| Plan Review Notes For Permit 17111031 |
| Permit Number |
17111031 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2018-03-19 14:52:16 | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED | | | NFPA 70 2011 EDITION | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | ELECTRICAL WORK IS NOT CLEAR ON WHAT IS BEING DONE. | | | | | | SUBMIT AN ELECTRICAL PLAN SHOWING EXACTLLY WHAT IS | | | BEING DONE. | | | | | | FOR LIGHTING OUTDOORS SEE BELOW | | | | | | EXTERIOR LIGHTING CONTROLS. LIGHTING NOT DESIGNATED FOR | | | DUSK-TO-DAWN OPERATION SHALL BE CONTROLLED BY EITHER A | | | COMBINATION OF A | | | PHOTOSENSOR AND A TIME SWITCH, OR AN ASTRONOMICAL TIME | | | SWITCH. LIGHTING DESIGNATED FOR DUSK-TO-DAWN OPERATION | | | SHALL BE CONTROLLED | | | BY AN ASTRONOMICAL TIME SWITCH OR PHOTOSENSOR. ALL TIME | | | SWITCHES SHALL BE CAPABLE OF RETAINING PROGRAMMING AND | | | THE TIME SETTING | | | DURING LOSS OF POWER FOR A PERIOD OF AT LEAST 10 HOURS. | | | FBC CE 405.2.4 | | | | | | | | | | | | |
|