2017-12-12 11:15:141ST REVIEW FBC-2014 MECHANICAL, EXISTING BUILDING, FUEL
 GAS CODES 2014.
 PERMIT #17111177
 12/12/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE NEW
 GRIDDLE- SECTION 623.1 FBC-14 FUEL GAS.
  
 2) PLACE A NOTE ON THE PLAN INDICATING THAT ANY
 ALTERATIONS TO THE EXISTING KITCHEN EXHAUST HOOD AND
 FIRE SUPPRESSION SYSTEM WILL BE DONE UNDER SEPARATE
 PERMIT.
  
 3) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE
 AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL
 ROOMS AND SPACES PER TABLE 403.3 FBC-14 MECHANICAL.
 PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND
 PROVIDED CFMS OF OUTDOOR AIR.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  