| 2017-12-14 14:43:57 | 1) SHT. A-1.4 - ROOF DRAINAGE CALCULATIONS - THE |
| | PRIMARY ROOF DRAINAGE SYSTEM SHALL BE SIZED IN |
| | ACCORDANCE WITH TABLES 1106.2 (1), 1106.2 (2), AND |
| | 1106.3 NOT TABLE 1106.7 AS NOTED. REVISE THE NOTE. |
| | ALSO, PLEASE REFER THE ROOF AREA TO BEING DRAINED AS |
| | "ROOF AREA" INSTEAD OF "FLOOR AREA." |
| | 2) SHT.A-1.4 - CLARIFY WHY THE STAIR ROOF DRAINAGE IS |
| | CALCULATED AT 50%. WHY ISN'T THE STAIR ROOF AREA |
| | CALCULATED AT 100%? CLARIFY.IF THE STAIR ROOF HAS A |
| | PARAPET WALL THEN 1/2 OF THE AREA OF THE ENTIRE PARAPET |
| | WALL SHALL BE ADDED TO 100% OF THE ROOF AREA OF STAIR |
| | ROOF. 2014 FBC-PLUMBING SEC. 1106.4. |
| | 3) SHT. A-1.4 - ROOF DRAIN CALCULATIONS SHOW THE AREAS |
| | DRAINED AS ALL BEING LESS THAN 928 SQ. FT. WHERE IS THE |
| | 928 NUMBER COMING FROM AND WHY IS IT BEING USED? |
| | CLARIFY. |
| | 4) SHTS. A-6.5.1 THROUGH A-6.5.4 - SHOW ON THE FHA |
| | FLOOR PLANS OF THE UNITS THAT THE REQUIRED 48 INCH DEEP |
| | BY 30 INCH WIDE CLEAR FLOOR SPACE FOR THE LAVATORIES IS |
| | CENTERED ON THE FIXTURE ( LAVATORY) AS REQUIRED BY THE |
| | FAIR HOUSING ACT DESIGN MANUAL PART TWO: CHAPTER 7 OR |
| | PLACE A NOTE ON THE PLANS STATING SUCH. THIS ALSO |
| | APPLIES TO FIXTURES AND APPLIANCES IN THE KITCHEN. |
| | 5) SHTS. A-6.5.1 THROUGH A-6.5.4 - CLEARLY |
| | MARK/IDENTIFY THE REQUIRED CLEAR FLOOR SPACE FOR THE |
| | WATER CLOSETS ON THE PLANS AND SHOW THE DIMENSIONS. THE |
| | CLEAR FLOOR SPACE FOR THE WATER CLOSETS SHALL BE 66 |
| | INCHES DEEP MINIMUM BY 48 INCHES WIDE MINIMUM, 56 |
| | INCHES DEEP MINIMUM BY 48 INCHES WIDE MINIMUM, OR 56 |
| | INCHES DEEP MINIMUM BY 60 INCHES WIDE MINIMUM DEPENDING |
| | ON THE DIRECTION OF APPROACH TO THE WATER CLOSET BY A |
| | PERSON USING A WHEELCHAIR. FAIR HOUSING ACT DESIGN |
| | MANUAL PART TWO, CHAPTER 7. |
| | 6) CLARIFY THE USE/REASON FOR THE T- SHAPED TURNING |
| | SPACE SHOWN ON THE PLANS. THIS DOES NOT APPEAR TO BE |
| | COMPLIANT WITH THE FAIR HOUSING ACT DESIGN MANUAL IF |
| | THIS IS BEING USED FOR THE REQUIRED CLEAR FLOOR SPACE |
| | FOR THE WATER CLOSET.. THIS DETAIL APPEARS ON SEVERAL |
| | SHEETS. |
| | 7) SHTS. A-6.5.1 THROUGH A-6.5.4 - SHOW THE LENGTHS OF |
| | ALL REINFORCING FOR THE GRAB BARS FOR ALL FIXTURES ON |
| | THE PLAN. WPB AMEND. TO FBC SEC. 107.2.1, FHA DESIGN |
| | MANUAL PART TWO: CHAPTER 6. |
| | 8) SHT.A-6.5.1 - DETAIL #1 - SHOW THE MINIMUM AND |
| | MAXIMUM HEIGHTS OF THE REINFORCEMENT FOR THE TUB |
| | CONTROL WALL. SHOW THE LENGTH OF THE REINFORCEMENT. |
| | COMPLY WITH FHA DESIGN MANUAL PART TWO: CHAPTER 6. |
| | 9) SHT. A-6.5.1 - DETAIL #2 - THE ENDS OF THE GRAB BAR |
| | REINFORCEMENT FOR THE BATHTUB SHALL BE LOCATED A |
| | MAXIMUM OF 6 INCHES IN FROM THE SIDE WALLS OF THE TUB |
| | IN ACCORDANCE WITH THE FHA DESIGN MANUAL PART TWO: |
| | CHAPTER 6. SHOW THE LENGTH OF THE REINFORCEMENT ON THE |
| | DETAIL. |
| | 10) SHT. A-6.5.2 - DETAIL #1 - SHOW THE MINIMUM AND |
| | MAXIMUM HEIGHT OF THE REINFORCEMENT FOR THE GRAB BAR |
| | FOR THE TUB ON THE CONTROL WALL. SHOW THE LENGTH OF THE |
| | REINFORCEMENT. COMPLY WITH FHA DESIGN MANUAL PART TWO: |
| | CHAPTER 6. |
| | 11) SHT. A-6.5.2 - DETAIL #4 - THE ENDS OF THE GRAB BAR |
| | REINFORCEMENT FOR THE BATHTUB SHALL BE LOCATED A |
| | MAXIMUM OF 6 INCHES IN FROM THE SIDE WALLS OF THE TUB |
| | IN ACCORDANCE WITH THE FHA DESIGN MANUAL PART TWO: |
| | CHAPTER 6.SHOW THE LENGTH OF THE REINFORCEMENT ON THE |
| | DETAIL. |
| | 12) SHT. A-6.5.3 - DETAIL #2 - THE ENDS OF THE GRAB BAR |
| | REINFORCEMENT FOR THE BATHTUB SHALL BE LOCATED A |
| | MAXIMUM OF 6 INCHES IN FROM THE SIDE WALLS OF THE TUB |
| | IN ACCORDANCE WITH THE FHA DESIGN MANUAL PART TWO: |
| | CHAPTER 6.SHOW THE LENGTH OF THE REINFORCEMENT ON THE |
| | DETAIL. |
| | 13) SHT. A-6.5.4 - DETAIL #1 - SHOW THE MINIMUM AND |
| | MAXIMUM HEIGHT OF THE REINFORCEMENT FOR THE TUB CONTROL |
| | WALL. ALSO, SHOW THE MINIMUM AND MAXIMUM HEIGHTS FOR |
| | THE REINFORCEMENT FOR THE TOILET.SHOW THE LENGTHS OF |
| | THE REINFORCEMENT ON THE DETAIL. COMPLY WITH FHA DESIGN |
| | MANUAL PART TWO: CHAPTER 6. |
| | 14) SHT. A-6.5.4 - DETAIL # 2 - THE ENDS OF THE GRAB |
| | BAR REINFORCEMENT FOR THE BATHTUB SHALL BE LOCATED A |
| | MAXIMUM OF 6 INCHES IN FROM THE SIDE WALLS OF THE TUB |
| | IN ACCORDANCE WITH THE FHA DESIGN MANUAL PART TWO: |
| | CHAPTER 6.SHOW THE LENGTH OF THE REINFORCEMENT ON THE |
| | DETAIL. |
| | 15) SHT. A-6.5.4 - DETAIL #3 - SHOW THE MINIMUM AND |
| | MAXIMUM HEIGHT OF THE REINFORCEMENT FOR THE TUB AND |
| | SHOW THE MINIMUM LENGTH OF THE REINFORCEMENT ON THE |
| | DETAIL. COMPLY WITH FHA DESIGN MANUAL PART TWO: CHAPTER |
| | 6. |
| | 16) SHT. A-6.7.1 & A-6.7.2. - INDICATE ON THE PLAN IF |
| | THE ELEVATOR IS OF A TRACTION TYPE OR HYDRAULIC. IF THE |
| | ELEVATOR IS HYDRAULIC, THEN AN OIL SEPARATOR IS |
| | REQUIRED ON THE DISCHARGE FROM THE ELEVATOR SUMP PER |
| | THE 2014 FBC-PLUMBING SEC.1003.4.EXCEPTION: AN OIL |
| | SEPARATOR IS NOT REQUIRED IN HYDRAULIC ELEVATOR PITS |
| | WHERE AN APPROVED ALARM SYSTEM IS INSTALLED. IF THE |
| | INTENT IS TO USE THE GOULD PUMPS, THIS WOULD NOT MEET |
| | THE INTENT OF THE PLUMBING CODE. |
| | 17) IF THE ELEVATOR IS HYDRAULIC, THE ELEVATOR CYLINDER |
| | SHALL BE PROTECTED AGAINST ELECTROLYSIS IN ACCCORDANCE |
| | WITH THE 2014 FBC-BUILDING SEC.3011.1. |
| | 18) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE WATER |
| | SUB-METER THAT IS LOCATED IN THE PLENUM CLOSET. |
| | MATERIALS LOCATED WITHIN PLENUMS SHALL COMPLY WITH 2014 |
| | FBC-MECHANICAL, SEC.602.2.1. |
| | 19) SHT.P-5 & P-5.1 - THE KITCHEN SINKS SHOWN ON THE |
| | WASTE STACKS ARE DRAWN AS S- TRAPPED. THE FIXTURE DRAIN |
| | SHALL CONNECT DIRECTLY INTO THE WASYE STACK. 2014 |
| | FBC-PLUMBING SEC.913. |
| | 20) CLEARLY LABEL THE RISER LOCATIONS ON SHTS. P-1 |
| | THROUGH P-4 AND ALSO ON THE FLOOR PLANS OF THE UNITS ON |
| | SHTS.P-8 & P-9. WPB AMEND. TO FBC SEC. 107.3.5.1.3. |
| | 21) THE DRAIN LINE FROM THE ELEVATOR SUMPS SHALL BE |
| | EQUIPPED WITH A FULL OPEN SHUTOFF VALVE. THE FULL OPEN |
| | SHUTOFF VALVE SHALL BE LOCATED ON THE DISCHARGE SIDE OF |
| | THE CHECK VALVE.. 2014 FBC-PLUMBING SEC. 712.2. |
| | 22) SHT. P-5 - THE TWO FLOOR DRAINS ABOVE THE TRASH AND |
| | PUMP ROOM ARE NOT PROPERLY VENTED AND APPEAR TO EXCEED |
| | THE ALLOWABLE DISTANCE OF A TRAP TO A VENT PER 2014 |
| | FBC-PLUMBING TABLE 909.1, 901.2, 901.2.1. |
| | 23) SHT. P-5.1 - THE WASTE STACKS FOR THE WASHING |
| | MACHINES SHALL HAVE A STACK VENT THROUGH THE ROOF. |
| | FBC-PLUMBING SEC. 913.3. |
| | 24) SHTS. P- 1 THROUGH P-4 - IDENTIFY AND SHOW THE |
| | LOCATIONS OF THE SANITARY AND WATER RISERS ON THE |
| | PLANS. |
| | 25) SHT.P-6 - THE HOSE BIBBS SHALL BE EQUIPPED WITH |
| | SHUTOFF VALVES. 2014 FBC-PLUMBING SEC. 606.2. |
| | 26) SHT. P-6 - THE BACKFLOW ON THE FLUSHING RING SHALL |
| | BE LEAD FREEE. FBC-PLUMBING SEC.605.2.1. |
| | 27) SHT.P-7 - CLEANOUTS ARE REQUIRED AT THE BASE OF THE |
| | STORM DRAIN RISERS AND HORIZONTAL PIPING PER 2014 |
| | FBC-PLUMBING SEC.1101.8, 708. |
| | 28) SHTS. P-8 & P-9 - THE FLOOR PLAN SHOWS AN 1 1/2 |
| | INCH WATER HEATER DRAIN AND SHTS. M-5 & P-7 SHOW 2 |
| | INCH. CLARIFY. |
| | 29) SHT. P-10 - THE AHU & WATER HEATER DRAIN DETAIL |
| | SHOWS THE HEATER PAN WITH A MINIMUM OF 1 INCH HIGH |
| | SIDES. FBC-PLUMBING SEC.504.7.1 REQUIRES THE SIDES TO |
| | BE A MINIMUM OF 1 1/2 INCHES. |
| | 30) SUBMIT MANUFACTURER'S SPECIFICATIONS/INSTALLATION |
| | MANUAL FOR THE OIL MINDER PUMP/ALARM SYSTEM. |
| | 31) SHT. P-6 - THE WATER RISER SHOWS THE CONTINUATION |
| | OF THE WATER LINE FROM THE DOMESTIC PUMP TO SHT. P- |
| | 6.1. THIS DOES NOT CORRELATE WITH SHT. 6.1.WHAT IS THE |
| | SIZE OF THE WATER LINE AT THE FULLY OPEN VALVE AT THE |
| | DOMESTIC PUMP? WHERE DOES IT CONTINUE? THIS LINE IS NOT |
| | SHOWN ON SHT. P-6.1. SHT. P-6.1 ONLY SHOWS ONE 2 INCH |
| | WATER LINE.CLARIFY. |
| | 32.) SHT. 6 OF THE CIVIL DRAWINGS SHOWS A 3 INCH WATER |
| | SERVICE TO THIS BUILDING. WHERE IS THIS LINE ON SHT. |
| | P-6 OR SHT. P-6.1? CLARIFY. |
| | 33) THERE ARE LOOSE PLUMBING SHEETS IN THE PLAN SET. |
| | PLEASE SECURE THE SHEETS TO THE MAIN SET. |
| | |
| | TIM LARGE |