Plan Review Notes
Plan Review Notes For Permit 17110874
Permit Number 17110874
Review Stop G
Sequence Number 5
Notes
Date Text
2018-09-24 12:04:08PROVISO:
  
 3. PROVIDE SHOP DRAWINGS FOR THE EXHAUST AND INTAKE
 PIPING FOR THE BOILERS SHOW ALL REQUIRED CLEARANCES
 FROM OPENINGS, PROPERTY LINES AND ROOFS OR OVERHANGS
 STAMPED BY THE ENGINEER OF RECORD.
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
2018-09-21 12:25:09***PROVISO***
  
 GEORGE JOHNSON, PLUMBING PLANS EXAMINER II
 [email protected]
 561-805-6711
  
 1. PROVIDE DOCUMINTATION FROM MANUFACTURE THAT THE
 CONFIGURATION OF THE BOILER INTAKE AND EXHAUST AND THE
 GENARATOR WILL FUNCTION PROPERLY WITH BOTH RUNNING
 SIMULTANIOUSLY. AS SHOWN ON THE PLAN.
  
 2. PROVIDE SIGNED ANS SEALED LETTER FROM THE ENGINEER
 OF RECORD THAT THE CONFIGURATION OF THE BOILER INTAKE
 AND EXHAUST AND THE GENARATOR WILL FUNCTION PROPERLY
 WITH BOTH RUNNING SIMULTANIOUSLY. AS SHOWN ON THE PLAN.
  
  