Plan Review Notes
Plan Review Notes For Permit 17110874
Permit Number 17110874
Review Stop M
Sequence Number 4
Notes
Date Text
2018-09-19 16:19:10MECHANICAL PROVISOS:
 9/19/2018
  
 1) SEPARATE PERMITS ARE REQUIRED FOR THE KITCHEN HOODS
 AND EXHAUST SYSTEMS, THE FIRE SUPPRESSION SYSTEMS, THE
 WALK-IN COOLER AND FREEZER, GENERATOR, FIRE ALARM, AND
 FIRE SPRINKLERS.
  
 CONCERNING THE KITCHEN HOODS AND EXHAUST SYSTEMS, THE
 CURRENT DESIGN AS SHOWN ON THE MAIN PLANS WILL BE
 ACCEPTED WITH THE CONTINGENCIES LISTED BELOW:
  
 A) THE LOCATIONS OF THE GOOSENECK EXHAUST TERMINATIONS
 ON THE LOW ROOF WILL NOT CAUSE EITHER A PUBLIC NUISANCE
 TO OCCUPANTS OF EITHER THE AUTOGRAPH HOTEL OR THE
 ADJACENT APARTMENT BUILDING, NOR WILL THEY CAUSE DAMAGE
 TO OR DEGRADATION OF THE ROOF SURFACE, OR POTENTIALLY
 IMPEDE ROOF DRAINAGE.
  
 B) THE IN-LINE GREASE EXHAUST FANS WILL BE EQUIPPED
 WITH ADEQUATE FILTERS TO MINIMIZE THE GREASE LADEN
 EXHAUST VAPOR AND ODORS FROM BEING DISPERSED INTO THE
 AIR WHERE THEY MAY BECOME A NUISANCE TO OCCUPANTS OF
 THE APARTMENT AND HOTEL BUILDINGS.
  
 C) A MAINTENANCE PROGRAM AND SCHEDULE FOR PERIODIC
 CLEANING AND INSPECTION OF THE EXHAUST FANS AND DUCTS
 WILL BE DEVELOPED BY THE OWNERSHIP OF THE AUTOGRAPH
 HOTEL, AND AN OUTLINE OF THE PROGRAM SHALL BE SUBMITTED
 TO THE BUILDING DEPARTMENT.
  
 2) THE 36"X82" CASEMENT WINDOW USED FOR ACCESS TO THE
 LOW ROOF FOR SERVICING AND REPLACEMENT OF EQUIPMENT IS
 NOT ACCEPTED. IN IT'S PLACE, A MINIMUM 36" WIDE
 EXTERIOR DOOR SHALLL BE INSTALLED, ALONG WITH ANY
 REQUIRED PERMANENT STEPS OR LADDER NEEDED TO ACCESS THE
 ROOF.
  
 3) THE FIRE PUMP ROOM SHALL BE VENTILATED PER SECTION
 4.13.6 NFPA-20.
  
 4) THE COMBUSTION AIR INTAKE AND EXHAUST SYSTEM FOR THE
 GAS-FIRED WATER HEATERS SHALL BE INSTALLED IN
 ACCORDANCE WITH MANUFACTURER'S SPECIFICATIONS AND
 INSTALLATION INSTRUCTIONS. SHOP DRAWINGS FOR THE PVC
 INTAKE AND EXHAUST DUCTS SHOWING TOTAL RUN DISTANCES
 AND CLEARANCE DISTANCES FOR THE AIR INTAKE AND EXHAUST
 TERMINATION LOCATIONS SHALL BE SUBMITTED WITH AN
 APPROVAL STAMP BY THE EOR.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  
  