| 2017-12-14 19:11:47 | 1ST REVIEW: FBC 2014 5TH EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. PROVIDE DIMENSION BETWEEN THE TUB AND CENTER OF |
| | WATER CLOSET, 18" ABSOLUTE IS REQUIRED. PER FHA DESIGN |
| | MANUAL REQUIREMENT 7 PG. 7.43 |
| | |
| | 2. PLEASE SHOW CLEAR FLOOR SPACE FOR THE WATER CLOSETS. |
| | PER FHA DESIGN MANUAL REQUIREMENT 7 PG. 7.43 |
| | |
| | 3. SHT. A-6.3 DETAIL #3(B) WHAT IS THE DIMENSION OF |
| | 1'4" FOR PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 4. PROVIDE DIMENSION FOR DEPTH OF VANITY , MAX 24" PER |
| | PER FHA DESIGN MANUAL REQUIREMENT 7 PG. 7.43. 7.44 |
| | |
| | 5. PLEASE PROVIDE A DETAIL FOR THE EMERGENCY OVERFLOW |
| | SCUPPER SHOWING THE DIMENSION FROM THE LOWEST POINT OF |
| | THE ROOF AND THE BOTTOM OF THE SCUPPER. PER FBC PL |
| | 1101.7 |
| | |
| | 6. IN THE AC CLOSETS WHAT TYPE OF PIPE WILL BE USED FOR |
| | THE PAN DRAIN AND THE CONDENSATE DRAIN. PER WPB AMEND |
| | TO FBC 107.2.1 |
| | |
| | 7. PLEASE CHANGE THE NOTE ON THE PLAN ON THE WATER |
| | RISER PAGE TO READ THE MANUFACTURE SPECIFICATION FOR |
| | THE SUBMETER SHALL BE PROVIDED PRIOR TO INSPECTION. PER |
| | WPB AMEND TO FBC 107.2.1 |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561-805-6711 |
| | [email protected] |
| | |