| Notes |
| Date |
Text |
| 2017-12-12 11:15:14 | 1ST REVIEW FBC-2014 MECHANICAL, EXISTING BUILDING, FUEL | | | GAS CODES 2014. | | | PERMIT #17111177 | | | 12/12/17 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE NEW | | | GRIDDLE- SECTION 623.1 FBC-14 FUEL GAS. | | | | | | 2) PLACE A NOTE ON THE PLAN INDICATING THAT ANY | | | ALTERATIONS TO THE EXISTING KITCHEN EXHAUST HOOD AND | | | FIRE SUPPRESSION SYSTEM WILL BE DONE UNDER SEPARATE | | | PERMIT. | | | | | | 3) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE | | | AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL | | | ROOMS AND SPACES PER TABLE 403.3 FBC-14 MECHANICAL. | | | PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND | | | PROVIDED CFMS OF OUTDOOR AIR. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | |
|