| 2017-12-08 14:10:37 | ****PLAN REVIEW COMMENTS**** |
| | |
| | ART LANGE BUILDING PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH, FL 33402 |
| | |
| | 561-805-6718 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2014 5TH EDITION W/2010 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION / FRC FLORIDA RESIDENTIAL CODE |
| | 2015 5TH EDITION |
| | |
| | VILLAGE AT MANGONIA LAKE 17111009 |
| | |
| | FIRST REVIEW: |
| | |
| | ART IN PUBLIC PLACES |
| | |
| | 1. INFORMATION NOTICE: THE CITY OF WEST PALM BEACH ART |
| | IN PUBLIC PLACES ORDINANCE REQUIREMENT THAT APPLIES TO |
| | ANY REMODEL OR NEW CONSTRUCTION PROJECT FOR WHICH THE |
| | PERMIT APPLICATION WAS SUBMITTED AFTER 6/29/14, AND THE |
| | TOTAL PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR |
| | GREATER THAN $750,000 WILL NEED TO COMPLY WITH THIS |
| | ORDINANCE. |
| | PER CITY OF WEST PALM BEACH ORDINANCE NO. 4504-14, AND |
| | CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE V, |
| | ART IN PUBLIC PLACES, SECTION 78-123(A) AND SECTION |
| | 78-126(A), THE ART ASSESSMENT IS 1% OF THE TOTAL |
| | PROJECT CONSTRUCTION COST. |
| | PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE |
| | V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND |
| | NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO |
| | THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE |
| | PROJECTS. |
| | FOR CONTACT INFORMATION PLEASE CONTACT: |
| | MS. SYBILLE WELTER ART IN PUBLIC PLACES COORDINATOR |
| | 822-1515 E-MAIL: [email protected] |
| | |
| | 2. THIS BUILDING QUALIFIES AS A THRESHOLD BUILDING. |
| | ?THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS |
| | GREATER THAN (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH |
| | HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN |
| | THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. |
| | IN AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500 |
| | PERSONS. |
| | |
| | A) 109.3.6.1 THRESHOLD INSPECTION PLAN. THE ENFORCING |
| | AGENCY SHALL REQUIRE A (WRITTEN/ TYPED) SPECIAL |
| | INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A |
| | THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION |
| | PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL |
| | INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING |
| | AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR |
| | THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE |
| | OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE |
| | SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT |
| | THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE |
| | WITH THE PERMITTED DOCUMENTS. |
| | |
| | B) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B. |
| | CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD |
| | BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY 553.79(5) |
| | FLORIDA STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY |
| | THIS CODE. THE THRESHOLD INSPECTION FORMS ARE REQUIRED |
| | TO BE FILED OUT BY ALL PARTIES WITH INTEREST, NOTARIZED |
| | AND RETURNED TO THIS OFFICE, AND REVIEWED AND APPROVED |
| | BEFORE PERMIT ISSUANCE WILL TAKE PLACE. |
| | |
| | C) THRESHOLD BUILDING, REQUIRED STATEMENT: W.P.B. |
| | AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING WHICH |
| | ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT |
| | OR ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE |
| | BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE |
| | PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE |
| | FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL |
| | AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633 |
| | FLORIDA STATUTE. |
| | |
| | D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME OF |
| | INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE RESUME |
| | MUST BE ACCOMPANIED BY ALL CERTIFICATES AS SPECIFIED |
| | HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE WILL |
| | REVIEW THE RESUME. AFTER THE RESUME' IS REVIEWED, AN |
| | INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES |
| | WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST |
| | MEETING THE ABOVE CRITERIA. |
| | |
| | E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR HISTORY |
| | FOR THIS TYPE OF CONSTRUCTION. |
| | 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION, 110.3.7 THRESHOLD |
| | BUILDINGS, GUIDELINES AND POLICIES FOR PROJECTS |
| | CONCERNING SPECIAL INSPECTORS. |
| | |
| | F) PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED |
| | TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR ALL |
| | BUILDING INSPECTIONS FOR AUDITING OF JOBSITE |
| | INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN 6 |
| | MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY. |
| | |
| | 3. PROVIDE PRODUCT APPROVALS FOR THE FOLLOWING. |
| | EXTERIOR DOORS AND WINDOWS, LOUVERS AT ELEVATOR SHAFT |
| | AND ROOFING. |
| | |
| | THESE ITEMS CAN BE DONE AS DEFERRED SUBMITTALS. IF YOU |
| | ELECT TO DO THIS PLEASE ADD THESE TO THE LIST OF |
| | DEFERRED SUBMITTALS ON THE COVER PAGE. |
| | |
| | W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | FBC 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF |
| | THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE |
| | PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE |
| | TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO |
| | THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. |
| | DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR |
| | APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED |
| | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST |
| | THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS |
| | FOR REVIEW BY THE BUILDING OFFICIAL. |
| | |
| | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| | THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| | OFFICIAL. |
| | |
| | 4. ALL CONSTRUCTION TRAILERS (MOBILE OR MODULAR |
| | BUILDINGS) THAT ARE GOING TO HAVE MEETING IN THEM WILL |
| | BE REQUIRED TO GET A PERMIT, 102.2( E ) MOBILE OR |
| | MODULAR STRUCTURES USED AS TEMPORARY OFFICES, EXCEPT |
| | THAT THE PROVISIONS OF PART V (SECTION 553.501-553.513, |
| | FLORIDA STATUTES) RELATING TO ACCESSIBILITY BY PERSONS |
| | WITH DISABILITIES, AND PERMITS SHALL BE REQUIRED FOR |
| | STRUCTURAL SUPPORT AND TIE DOWN, ELECTRICAL SUPPLY, AND |
| | ALL UTILITY CONNECTIONS TO SUCH MOBILE OR MODULAR |
| | STRUCTURES. |
| | |
| | 5. PROVIDE SOUND PROOFING TEST REPORTS FOR ALL FLOORS |
| | ABOVE THE FIRST FLOOR. THE SOUND PROOFING SHALL COMPLY |
| | WITH THE FOLLOWING SECTIONS. |
| | FBC 603.1 FLAME SPREAD ? ASTM E-84-09 |
| | FBC 1207.2 AIR-BORNE SOUND. ASTM E - 90-04 |
| | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| | E 90. |
| | FBC 1207.3 STRUCTURE-BORNE SOUND. ASTM E - 492-09 |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| | |
| | 6. WELDED OR BOLTED CONNECTIONS |
| | THE CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE |
| | SPECIFICATIONS & WELDER OPERATOR PERFORMANCE |
| | QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED |
| | STANDARDS AT TIME OF INSPECTION. |
| | 2014 FBC-B 2204.1 WELDING |
| | 2014 FBC-B 2204.2 BOLTING. |
| | |
| | 7. SLIDING GLASS DOOR THRESHOLD. THE SILL RISER WILL |
| | INTERFERE WITH THE MAXIMUM THRESHOLD AND ALLOWABLE 4? |
| | STEP. SEE FAIR HOUSING ACT DESIGN MANUAL?S DETAIL ON |
| | PAGE 4.15. |
| | |
| | 8. PARK LOT ACCESSIBLE SIGN DETAIL ON CIVIL PAGE 13 HAS |
| | BEEN UPDATED. PLEASE REVISE SIGN DETAIL TO REFLECT 60 |
| | INCHES ABOVE FINISHED FLOOR OR GROUND. FS 553.5041(6). |
| | |
| | 9. IMPACT FEES: |
| | BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM: |
| | |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | THIS FORM IS ALSO AVAILABLE AT THE BUILDING DIVISION. |
| | |
| | WHEN RESUBMITTING, SWAP OUT SHEETS WHICH HAVE CHANGED |
| | SO THAT THERE ARE TWO COMPLETE, COLLATED SETS OF PLANS |
| | READY FOR PERMIT ISSUANCE. OLD SHEETS ARE TO BE |
| | RETAINED IN THE PERMIT APPLICATION PACKAGE (SEPARATE |
| | FROM THE PERMIT SETS) AND MARKED *OLD SHEETS* OR |
| | *VOID*. PLEASE KEEP BOTH SETS OF OLD VOIDED SHEETS IN |
| | THE PERMIT PACKAGE. |
| | |
| | A RESPONSE LETTER INDICATING HOW EACH ITEM WAS |
| | ADDRESSED WILL HELP TO EXPEDITE PLAN REVIEW. |
| | |