| 2017-12-12 10:25:19 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED | | | NFPA 70 2011 EDITION | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | NEEDS ELECTRICAL CONTRACTOR TO PULL PERMIT. | | | | | | ORIGINAL PLAN SHOWS ONLY TWO POLE LIGHTS YOUR PLAN | | | SHOWS 7, PLUS 4 FIXTURES ON BUILDING. | | | | | | SUBMIT PLAN SHOWING THE BRANCH CIRCUIT NUMBER AND SIZE | | | FOR THESE FIXTURES. | | | | | | NEED TO SUBMIT CUTSHEETS FOR THE FIXTURES AND POLE | | | LIGHTS, INCLUDING THE WIND LOADS FOR THE POLE LIGHTS. | | | | | | PLANS WILL NEED TO SIGNED AND SEALED BY ENGINEER OF | | | RECORD. | | | | | | VALUE COULD NOT HAVE BEEN INCLUDED FOR THE FIXTURES IF | | | THEY ARE NOT SHOWN ON ORIGINAL PLANS, PLEASE INCLUDE | | | THE VALUE FOR THE ADDITIONAL WORK SHOWN ON PLANS. | | | | | | LIGHTING CONTROL WILL BE REVIEW PER FBC ENERGY | | | CONSERVATION CODE 2014 |
|