| Notes |
| Date |
Text |
| 2018-04-16 11:31:05 | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED | | | NFPA 70 2011 EDITION | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | CUT SHEETS NOT SUBMITTED FOR WALL PACKS OR WHAT EVER IS | | | INSTALLED ON BUILDING. | | | | | | LIGHTING CONTROL NOT SHOWN ON PLANS | | | | | | ORIGINAL PLANS SHOW TWO (2) PARKING LOT FIXTURES AND | | | ZERO (0) ON THE BUILDING | | | NEW PLAN SHOWS SEVEN (7) PARKING LOT FIXTURES, AND | | | THREE OR FOUR WALL PACKS ON BUILDING. | | | PLEASE INCLUDE THE VALUE FOR THESE FIXTURES AND WORK. | | | | | | IF VALUE IS NOT INCLUDED WITH THE RESUBMITTAL THIS NEXT | | | TIME YOU WILL BE ACCESSED A PENALTY FOR EXCESSIVE PLAN | | | REVIEW FOR SAME ITEM. | | | | | | CGC IS NOT ALLOWED TO PULL A PERMIT FOR ELECTRICAL | | | WORK!!!!! |
|