| Notes |
| Date |
Text |
| 2018-09-24 12:04:08 | PROVISO: | | | | | | 3. PROVIDE SHOP DRAWINGS FOR THE EXHAUST AND INTAKE | | | PIPING FOR THE BOILERS SHOW ALL REQUIRED CLEARANCES | | | FROM OPENINGS, PROPERTY LINES AND ROOFS OR OVERHANGS | | | STAMPED BY THE ENGINEER OF RECORD. | | | | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | | | 2018-09-21 12:25:09 | ***PROVISO*** | | | | | | GEORGE JOHNSON, PLUMBING PLANS EXAMINER II | | | [email protected] | | | 561-805-6711 | | | | | | 1. PROVIDE DOCUMINTATION FROM MANUFACTURE THAT THE | | | CONFIGURATION OF THE BOILER INTAKE AND EXHAUST AND THE | | | GENARATOR WILL FUNCTION PROPERLY WITH BOTH RUNNING | | | SIMULTANIOUSLY. AS SHOWN ON THE PLAN. | | | | | | 2. PROVIDE SIGNED ANS SEALED LETTER FROM THE ENGINEER | | | OF RECORD THAT THE CONFIGURATION OF THE BOILER INTAKE | | | AND EXHAUST AND THE GENARATOR WILL FUNCTION PROPERLY | | | WITH BOTH RUNNING SIMULTANIOUSLY. AS SHOWN ON THE PLAN. | | | | | | |
|