| 2018-05-01 17:24:34 | FLORIDA BUILDING CODE 2017 6TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED |
| | NFPA 70 2014 EDITION |
| | |
| | JAKE LEAHY |
| | ELECTRICAL PLANS EXAMINER II |
| | 561-805-6713 |
| | [email protected] |
| | |
| | |
| | PLAN STATES LANDSCAPE LIGHTING, PLAN IS SHOWING POOL |
| | LIGHTING? |
| | |
| | PANEL SCHEDULE SHOWS CIRCUIT #7 AS LANDSCAPE LIGHTING? |
| | THIS CIRCUIT FEEDS THE POOL LIGHTS. |
| | |
| | FBC 454.1.9.8.4 |
| | IF NIGHT OPERATION IS PROPOSED, 6 FOOTCANDLES (60 LUX) |
| | OF LIGHT SHALL BE PROVIDED ON THE POOL DECK AND THE |
| | WATER FEATURE AREA. |
| | LIGHTING THAT MAY BE EXPOSED TO THE FEATURE POOL WATER |
| | SHALL NOT EXCEED 15 VOLTS, SHALL BE INSTALLED IN |
| | ACCORDANCE WITH |
| | MANUFACTURER?S SPECIFICATIONS AND BE APPROVED FOR SUCH |
| | USE BY UL OR NSF. |
| | |
| | SEE 64E-9.006 (C) (3) |
| | 3. UNDERWATER LIGHTING ? UNDERWATER LIGHTING SHALL |
| | UTILIZE TRANSFORMERS AND LOW VOLTAGE CIRCUITS WITH EACH |
| | UNDERWATER LIGHT BEING GROUNDED. THE MAXIMUM VOLTAGE |
| | FOR EACH LIGHT SHALL BE 15 VOLTS AND THE MAXIMUM |
| | INCANDESCENT LAMP SIZE SHALL BE 300 WATTS. THE LOCATION |
| | OF THE UNDERWATER LIGHTS SHALL BE SUCH THAT THE |
| | UNDERWATER ILLUMINATION IS AS UNIFORM AS POSSIBLE AND |
| | SHALL NOT BE LESS THAN 18 INCHES BELOW THE NORMAL |
| | OPERATING WATER LEVEL DETERMINED BY THE CENTERLINE OF |
| | THE SKIMMER OR TOP LIP OF THE GUTTER. ALL UNDERWATER |
| | LIGHTS WHICH DEPEND UPON SUBMERSION FOR SAFE OPERATION |
| | SHALL HAVE PROTECTION FROM OVERHEATING WHEN NOT |
| | SUBMERGED. UNDERWATER LIGHTING REQUIREMENTS CAN BE |
| | WAIVED WHEN THE OVERHEAD LIGHTING PROVIDES AT LEAST |
| | 15 FOOT CANDLES OF ILLUMINATION AT THE POOL WATER |
| | SURFACE AND POOL WET DECK SURFACE. ALTERNATIVE LIGHTING |
| | SYSTEMS WHICH USE 15 VOLTS OR LESS, OR USE NO |
| | ELECTRICITY IN THE POOL OR ON THE POOL DECK, SUCH AS |
| | LED, (LIGHT |
| | EMITTING DIODE) OR FIBER OPTIC SYSTEMS, MAY BE UTILIZED |
| | IF THE APPLICANT DEMONSTRATES TO REASONABLE CERTAINTY |
| | THAT THE SYSTEM DEVELOPMENT HAS ADVANCED TO THE POINT |
| | WHERE THE DEPARTMENT IS CONVINCED THAT THE POOL |
| | ILLUMINATION IS EQUAL TO THE REQUIREMENTS IN |
| | SUBPARAGRAPH 1. AND 2. ABOVE. |
| | |
| | FIXTURES L-4 ARE SHOWN TO BE 120 VOLT, SEE FBC ABOVE |
| | |
| | NEED CUT SHEETS FOR FIXTURE AND NICHE |
| | |
| | PLEASE SUBMIT A SHEET SHOWING THE MOUNTING IN THE WALL |
| | ABOVE OR BELOW THE WATER. |