2018-01-18 08:20:461) SHT. P-6 - THERE IS A DDOTTED LINE SHOWN ON THE PLAN
 THAT IS CALLED OUT AS DOMESTIC WATER. THERE IS NO PIPE
 SIZE SHOWN ON THE PLANS OR WHERE IT ORIGINATES OR
 TERMINATES. CLARIFY. WPB AMEND. TO FBC SEC. 107.2.1.
 2) SHT. P-6 SHOWS A 3 INCH COLD WATER LINE AND IT
 APPEARS THE SAME LINE IS SHOWN AS 2 INCH ON SHT. P-6.1.
 CLARIFY.
 3) ARE ALL THE DWELLING UNIT BATHROOMS DESIGNED ON
 DESIGN SPECIFICATION "A" OF THE FAIR HOUSSING DEIGN
 MANUAL? CLARIFY.REFER TO SHT. A-1.2.
 4) WHERE ARE THE STORM DRAINAGE AREAS #19 & #20 LOCATED
 ON THE PLANS? CLEARLY SHOW THE LOCATION.
 5) SHTS. A-6.5.1 THROUGH A-6.5.4 - IT IS DIFFICULT TO
 DETERMINE IF THE REQUIRED 30 INCH BY 48 INCH CLEAR
 FLOOR SPACE FOR THE LAVATORIES IS CENTERED ON THE
 FIXTURE AS REQUIRED BY THE FAIR HOUSING ACT DESIGN
 MANUAL PART TWO:CHAPTER 7.
 6) SHTS. A-6.5.1 THROUGH A-6.5.4 - CLEARLY
 MARK/IDENTIFY THE REQUIRED CLEAR FLOOR SPACE FOR THE
 WATER CLOSETS ON THE PLANS AND SHOW THE DIMENSIONS. THE
 CLEAR FLOOR SPACE FOR THE WATER CLOSETS SHALL BE 66
 INCHES DEEP MINIMUM BY 48 INCHES WIDE MINIMUM, 56
 INCHES DEEP MINIMUM BY 48 INCHES WIDE MINIMUM, OR 56
 INCHES DEEP MINIMUM BY 60 INCHES WIDE MINIMUM DEPENDING
 ON THE DIRECTION OF APPROACH TO THE WATER CLOSET BY A
 PERSON USING A WHEELCHAIR. FAIR HOUSING ACT DESIGN
 MANUAL PART TWO, CHAPTER 7.
  