| 2017-12-14 10:05:34 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 | | | 5TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION | | | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. PROVIDE GRAPH/CALCULATION OF INTERIOR LIGHTING POWER | | | ALLOWANCES PER THE FBC ENERGY CODE IN RELATION TO THE | | | CONNECTED INTERIOR LIGHTING PROPOSED TO CONFIRM THE | | | ADDITIONAL FIXTURES DOES NOT EXCEED THE ALLOWABLE | | | WATTAGE FOR THE SPACE. FBC EC 405.5.2 | | | 2. PROVIDE THE ADDITIONAL AUTOMATIC LIGHTING CONTROLS | | | FOR NEW LIGHTING INSTALLED STIPULATED IN THE FBC ENERGY | | | CODE. FBC EC 405.2.2, 405.2.2.2 | | | 3. PROVIDE CORRECT ADDRESS ON PLANS, THE SUITE NUMBER | | | IS NOT LISTED. FBC 107.2.1 | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|