| 2017-12-08 15:30:02 | 2014 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 17111177 |
| | ADD: 330 CLEMATIS ST. SUITE: 110 |
| | CONT: NEW VISION CONSTRUCTION & DESIGN |
| | TEL: 954-709-6360 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: FRI. DEC. 08/2017 |
| | ACTION: DENIED |
| | |
| | 1) SHEET A1.0 THE FLOOR PLAN HAS 61 SEATS THAT ARE |
| | ACCOUNTED FOR, THE PLAN IS NOT CLEAR TO THE RIGHT SIDE |
| | OF THE SHEET WHAT APPEARS AS SEATS AND TABLES BUT THIS |
| | AREA MAY BRING THE SEATING LOAD TO OVER 80 CLIENTS. 80 |
| | X 0.05 = 4 ACCESSIBLE SEATS REQUIRED. 2014 |
| | ACCESSIBILITY CODE 226.1 WHERE DINING SURFACES ARE |
| | PROVIDED FOR THE CONSUMPTION OF FOOD OR DRINK, AT LEAST |
| | 5 PERCENT OF THE SEATING SPACES AND STANDING SPACES AT |
| | THE DINING SURFACES SHALL COMPLY WITH 902. |
| | |
| | 1A) 226.2 DISPERSION. DINING SURFACES AND WORK SURFACES |
| | REQUIRED TO COMPLY WITH 902 SHALL BE DISPERSED |
| | THROUGHOUT THE SPACE OR FACILITY CONTAINING DINING |
| | SURFACES AND WORK SURFACES. |
| | |
| | 1B) 902.1 .DINING SURFACES AND WORK SURFACES SHALL |
| | COMPLY WITH 902.2 AND 902.3. ADVISORY 902.1 GENERAL. |
| | DINING SURFACES INCLUDE, BUT ARE NOT LIMITED TO, BARS, |
| | TABLES, LUNCH COUNTERS, AND BOOTHS. |
| | |
| | 1B)(1) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR |
| | SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD |
| | APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE |
| | COMPLYING WITH 306 SHALL BE PROVIDED. |
| | |
| | 1B)(2) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND |
| | WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES |
| | MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. |
| | |
| | 2) THE A1.0 SHEET SHOWS THE REMOVAL AND INDICATES NEW |
| | MECHANICAL EQUIPMENT. THERE IS NO MECHANICAL SHEET IN |
| | THIS SET OF PLANS. THIS REVIEW CYCLE A THOROUGH REVIEW |
| | COULD NOT BE COMPLETED AND ADDITIONAL AND OR NEW |
| | COMMENTS MAY OCCUR ON SUBSEQUENT REVIEWS. |
| | LATERAL FORCE-RESISTING SYSTEM. FOR ALL ROOF TOP |
| | EQUIPMENT, CURBS, FANS OR A/C STANDS, AND OR VENTS, |
| | DETAILED ATTACHMENT TO THE ROOF FRAMING & DECK AS WELL |
| | AS FROM THE CURB OR ROOF STAND TO THE EQUIPMENT ABOVE. |
| | |
| | 2014 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL |
| | MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY |
| | METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT |
| | EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY |
| | AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES. |
| | EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE |
| | OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES |
| | SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND |
| | LOADS. |
| | |
| | 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER BN, PX, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES |
| | DEPARTMENT |
| | 401 CLEMATIS ST. |
| | WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |