| Plan Review Notes For Permit 17111142 |
| Permit Number |
17111142 |
|
| Review Stop |
B |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2018-10-25 17:14:29 | PLAN | | | REVIEW COMMENTS | | | 3611 S. FLAGLER DRIVE | | | "THE CRYSTAL" 6 UNIT, 7 STOREY R-2 (CONDO) | | | AE FLOOD ZONE | | | | | | 4TH REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) FBC 107.2.1.3 PROVIDE CERTIFICATION DOCUMENTS FROM | | | THE THRESHOLD INSPECTOR THAT HAVE BEEN REVIEWED AND | | | ACCEPTED BY THE DESIGNER OF RECORD ATTESTING THAT THE | | | PRODUCTION PILES AND PILE CAPS HAVE BEEN INSPECTED AND | | | ARE INSTALLED PER THE PLANS FROM THE DESIGNER OF | | | RECORD. | | | | | | 2) FBC 110.3.7 SUBMIT THREE SETS OF A THRESHOLD | | | INSPECTION PLAN FROM THE NEW DESIGNER OF RECORD. THE | | | ENGINEER'S ORIGINAL HANDWRITTEN SIGNATURES ARE REQUIRED | | | ON PAPER DOCUMENTS PER FAC 61G15-23.003 | | | | | | 3) SHOW COMPLIANCE WITH FBC1816.1 TERMITE PROTECTION. | | | | | | 4) FBC 107.2.1THERE ARE SOME DISCREPANCIES BETWEEN THE | | | ARCHITECTURAL PLANS AND THE STRUCTURAL PLANS THAT NEED | | | TO BE ADDRESSED. ON SHEET S3.1 THE OPENING AND STAIRS | | | ARE SHOWN ON THE WEST SIDE OF THE FIRE PUMP ROOM. THE | | | SITE PLANS AND SHEETS A101 AND A201 SHOW THE DOOR ON | | | THE SOUTH END OF THE FIRE PUMP ROOM. | | | | | | 5) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT A | | | RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW | | | COMMENTS HAS BEEN ADDRESSED. | | | | | | | | | |
|