Plan Review Notes
Plan Review Notes For Permit 17111013
Permit Number 17111013
Review Stop M
Sequence Number 1
Notes
Date Text
2017-12-12 16:52:171ST REVIEW FBC-2014 MECHANICAL, ENERGY CONSERVATION
 CODES, WPB AMENDMENTS TO THE FBC.
 PERMIT #17111013
 12/12/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M1: LABEL THE COMPACTOR ROOM AND THE ELEVATOR
 SHAFTS- SECTION 107.2.1 WPB AMENDMENTS
  
 2) SHEETS M1, M2: NUMBER THE APARTMENTS TO MATCH THE
 APARTMENT NUMBERS SHOWN IN THE AC CALCULATIONS- SECTION
 107.2.1
  
 3) SHEETS M2 & M3: LABEL ALL ROOMS IN THE CENTER CORE
 AND SHOW HOW THEY ARE BEING VENTILATED- SECTION
 107.2.1.
  
 4) M3: SHOW THE HOISTWAY VENT OPENING AND PROVIDE A
 FIRE DAMPER IN THE OPENING- SECTION 607.5 FBC-14
 MECHANICAL
  
 5) M4: EXHAUST VENTILATION AT A RATE OF 25 CFMS
 CONTINUOUSLY OR 100 CFMS INTERMITTENTLY IS REQUIRED FOR
 THE KITCHENS- SEE TABLE 403.3
  
 6) M4: AUTO-CONTROLLED SHUT OFF DAMPERS ARE REQUIRED
 FOR THE OUTDOOR AIR SUPPLY DUCTS- SECTION C403.2.44
 FBC-14 ENERGY CONSERVATION. PLEASE SHOW THE LOCATION OF
 THE DAMPERS AND PROVIDE A PRODUCT DATA SHEET THAT
 INDICATES COMPLIANCE WITH SECTION C402.4.5.2.
  
 7) M5: REMOVE THE ELEVATOR CONTROL ROOM THROUGH THE
 WALL AC SCHEDULE- NOT USED.
  
 8) THE AC CALCULATIONS ARE INDICATING SUMMER DRY BULB
 AND WET BULB TEMPERATURES THAT ARE LOWER THAN THE
 TEMPERATURES LISTED FOR WEST PALM BEACH IN ACCA MANUAL
 N WHICH ARE 90 AND 78 DEGREES. VERIFY THAT THE
 WRIGHTSOFT CALCULATION PROGRAM IS COMPLIANT WITH
 ASHRAE/ACCA STANDARD 183 OR ACCA MANUAL N PER SECTION
 C403.2.1 FBC-14 ENERGY CONSERVATION.
  
 9) SUBMIT FLORIDA PRODUCT APPROVALS OR MIAMI-DADE NOAS
 FOR THE LOUVERS AND THE WALL CAPS.
  
 10) AC STAND NOA #15-0902.05: THE ENGINEER OF RECORD
 SHALL CIRCLE, HIGHLIGHT, OR OTHERWISE MARK ALL DETAILS,
 NOTES, DESIGN PRESSURES ETC. THAT PERTAIN TO THE
 PROPOSED ROOFTOP AC INSTALLATIONS
  
 11) COMMISSIONING OF THE MECHANICAL SYSTEMS IS REQUIRED
 PER SECTION C408.2 FBC-14 ENERGY CONSERVATION. SUBMIT A
 COMMISSIONING PLAN AS OUTLINED IN SECTION C408.2.1 AND
 DESCRIBED IN SECTIONS C403.2.2- C408.2.3.3. PLEASE NOTE
 THAT A COPY OF THE COMMISSIONING REPORT SHALL BE
 SUBMITTED FOR REVIEW AT FINAL INSPECTION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  