| Date |
Text |
| 2017-12-12 17:53:42 | 1ST REVIEW FBC-2014 MECHANICAL AND FBC-14RESIDENTIAL |
| | ENERGY CODE |
| | PERMIT #1711014 |
| | 12/12/17 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PROVIDE COOLING AND HEATING CALCULATIONS FOR THE AC |
| | SYSTEMS- SECTION R403.6.1 FBC-14 ENERGY CONSERVATION |
| | |
| | 2) THE 718 TOTAL SQUARE FOOTAGE LISTED ON PAGE 1 OF THE |
| | ENERGY EFFICIENCY FORM R405-2014 INDICATES THE |
| | COMPLIANCE REPORT IS FOR ONLY ONE OF THE 12 APARTMENTS. |
| | COMPLIANCE FOR THE ENTIRE BUILDING IS REQUIRED PER |
| | SECTION R101.2 FBC-14 ENERGY CONSERVATION |
| | |
| | 3) THE OWNER/AGENT SHALL SIGN AND DATE THE ENERGY FORM |
| | R405-2014 AS REQUIRED BY SECTION R103.1.1.2 FBC-14 |
| | ENERGY CONSERVATION. |
| | |
| | 4) MANDATORY BLOWER DOOR TESTING IS REQUIRED PER |
| | SECTION R402.4.1.2. PLEASE PLACE A NOTE ON THE PLANS |
| | ACCORDINGLY. |
| | |
| | 5) AC STAND NOA #15-0902.05: THE ENGINEER OF RECORD |
| | SHALL CIRCLE, HIGHLIGHT, OR OTHERWISE MARK ALL DETAILS, |
| | NOTES, DESIGN PRESSURES ETC. THAT PERTAIN TO THE |
| | PROPOSED ROOFTOP AC INSTALLATIONS. |
| | |
| | 6) M1: EXHAUST VENTILATION AT A RATE OF 25 CFMS |
| | CONTINUOUSLY OR 100 CFMS INTERMITTENTLY IS REQUIRED FOR |
| | THE KITCHENS- SEE TABLE 403.3 |
| | |
| | 7) M1: AUTO-CONTROLLED SHUT OFF DAMPERS ARE REQUIRED |
| | FOR THE OUTDOOR AIR SUPPLY DUCTS- SECTION C403.2.44 |
| | FBC-14 ENERGY CONSERVATION. PLEASE SHOW THE LOCATION OF |
| | THE DAMPERS AND PROVIDE A PRODUCT DATA SHEET THAT |
| | INDICATES COMPLIANCE WITH SECTION C402.4.5.2. |
| | |
| | 8) SUBMIT A FLORIDA PRODUCT APPROVAL OR A MIAMI-DADE |
| | NOA FOR THE THE WALL CAPS. IN LIEU OF STATE APPROVAL, |
| | MANUFACTURER'S SPECIFICATIONS MAY BE SUBMITTED THAT |
| | INDICATE THE PRODUCT IS COMPLIANT WITH SECTION 401.5 |
| | |
| | CHRISTOPHER L. COLE |
| | BUILDING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |
| | |