Plan Review Notes
Plan Review Notes For Permit 17111014
Permit Number 17111014
Review Stop M
Sequence Number 1
Notes
Date Text
2017-12-12 17:53:421ST REVIEW FBC-2014 MECHANICAL AND FBC-14RESIDENTIAL
 ENERGY CODE
 PERMIT #1711014
 12/12/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE COOLING AND HEATING CALCULATIONS FOR THE AC
 SYSTEMS- SECTION R403.6.1 FBC-14 ENERGY CONSERVATION
  
 2) THE 718 TOTAL SQUARE FOOTAGE LISTED ON PAGE 1 OF THE
 ENERGY EFFICIENCY FORM R405-2014 INDICATES THE
 COMPLIANCE REPORT IS FOR ONLY ONE OF THE 12 APARTMENTS.
 COMPLIANCE FOR THE ENTIRE BUILDING IS REQUIRED PER
 SECTION R101.2 FBC-14 ENERGY CONSERVATION
  
 3) THE OWNER/AGENT SHALL SIGN AND DATE THE ENERGY FORM
 R405-2014 AS REQUIRED BY SECTION R103.1.1.2 FBC-14
 ENERGY CONSERVATION.
  
 4) MANDATORY BLOWER DOOR TESTING IS REQUIRED PER
 SECTION R402.4.1.2. PLEASE PLACE A NOTE ON THE PLANS
 ACCORDINGLY.
  
 5) AC STAND NOA #15-0902.05: THE ENGINEER OF RECORD
 SHALL CIRCLE, HIGHLIGHT, OR OTHERWISE MARK ALL DETAILS,
 NOTES, DESIGN PRESSURES ETC. THAT PERTAIN TO THE
 PROPOSED ROOFTOP AC INSTALLATIONS.
  
 6) M1: EXHAUST VENTILATION AT A RATE OF 25 CFMS
 CONTINUOUSLY OR 100 CFMS INTERMITTENTLY IS REQUIRED FOR
 THE KITCHENS- SEE TABLE 403.3
  
 7) M1: AUTO-CONTROLLED SHUT OFF DAMPERS ARE REQUIRED
 FOR THE OUTDOOR AIR SUPPLY DUCTS- SECTION C403.2.44
 FBC-14 ENERGY CONSERVATION. PLEASE SHOW THE LOCATION OF
 THE DAMPERS AND PROVIDE A PRODUCT DATA SHEET THAT
 INDICATES COMPLIANCE WITH SECTION C402.4.5.2.
  
 8) SUBMIT A FLORIDA PRODUCT APPROVAL OR A MIAMI-DADE
 NOA FOR THE THE WALL CAPS. IN LIEU OF STATE APPROVAL,
 MANUFACTURER'S SPECIFICATIONS MAY BE SUBMITTED THAT
 INDICATE THE PRODUCT IS COMPLIANT WITH SECTION 401.5
  
 CHRISTOPHER L. COLE
 BUILDING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  