| 2017-12-05 13:10:53 | 1ST REVIEW FBC-2014 MECHANICAL | | | MASTER #15111020 THE BRISTOL | | | REVISION PERMIT #17120001 | | | 12/5/17 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) ELECTRONIC SIGNATURES AND SEALS ARE MISSING FROM ALL | | | OF THE UPLOADED REVISED PLAN SHEETS. PLEASE NOTE THAT | | | MECHANICAL SHEETS M2.0P1, M2.0P2, M2.01, M2.02, AND | | | M2.03 STILL BEAR THE TITLE BLOCK OF EDWARDS AND ZUCK | | | WHO HAVE BEEN REPLACED BY STANTEC AS THE MECHANICAL | | | ENGINEERS OF RECORD. THESE SHEETS DO NOT APPEAR TO BE | | | UPDATED BY THE DATES LISTED, HOWEVER ALL OTHER | | | | | | MECHANICAL SHEETS BY STANTEC HAVE REVISION DATES OF | | | 10/27/17. THE ARCHITECTURAL SHEETS A7.01, A7.02, ANSD | | | A7.03 ALSO NEED TO BE UPDATED. | | | | | | 2) SHEET A7.01: ACESS PANEL LOCATIONS NOT SHOWN IN RM | | | 142- HP1L-8, RM 116- HP-1L-2, AND RM 117-HP-1L-3. | | | | | | 3) PLEASE VERIFY THAT THE ACCESS PANELS ARE PLENUM | | | RATED IN ACCORDANCE WITH SECTION 602.2.1, AND THAT THEY | | | WILL BE SIZED LARGE ENOUGH TO REMOVE AND REPLACE ANY | | | HP'S OR OTHER MECHANICAL EQUIPMENT LOCATED ABOVE | | | CEILINGS- SECTION 306.1 | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | |
|