TO |
| | SHOW COMPLIANCE WITH: |
| | 2014 FBC-B 1009.9.3 ENCLOSURES UNDER INTERIOR |
| | STAIRWAYS. THE WALLS AND SOFFITS WITHIN ENCLOSED USABLE |
| | SPACES UNDER ENCLOSED AND UNENCLOSED STAIRWAYS SHALL BE |
| | PROTECTED BY 1-HOUR FIRE-RESISTANCE-RATED CONSTRUCTION |
| | OR THE FIRE-RESISTANCE RATING OF THE STAIRWAY |
| | ENCLOSURE, WHICHEVER IS GREATER. NOTE UNDER THE 2012 |
| | IBC COMMENTARY. NO STORAGE ALLOWED EVEN FOR OPEN |
| | STAIRS. |
| | |
| | 3B) THE NORTH STAIR PLAN SHOW 4X4 WOOD POST HOLDING UP |
| | THE MID-LANDING AT STRINGERS, BUT IN THE CUT SECTION 2 |
| | OF THE STAIRS, THE PLAN DOES NOT SHOW THE 4X4 POST. |
| | 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 3C) SHEET A6.1 SHOWS IN DETAIL 4 THE STAIR GUARDRAIL |
| | AND HAND RAIL. WHAT THIS DETAIL DOES NOT INDICATE HOW |
| | THE GUARDRAIL IS TO BE ANCHORED INTO THE WOOD |
| | STRINGERS, AND OR WOOD TREADS. SHOW COMPLIANCE WITH: |
| | |
| | FBC-B 1607.8.1 HANDRAILS AND GUARDS. HANDRAILS AND |
| | GUARDS SHALL BE DESIGNED TO RESIST A LINEAR LOAD OF 50 |
| | POUNDS PER LINEAR FOOT (PLF) IN ACCORDANCE WITH SECTION |
| | 4.5.1 OF ASCE 7. GLASS HANDRAIL ASSEMBLIES AND GUARDS |
| | SHALL ALSO COMPLY WITH SECTION 2407. |
| | |
| | 3C)(1) 1607.8.1.1 CONCENTRATED LOAD. HANDRAILS AND |
| | GUARDS SHALL ALSO BE DESIGNED TO RESIST A CONCENTRATED |
| | LOAD OF 200 POUNDS IN ACCORDANCE WITH SECTION 4.5.1 OF |
| | ASCE 7. |
| | |
| | 3C)(2) 1607.8.1.2 INTERMEDIATE RAILS. INTERMEDIATE |
| | RAILS (ALL THOSE EXCEPT THE HANDRAIL), BALUSTERS AND |
| | PANEL FILLERS SHALL BE DESIGNED TO RESIST A |
| | CONCENTRATED LOAD OF 50 POUNDS IN ACCORDANCE WITH |
| | SECTION 4.5.1 OF ASCE 7. |
| | |
| | 3D) PLEASE REVIEW THE 3RD FLOOR HANDRAIL SYSTEM, THE |
| | TRANSITION TO A HORIZONTAL POSITION STARTS AT THE 1ST |
| | TREAD, THIS IS WRONG. THE SLOPE OF THE HANDRAIL IS TO |
| | CONTINUE THE SLOPE FOR THE DEPTH OF ONE TREAD BEYOND |
| | THE BOTTOM RISER. PLEASE REVIEW FBC-B 1012.6 HANDRAIL |
| | EXTENSIONS. |
| | |
| | 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | JAMES A. WITMER BN, PX, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES |
| | DEPARTMENT |
| | 401 CLEMATIS ST. |
| | WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |