| 2018-04-10 09:01:15 | 2ND REVIEW: FBC 2014 5TH EDITION |
| | |
| | |
| | PREVIOUS COMMENTS NOT ADDRESSED THEY CAN BE ADDRESSED |
| | UNDER THE MAIN PERMIT IF REFERENCED SHEETS ARE REMOVED |
| | AND THE FOLLOWING IS PROVIDED . |
| | 1. PROVIDE ISOMETRIC WITH UNDERGROUND PIPING ONLY FOR |
| | SANITARY, WATER AND STORM SHOWING DFU, PIPE SIZE AND |
| | SQFT FOR STORM DRAINS. PER WPB AMEND TO FBC |
| | 107.3.5.1.3(13) |
| | 2. PROVIDE FLOOR PLAN WITH UNDER GROUND PIPING ONLY. |
| | PER WPB AMEND TO FBC 107.2.1 |
| | |
| | PLUMBING COMMENTS: TO EXPEDITE APPROVAL OF THIS PERMIT |
| | I SUGGEST SCHEDULING A MEETING TO GO OVER COMMENTS SEE |
| | MY CONTACT INFO BELOW. |
| | |
| | 1. THIS BUILDING SHALL COMPLY WITH FHA. PER FAIR |
| | HOUSING ACCESSIBILITY GUIDELINES : SECTION 3. FAIR |
| | HOUSING ACT DESIGN AND CONSTRUCTION REQUIREMENTS |
| | |
| | THE REGULATIONS ISSUED BY THE DEPARTMENT AT 24 CFR |
| | 100/205 STATE: |
| | |
| | SECTION 100.205 DESIGN AND CONSTRUCTION REQUIREMENTS. |
| | (A) COVERED MULTIFAMILY DWELLINGS FOR FIRST OCCUPANCY |
| | AFTER MARCH 13, 1991, SHALL BE DESIGNED AND CONSTRUCTED |
| | TO HAVE AT LEAST ONE BUILDING ENTRANCE ON AN ACCESSIBLE |
| | ROUTE UNLESS IT IS IMPRACTICAL TO DO SO BECAUSE OF THE |
| | SITE. FOR PURPOSES OF THIS SECTION, A COVERED |
| | MULTIFAMILY DWELLING SHALL BE DEEMED TO BE DESIGNED AND |
| | CONSTRUCTED FOR FIRST OCCUPANCY ON OR BEFORE MARCH 13, |
| | 1991, IF THEY ARE OCCUPIED BY THAT DATE OR IF THE LAST |
| | BUILDING PERMIT OR RENEWAL THEREOF FOR THE COVERED |
| | MULTIFAMILY DWELLINGS IS ISSUED BY A STATE, COUNTY OR |
| | LOCAL GOVERNMENT ON OR BEFORE JANUARY 13, 1990. THE |
| | BURDEN OF ESTABLISHING IMPRACTICALITY BECAUSE OF |
| | TERRAIN OR UNUSUAL SITE CHARACTERISTICS IS ON THE |
| | PERSON OR PERSONS WHO DESIGNED OR CONSTRUCTED THE |
| | HOUSING FACILITY. |
| | |
| | A) INDICATE ON THE PLAN WHICH FHA DESIGN DOCUMENT WILL |
| | BE USED IN DESIGNING BUILDING TO MEET FHA REQUIREMENTS. |
| | PER WPB AMEND TO FBC 107.2.1 |
| | B) INDICATE ON THE PLAN HOW FHA REQUIREMENTS 1-5 WILL |
| | BE MET. |
| | C) SHOW ON THE PLANS THE DIMENSIONS OF THE MOUNTING |
| | HEIGHTS FOR THE GRAB BAR BACKING. PER FHA REQUIREMENT 6 |
| | D) INDICATE ON THE PLAN WHICH DESIGN SPEC WILL BE USED |
| | FOR THE BATHROOMS. PER FHA REQUIREMENT 7 |
| | E) SHOW ON THE PLAN THE CLEAR FLOOR SPACE REQUIRED AT |
| | THE FIXTURES IN THE BATHROOMS AND KITCHEN. PER FHA |
| | REQUIREMENT 7 |
| | F) SHOW ON THE PLANS THE DIMENSIONS FOR THE HEIGHT AND |
| | DEPTH OF THE VANITY OR WING WALL ADJACENT TO THE WATER |
| | CLOSET. PER FHA REQUIREMENT 7 |
| | |
| | 2. PLEASE INDICATE ON THE PLAN FOR FOUNDATION ONLY. PER |
| | WPB AMEND TO FBC 107.2.1 |
| | |
| | 3. SHT. A701 SHOW THE SQFT AT EACH ROOF DRAIN. PER WPB |
| | AMEND TO FBC 107.2.1 AND FBC PL CH 11 |
| | |
| | 4. ON SHT. P-1 AND P-5 IT SHOWS 685 SQFT ON 3 OF THE |
| | ROOF DRAINS ON SHT A701 IT SHOWS THOSE SAME ROOF AREAS |
| | AS 3 DIFFERENT SIZES PLEASE CLARIFY. PER WPB AMEND TO |
| | FBC 107.2.1 |
| | |
| | 5. SHT. P-1 PLEASE PLACE NOTE ON PLAN A SEPARATE PERMIT |
| | IS REQUIRED FOR BACKFLOW DEVICES. PER WPB UTILITIES |
| | DEPARTMENT |
| | |
| | 6. SHT. P-6 SHOW SIZE ON THE BRANCH'S ON WATER MAIN |
| | RISER. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 7.SHT. P-1 SHOWS THE HOT AND COLD WATER PIPING TO THE |
| | WATER HEATER ON THE GROUND FLOOR AS 1/2" THE ISOMETRIC |
| | SHOWS IT AT 3/4" PLEASE CLARIFY. PER WPB AMEND TO FBC |
| | 107.2.1 |
| | |
| | 8. PLEASE LABEL ALL ALL WASTE AND SOIL STACKS ON |
| | ISOMETRICS , RISERS AND FLOOR PLANS. PER WPB AMEND TO |
| | FBC 107.2.1 |
| | |
| | 9. SHT. P-7 SHOW BRANCH'S AND SIZE OF BRANCH ON THE |
| | RISERS. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 10. SHT. P-8 SHOWS 2 ROUND ROOF DRAINS FOR OBSERVATION |
| | DECK SHT. A701 SHOWS 3 LINEAR FLOOR DRAINS ON THE |
| | OBSERVATION DECK PLEASE CLARIFY. PER WPB AMEND TO FBC |
| | 107.2.1 |
| | |
| | 11. LABEL STORM RISER TO MATCH THE FLOOR PLAN. PER WPB |
| | AMEND TO FBC 107.2.1 |
| | |
| | 12. PLEASE SHOW PUMP AND DRAIN PIPING FOR ELEVATOR |
| | SUMP. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |