| 2018-01-11 16:30:23 | 2ND REVIEW FBC-2014 MECHANICAL, ENERGY CONSERVATION |
| | CODE |
| | PERMIT #17111014 |
| | 1/11/18 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) AC CALCULATIONS: PLEASE PROVIDE ADDITIONAL "PROJECT |
| | INFORMATION" IN THE NOTES SECTION IDENTIFTYING ALL OF |
| | THE 12 APARTMENTS INCLUDED IN THE CALCULATIONS, AND |
| | WHICH APARTMENT ON WAS USED AS THE BASE MODEL FOR THE |
| | MULTIPLE ORIENTATION CALCULATIONS. WAS THE APARTMENT ON |
| | THE 1ST, 2ND, OR 3RD LEVEL? DO THE MULTIPLE |
| | ORIENTATIONS PERTAIN TO ALL 3 LEVELS? |
| | |
| | 2) SHEETS M-1 & M-2: PLEASE REMOVE OR CORRECT ALL THE |
| | NOTES THAT ARE SPECIFYING PVC CONDENSATE PIPING IN THE |
| | AC CLOSETS. REFER TO SECTIONS R403.2.2 FBC-14 ENERGY |
| | CONSERVATION AND SECTION 602.2.1 FBC-14 MECHANICAL- PVC |
| | IS COMBUSTIBLE AND NOT PERMITTED IN THE AC CLOSETS. |
| | PLEASE NOTE THAT IS IS SPECIFIED AS COPPER (CU) IN THE |
| | AIR HANDLER DETAIL ON M-3. |
| | |
| | 3) SHEET A-7.1: PLEASE CLARIFY HOW THE AC CLOSET WOOD |
| | DOOR IS ALSO SPECIFIED AS "NON-COMBUSTIBLE" IN THE |
| | SCHEDULE. REFER TO THE CODE SECTIONS LISTED IN COMMENT |
| | #2. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |