| 2018-08-29 12:19:44 | |
| | 4TH REVIEW: FBC 2014 5TH EDITION |
| | |
| | PLUMBING COMMENTS: IT APPEARS THAT THE PLUMBING COMMENT |
| | WERE NOT ADDRESSED I COULD NOT FIND A RESPONSE LETTER |
| | AND PREVIOUS COMMENT NOT COMPLIED WITH. |
| | |
| | 1. SHT. P-902 + P-904 THE SANITARY STACKS ARE NOT |
| | LABELED THE SAME SHT. P902 IS LABELED WITH AN S THE |
| | STACKS ON P-904 ARE LABELED WITH AN X PLEASE LABEL THE |
| | STACKS ON EACH SHT. TO MATCH THE COINCIDING STACKS ON |
| | ALL SHTS. PER WPB AMEND TO FBC 107.2.1 |
| | 2. PREVIOUS COMMENT #3 SHT. A -512 DETAIL # 8 STILL |
| | SHOWS THE WATERPROOFING MEMBRANE STOPPING AT THE CURB |
| | AT THE SLIDING BOOKCASE GLASS PLEASE SHOW THE MEMBRANE |
| | RUNNING UP AND OVER THE CURB. PER FBC PL 417.5.2 |
| | 3. SHT. P-905 PLEASE SHOW THE PIPE SIZING ON THE |
| | PRESSURE RISER LOBBY DETAIL #1. PER WPB AMEND TO FBC |
| | 107.2.1 |
| | 5. SHTS P-901 P-905 THE RISER LABELING DOES NOT MATCH |
| | SHT. 901 THE STACKS ARE LABELED WITH AN W THE STACKS ON |
| | SHT. 905 ARE LABELED WITH AN X PLEASE LABEL THEM ALL |
| | WITH COINCIDING LABELS WITH THE STACK NUMBER. PER WPB |
| | AMEND TO FBC 107.2.1 |
| | 6. SHT. 902 RISER S1 THE BATHROOM GROUP AT THE BOTTOM |
| | OF THE RISER IS NOT VENTED PROPERLY THE LAVATORY SHALL |
| | CONNECT UPSTREAM OF THE SOIL STACK IT CANNOT CONNECT TO |
| | THE SOIL STACK WITHOUT A SEPARATE VENT AND THERE SHALL |
| | BE A VENT BETWEEN THE SHOWER AND TOILET. PER FBC PL |
| | 901.2.1, 912.1 |
| | 7. SHT. P-102 THE OVERFLOW STORM DRAINS THAT ARE |
| | TERMINATING ON THE WEST SIDE OF THE BUILDING WILL NEED |
| | TO BE RELOCATED, AS YOU KNOW THIS SIDE OF THE BUILDING |
| | IS NOT OPEN IT IS CONNECTED TO THE PARKING GARAGE |
| | APARTMENT BUILDING THE OVER FLOW ON THE NORTH END IS |
| | DUMPING INTO THE PARKING GARAGE AND THE OVER FLOW ON |
| | THE SOUTH END IS DUMPING INTO THE GENERATOR AREA AND |
| | WILL FLOOD THE GENERATOR IF THE OVERFLOW IS BEING USED. |
| | PER WPB AMEND TO FBC 107.2.1 |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |