2017-12-14 14:43:571) SHT. A-1.4 - ROOF DRAINAGE CALCULATIONS - THE
 PRIMARY ROOF DRAINAGE SYSTEM SHALL BE SIZED IN
 ACCORDANCE WITH TABLES 1106.2 (1), 1106.2 (2), AND
 1106.3 NOT TABLE 1106.7 AS NOTED. REVISE THE NOTE.
 ALSO, PLEASE REFER THE ROOF AREA TO BEING DRAINED AS
 "ROOF AREA" INSTEAD OF "FLOOR AREA."
 2) SHT.A-1.4 - CLARIFY WHY THE STAIR ROOF DRAINAGE IS
 CALCULATED AT 50%. WHY ISN'T THE STAIR ROOF AREA
 CALCULATED AT 100%? CLARIFY.IF THE STAIR ROOF HAS A
 PARAPET WALL THEN 1/2 OF THE AREA OF THE ENTIRE PARAPET
 WALL SHALL BE ADDED TO 100% OF THE ROOF AREA OF STAIR
 ROOF. 2014 FBC-PLUMBING SEC. 1106.4.
 3) SHT. A-1.4 - ROOF DRAIN CALCULATIONS SHOW THE AREAS
 DRAINED AS ALL BEING LESS THAN 928 SQ. FT. WHERE IS THE
 928 NUMBER COMING FROM AND WHY IS IT BEING USED?
 CLARIFY.
 4) SHTS. A-6.5.1 THROUGH A-6.5.4 - SHOW ON THE FHA
 FLOOR PLANS OF THE UNITS THAT THE REQUIRED 48 INCH DEEP
 BY 30 INCH WIDE CLEAR FLOOR SPACE FOR THE LAVATORIES IS
 CENTERED ON THE FIXTURE ( LAVATORY) AS REQUIRED BY THE
 FAIR HOUSING ACT DESIGN MANUAL PART TWO: CHAPTER 7 OR
 PLACE A NOTE ON THE PLANS STATING SUCH. THIS ALSO
 APPLIES TO FIXTURES AND APPLIANCES IN THE KITCHEN.
 5) SHTS. A-6.5.1 THROUGH A-6.5.4 - CLEARLY
 MARK/IDENTIFY THE REQUIRED CLEAR FLOOR SPACE FOR THE
 WATER CLOSETS ON THE PLANS AND SHOW THE DIMENSIONS. THE
 CLEAR FLOOR SPACE FOR THE WATER CLOSETS SHALL BE 66
 INCHES DEEP MINIMUM BY 48 INCHES WIDE MINIMUM, 56
 INCHES DEEP MINIMUM BY 48 INCHES WIDE MINIMUM, OR 56
 INCHES DEEP MINIMUM BY 60 INCHES WIDE MINIMUM DEPENDING
 ON THE DIRECTION OF APPROACH TO THE WATER CLOSET BY A
 PERSON USING A WHEELCHAIR. FAIR HOUSING ACT DESIGN
 MANUAL PART TWO, CHAPTER 7.
 6) CLARIFY THE USE/REASON FOR THE T- SHAPED TURNING
 SPACE SHOWN ON THE PLANS. THIS DOES NOT APPEAR TO BE
 COMPLIANT WITH THE FAIR HOUSING ACT DESIGN MANUAL IF
 THIS IS BEING USED FOR THE REQUIRED CLEAR FLOOR SPACE
 FOR THE WATER CLOSET.. THIS DETAIL APPEARS ON SEVERAL
 SHEETS.
 7) SHTS. A-6.5.1 THROUGH A-6.5.4 - SHOW THE LENGTHS OF
 ALL REINFORCING FOR THE GRAB BARS FOR ALL FIXTURES ON
 THE PLAN. WPB AMEND. TO FBC SEC. 107.2.1, FHA DESIGN
 MANUAL PART TWO: CHAPTER 6.
 8) SHT.A-6.5.1 - DETAIL #1 - SHOW THE MINIMUM AND
 MAXIMUM HEIGHTS OF THE REINFORCEMENT FOR THE TUB
 CONTROL WALL. SHOW THE LENGTH OF THE REINFORCEMENT.
 COMPLY WITH FHA DESIGN MANUAL PART TWO: CHAPTER 6.
 9) SHT. A-6.5.1 - DETAIL #2 - THE ENDS OF THE GRAB BAR
 REINFORCEMENT FOR THE BATHTUB SHALL BE LOCATED A
 MAXIMUM OF 6 INCHES IN FROM THE SIDE WALLS OF THE TUB
 IN ACCORDANCE WITH THE FHA DESIGN MANUAL PART TWO:
 CHAPTER 6. SHOW THE LENGTH OF THE REINFORCEMENT ON THE
 DETAIL.
 10) SHT. A-6.5.2 - DETAIL #1 - SHOW THE MINIMUM AND
 MAXIMUM HEIGHT OF THE REINFORCEMENT FOR THE GRAB BAR
 FOR THE TUB ON THE CONTROL WALL. SHOW THE LENGTH OF THE
 REINFORCEMENT. COMPLY WITH FHA DESIGN MANUAL PART TWO:
 CHAPTER 6.
 11) SHT. A-6.5.2 - DETAIL #4 - THE ENDS OF THE GRAB BAR
 REINFORCEMENT FOR THE BATHTUB SHALL BE LOCATED A
 MAXIMUM OF 6 INCHES IN FROM THE SIDE WALLS OF THE TUB
 IN ACCORDANCE WITH THE FHA DESIGN MANUAL PART TWO:
 CHAPTER 6.SHOW THE LENGTH OF THE REINFORCEMENT ON THE
 DETAIL.
 12) SHT. A-6.5.3 - DETAIL #2 - THE ENDS OF THE GRAB BAR
 REINFORCEMENT FOR THE BATHTUB SHALL BE LOCATED A
 MAXIMUM OF 6 INCHES IN FROM THE SIDE WALLS OF THE TUB
 IN ACCORDANCE WITH THE FHA DESIGN MANUAL PART TWO:
 CHAPTER 6.SHOW THE LENGTH OF THE REINFORCEMENT ON THE
 DETAIL.
 13) SHT. A-6.5.4 - DETAIL #1 - SHOW THE MINIMUM AND
 MAXIMUM HEIGHT OF THE REINFORCEMENT FOR THE TUB CONTROL
 WALL. ALSO, SHOW THE MINIMUM AND MAXIMUM HEIGHTS FOR
 THE REINFORCEMENT FOR THE TOILET.SHOW THE LENGTHS OF
 THE REINFORCEMENT ON THE DETAIL. COMPLY WITH FHA DESIGN
 MANUAL PART TWO: CHAPTER 6.
 14) SHT. A-6.5.4 - DETAIL # 2 - THE ENDS OF THE GRAB
 BAR REINFORCEMENT FOR THE BATHTUB SHALL BE LOCATED A
 MAXIMUM OF 6 INCHES IN FROM THE SIDE WALLS OF THE TUB
 IN ACCORDANCE WITH THE FHA DESIGN MANUAL PART TWO:
 CHAPTER 6.SHOW THE LENGTH OF THE REINFORCEMENT ON THE
 DETAIL.
 15) SHT. A-6.5.4 - DETAIL #3 - SHOW THE MINIMUM AND
 MAXIMUM HEIGHT OF THE REINFORCEMENT FOR THE TUB AND
 SHOW THE MINIMUM LENGTH OF THE REINFORCEMENT ON THE
 DETAIL. COMPLY WITH FHA DESIGN MANUAL PART TWO: CHAPTER
 6.
 16) SHT. A-6.7.1 & A-6.7.2. - INDICATE ON THE PLAN IF
 THE ELEVATOR IS OF A TRACTION TYPE OR HYDRAULIC. IF THE
 ELEVATOR IS HYDRAULIC, THEN AN OIL SEPARATOR IS
 REQUIRED ON THE DISCHARGE FROM THE ELEVATOR SUMP PER
 THE 2014 FBC-PLUMBING SEC.1003.4.EXCEPTION: AN OIL
 SEPARATOR IS NOT REQUIRED IN HYDRAULIC ELEVATOR PITS
 WHERE AN APPROVED ALARM SYSTEM IS INSTALLED. IF THE
 INTENT IS TO USE THE GOULD PUMPS, THIS WOULD NOT MEET
 THE INTENT OF THE PLUMBING CODE.
 17) IF THE ELEVATOR IS HYDRAULIC, THE ELEVATOR CYLINDER
 SHALL BE PROTECTED AGAINST ELECTROLYSIS IN ACCCORDANCE
 WITH THE 2014 FBC-BUILDING SEC.3011.1.
 18) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE WATER
 SUB-METER THAT IS LOCATED IN THE PLENUM CLOSET.
 MATERIALS LOCATED WITHIN PLENUMS SHALL COMPLY WITH 2014
 FBC-MECHANICAL, SEC.602.2.1.
 19) SHT.P-5 & P-5.1 - THE KITCHEN SINKS SHOWN ON THE
 WASTE STACKS ARE DRAWN AS S- TRAPPED. THE FIXTURE DRAIN
 SHALL CONNECT DIRECTLY INTO THE WASYE STACK. 2014
 FBC-PLUMBING SEC.913.
 20) CLEARLY LABEL THE RISER LOCATIONS ON SHTS. P-1
 THROUGH P-4 AND ALSO ON THE FLOOR PLANS OF THE UNITS ON
 SHTS.P-8 & P-9. WPB AMEND. TO FBC SEC. 107.3.5.1.3.
 21) THE DRAIN LINE FROM THE ELEVATOR SUMPS SHALL BE
 EQUIPPED WITH A FULL OPEN SHUTOFF VALVE. THE FULL OPEN
 SHUTOFF VALVE SHALL BE LOCATED ON THE DISCHARGE SIDE OF
 THE CHECK VALVE.. 2014 FBC-PLUMBING SEC. 712.2.
 22) SHT. P-5 - THE TWO FLOOR DRAINS ABOVE THE TRASH AND
 PUMP ROOM ARE NOT PROPERLY VENTED AND APPEAR TO EXCEED
 THE ALLOWABLE DISTANCE OF A TRAP TO A VENT PER 2014
 FBC-PLUMBING TABLE 909.1, 901.2, 901.2.1.
 23) SHT. P-5.1 - THE WASTE STACKS FOR THE WASHING
 MACHINES SHALL HAVE A STACK VENT THROUGH THE ROOF.
 FBC-PLUMBING SEC. 913.3.
 24) SHTS. P- 1 THROUGH P-4 - IDENTIFY AND SHOW THE
 LOCATIONS OF THE SANITARY AND WATER RISERS ON THE
 PLANS.
 25) SHT.P-6 - THE HOSE BIBBS SHALL BE EQUIPPED WITH
 SHUTOFF VALVES. 2014 FBC-PLUMBING SEC. 606.2.
 26) SHT. P-6 - THE BACKFLOW ON THE FLUSHING RING SHALL
 BE LEAD FREEE. FBC-PLUMBING SEC.605.2.1.
 27) SHT.P-7 - CLEANOUTS ARE REQUIRED AT THE BASE OF THE
 STORM DRAIN RISERS AND HORIZONTAL PIPING PER 2014
 FBC-PLUMBING SEC.1101.8, 708.
 28) SHTS. P-8 & P-9 - THE FLOOR PLAN SHOWS AN 1 1/2
 INCH WATER HEATER DRAIN AND SHTS. M-5 & P-7 SHOW 2
 INCH. CLARIFY.
 29) SHT. P-10 - THE AHU & WATER HEATER DRAIN DETAIL
 SHOWS THE HEATER PAN WITH A MINIMUM OF 1 INCH HIGH
 SIDES. FBC-PLUMBING SEC.504.7.1 REQUIRES THE SIDES TO
 BE A MINIMUM OF 1 1/2 INCHES.
 30) SUBMIT MANUFACTURER'S SPECIFICATIONS/INSTALLATION
 MANUAL FOR THE OIL MINDER PUMP/ALARM SYSTEM.
 31) SHT. P-6 - THE WATER RISER SHOWS THE CONTINUATION
 OF THE WATER LINE FROM THE DOMESTIC PUMP TO SHT. P-
 6.1. THIS DOES NOT CORRELATE WITH SHT. 6.1.WHAT IS THE
 SIZE OF THE WATER LINE AT THE FULLY OPEN VALVE AT THE
 DOMESTIC PUMP? WHERE DOES IT CONTINUE? THIS LINE IS NOT
 SHOWN ON SHT. P-6.1. SHT. P-6.1 ONLY SHOWS ONE 2 INCH
 WATER LINE.CLARIFY.
 32.) SHT. 6 OF THE CIVIL DRAWINGS SHOWS A 3 INCH WATER
 SERVICE TO THIS BUILDING. WHERE IS THIS LINE ON SHT.
 P-6 OR SHT. P-6.1? CLARIFY.
 33) THERE ARE LOOSE PLUMBING SHEETS IN THE PLAN SET.
 PLEASE SECURE THE SHEETS TO THE MAIN SET.
  