| Date |
Text |
| 2018-01-18 08:20:46 | 1) SHT. P-6 - THERE IS A DDOTTED LINE SHOWN ON THE PLAN |
| | THAT IS CALLED OUT AS DOMESTIC WATER. THERE IS NO PIPE |
| | SIZE SHOWN ON THE PLANS OR WHERE IT ORIGINATES OR |
| | TERMINATES. CLARIFY. WPB AMEND. TO FBC SEC. 107.2.1. |
| | 2) SHT. P-6 SHOWS A 3 INCH COLD WATER LINE AND IT |
| | APPEARS THE SAME LINE IS SHOWN AS 2 INCH ON SHT. P-6.1. |
| | CLARIFY. |
| | 3) ARE ALL THE DWELLING UNIT BATHROOMS DESIGNED ON |
| | DESIGN SPECIFICATION "A" OF THE FAIR HOUSSING DEIGN |
| | MANUAL? CLARIFY.REFER TO SHT. A-1.2. |
| | 4) WHERE ARE THE STORM DRAINAGE AREAS #19 & #20 LOCATED |
| | ON THE PLANS? CLEARLY SHOW THE LOCATION. |
| | 5) SHTS. A-6.5.1 THROUGH A-6.5.4 - IT IS DIFFICULT TO |
| | DETERMINE IF THE REQUIRED 30 INCH BY 48 INCH CLEAR |
| | FLOOR SPACE FOR THE LAVATORIES IS CENTERED ON THE |
| | FIXTURE AS REQUIRED BY THE FAIR HOUSING ACT DESIGN |
| | MANUAL PART TWO:CHAPTER 7. |
| | 6) SHTS. A-6.5.1 THROUGH A-6.5.4 - CLEARLY |
| | MARK/IDENTIFY THE REQUIRED CLEAR FLOOR SPACE FOR THE |
| | WATER CLOSETS ON THE PLANS AND SHOW THE DIMENSIONS. THE |
| | CLEAR FLOOR SPACE FOR THE WATER CLOSETS SHALL BE 66 |
| | INCHES DEEP MINIMUM BY 48 INCHES WIDE MINIMUM, 56 |
| | INCHES DEEP MINIMUM BY 48 INCHES WIDE MINIMUM, OR 56 |
| | INCHES DEEP MINIMUM BY 60 INCHES WIDE MINIMUM DEPENDING |
| | ON THE DIRECTION OF APPROACH TO THE WATER CLOSET BY A |
| | PERSON USING A WHEELCHAIR. FAIR HOUSING ACT DESIGN |
| | MANUAL PART TWO, CHAPTER 7. |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |