| 2018-04-02 14:34:58 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| | 5TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION |
| | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | BE ADVISED THIS PLAN REVIEW IS NOT A FULL REVIEW AND IS |
| | BASED ON ITEMS NECESSARY FOR FOUNDATION PERMIT ONLY. |
| | THE FULL REVIEW WILL BE COMPLETED UNDER THE MAIN |
| | PERMIT. |
| | |
| | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED |
| | SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS |
| | COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY |
| | HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW |
| | COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS. |
| | |
| | 1. PROVIDE DETAILS OF THE SECOND POWER SOURCE REQUIRED |
| | FOR FIRE PUMP. NEC 695.3(B) (NOT PROVIDED. FIRE PUMP |
| | REQUIRES A RELIABLE POWER SOURCE AND THE CITY DOES NOT |
| | CONSIDER FPL AS RELIABLE, THEREFORE A GENERATOR OR |
| | OTHER MEANS OF ALTERNATE POWER IS REQUIRED.) |
| | 2. FEEDER TO THE FIRE PUMP IS NOT PERMITTED TO BE RUN |
| | THROUGH THE BUILDING. PROVIDE CORRECTION. NEC 695.6, |
| | 695.4(B)(2), 230.79 (NO COMMENT RESPONSE PROVIDED. IF |
| | THIS FEED IS INSTALLED AS SHOWN CURRENTLY, IT: "SHALL |
| | BE INSTALLED USING ONE OF THE FOLLOWING METHODS: (1) BE |
| | ENCASED IN A MINIMUM 50 MM (2 IN.) OF CONCRETE |
| | (2) BE PROTECTED BY A FIRE-RATED ASSEMBLY LISTED TO |
| | ACHIEVE A MINIMUM FIRE RATING OF 2 HOURS AND DEDICATED |
| | TO THE FIRE PUMP CIRCUIT(S)(3) BE A LISTED ELECTRICAL |
| | CIRCUIT PROTECTIVE SYSTEM WITH A MINIMUM 2-HOUR FIRE |
| | RATING." NEC 695.6(A)(2) ) |
| | 3. IF A DISCONNECT FOR THE FIRE PUMP IS TO BE INSTALLED |
| | EVEN THOUGH IT IS NOT REQUIRED, IT MUST BE IN A REMOTE |
| | LOCATION FROM THE SERVICE DISCONNECTS. PROVIDE |
| | CORRECTION. NEC 695.4(B)(3), 230.72(B) (STILL SHOWN IN |
| | SAME LOCATION AS MAIN # 1, IT IS ALSO SHOWN WITH 2 |
| | MEANS OF DISCONNECTTHAT ARE NOT FUSED, WHICH IS A CODE |
| | VIOLATION) |
| | 4. PROVIDE FIRE PUMP SPEC SHEET, DETAILING THE LOCKED |
| | ROTOR CURRENT OF FIRE PUMP MOTOR. INCLUDE ANY DETAILS |
| | OF ELECTRICAL LOAD FOR ASSOCIATED EQUIPMENT. NEC 110.3, |
| | 695.10 (NOT PROVIDED) |
| | 5. RISER DIAGRAM SHOWS THE FIRE PUMP CONTROLLER IN THE |
| | PUMP ROOM. HOWEVER, THE PLUMBING PLAN SHOW THE DOMESTIC |
| | WATER PUMPS IN THIS ROOM, AND IT APPEARS THAT THE |
| | CLEARANCES REQUIRED ARE NOT POSSIBLE FOR THIS SIZE |
| | ROOM. PROVIDE CLARIFICATION. NEC 110.26; FBC 107.2.1 |
| | (NO RESPONSE PROVIDED) |
| | 6. PROVIDE ACCURATE LOAD CALCULATION FOR ENTIRE |
| | SERVICE. THE LOAD CALCULATION PROVIDED REFERENCES NEC |
| | 220.32, WHICH DOES NOT EXIST. ADDITIONALLY, THE FULL |
| | HOUSE LOAD IS NOT INCLUDED IN THE CALCULATION. PROVIDE |
| | CLARIFICATION AND CORRECTIONS. NEC 220 (LOAD |
| | CALCULATION INCORRECT, ALL LOADS IN HOUSE PANEL NOT |
| | INCLUDED IN LOAD CALC , NEC 220.32 SHOWN FOR MAIN # 1 |
| | LOAD CALC DOES NOT EXIST, PROVIDE CORRECT CODE |
| | REFERENCE.) |
| | |
| | NEW COMMENTS: |
| | |
| | 7. COVER SHEET STATES THAT PLAN IS DESIGNED PER THE |
| | 2014 FBC RESIDENTIAL. THE PROVISIONS OF THE FLORIDA |
| | BUILDING CODE, RESIDENTIAL SHALL APPLY TO THE |
| | CONSTRUCTION, ALTERATION, MOVEMENT, ENLARGEMENT, |
| | REPLACEMENT, REPAIR, EQUIPMENT, USE AND OCCUPANCY, |
| | LOCATION, REMOVAL AND DEMOLITION OF DETACHED ONE- AND |
| | TWO-FAMILY DWELLINGS AND TOWNHOUSES NOT MORE THAN THREE |
| | STORIES ABOVE GRADE PLANE IN HEIGHT WITH A SEPARATE |
| | MEANS OF EGRESS AND THEIR ACCESSORY STRUCTURES NOT MORE |
| | THAN THREE STORIES ABOVE GRADE PLANE IN HEIGHT. PROVIDE |
| | CORRECTION. FBC RE R101.2 |
| | 8. PLEASE BE ADVISED THAT SOME COMMENT HAV NOT BEEN |
| | ADDRESSED FOR TWO REVIEWS. IF UPON THE THIRD REVIEW, IF |
| | IT IS NECESSARY TO REJECT THE SUBMITTED PLAN A THIRD |
| | TIME FOR THE SAME REASONS, AN ADDITIONAL PLAN REVIEW IS |
| | REQUIRED. FLORIDA STATUTES STATE: ?WITH RESPECT TO |
| | EVALUATION OF DESIGN PROFESSIONALS? DOCUMENTS, IF A |
| | LOCAL GOVERNMENT FINDS IT NECESSARY, IN ORDER TO |
| | ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING CODE AND |
| | ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS REQUIRED BY |
| | THE CODE THREE OR MORE TIMES FOR FAILURE TO CORRECT A |
| | CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY NOTED IN |
| | EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, EGRESS, |
| | FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY, |
| | ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, |
| | MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER |
| | REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING |
| | COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL |
| | GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH |
| | REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION, |
| | A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE |
| | PERMIT FEE ATTRIBUTED TO PLANS REVIEW. FS 553.80(2)(B)? |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |
| | SINCERELY, |
| | |
| | JOHN PEARSON |
| | ELECTRICAL PLANS EXAMINER |