Plan Review Notes
Plan Review Notes For Permit 17110986
Permit Number 17110986
Review Stop E
Sequence Number 1
Notes
Date Text
2017-12-12 10:25:19ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED
 NFPA 70 2011 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 NEEDS ELECTRICAL CONTRACTOR TO PULL PERMIT.
  
 ORIGINAL PLAN SHOWS ONLY TWO POLE LIGHTS YOUR PLAN
 SHOWS 7, PLUS 4 FIXTURES ON BUILDING.
  
 SUBMIT PLAN SHOWING THE BRANCH CIRCUIT NUMBER AND SIZE
 FOR THESE FIXTURES.
  
 NEED TO SUBMIT CUTSHEETS FOR THE FIXTURES AND POLE
 LIGHTS, INCLUDING THE WIND LOADS FOR THE POLE LIGHTS.
  
 PLANS WILL NEED TO SIGNED AND SEALED BY ENGINEER OF
 RECORD.
  
 VALUE COULD NOT HAVE BEEN INCLUDED FOR THE FIXTURES IF
 THEY ARE NOT SHOWN ON ORIGINAL PLANS, PLEASE INCLUDE
 THE VALUE FOR THE ADDITIONAL WORK SHOWN ON PLANS.
  
 LIGHTING CONTROL WILL BE REVIEW PER FBC ENERGY
 CONSERVATION CODE 2014