| 2017-12-14 14:07:35 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| | 5TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION |
| | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | BE ADVISED THIS PLAN REVIEW IS NOT A FULL REVIEW AND IS |
| | BASED ON ITEMS NECESSARY FOR FOUNDATION PERMIT ONLY. |
| | THE FULL REVIEW WILL BE COMPLETED UNDER THE MAIN |
| | PERMIT. |
| | |
| | 1. PROVIDE DETAILS OF THE SECOND POWER SOURCE REQUIRED |
| | FOR FIRE PUMP. NEC 695.3(B) |
| | 2. FEEDER TO THE FIRE PUMP IS NOT PERMITTED TO BE RUN |
| | THROUGH THE BUILDING. PROVIDE CORRECTION. NEC 695.6, |
| | 695.4(B)(2), 230.79 |
| | 3. IF A DISCONNECT FOR THE FIRE PUMP IS TO BE INSTALLED |
| | EVEN THOUGH IT IS NOT REQUIRED, IT MUST BE IN A REMOTE |
| | LOCATION FROM THE SERVICE DISCONNECTS. PROVIDE |
| | CORRECTION. NEC 695.4(B)(3), 230.72(B) |
| | 4. PROVIDE FIRE PUMP SPEC SHEET, DETAILING THE LOCKED |
| | ROTOR CURRENT OF FIRE PUMP MOTOR. INCLUDE ANY DETAILS |
| | OF ELECTRICAL LOAD FOR ASSOCIATED EQUIPMENT. NEC 110.3, |
| | 695.10 |
| | 5. RISER DIAGRAM SHOWS THE FIRE PUMP CONTROLLER IN THE |
| | PUMP ROOM. HOWEVER, THE PLUMBING PLAN SHOW THE DOMESTIC |
| | WATER PUMPS IN THIS ROOM, AND IT APPEARS THAT THE |
| | CLEARANCES REQUIRED ARE NOT POSSIBLE FOR THIS SIZE |
| | ROOM. PROVIDE CLARIFICATION. NEC 110.26; FBC 107.2.1 |
| | 6. PROVIDE ACCURATE LOAD CALCULATION FOR ENTIRE |
| | SERVICE. THE LOAD CALCULATION PROVIDED REFERENCES NEC |
| | 220.32, WHICH DOES NOT EXIST. ADDITIONALLY, THE FULL |
| | HOUSE LOAD IS NOT INCLUDED IN THE CALCULATION. PROVIDE |
| | CLARIFICATION AND CORRECTIONS. NEC 220 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |
| | SINCERELY, |
| | |
| | JOHN PEARSON |
| | ELECTRICAL PLANS EXAMINER |
| | 561-805-6746 |
| | [email protected] |
| | |