| 2018-09-19 16:19:10 | MECHANICAL PROVISOS: |
| | 9/19/2018 |
| | |
| | 1) SEPARATE PERMITS ARE REQUIRED FOR THE KITCHEN HOODS |
| | AND EXHAUST SYSTEMS, THE FIRE SUPPRESSION SYSTEMS, THE |
| | WALK-IN COOLER AND FREEZER, GENERATOR, FIRE ALARM, AND |
| | FIRE SPRINKLERS. |
| | |
| | CONCERNING THE KITCHEN HOODS AND EXHAUST SYSTEMS, THE |
| | CURRENT DESIGN AS SHOWN ON THE MAIN PLANS WILL BE |
| | ACCEPTED WITH THE CONTINGENCIES LISTED BELOW: |
| | |
| | A) THE LOCATIONS OF THE GOOSENECK EXHAUST TERMINATIONS |
| | ON THE LOW ROOF WILL NOT CAUSE EITHER A PUBLIC NUISANCE |
| | TO OCCUPANTS OF EITHER THE AUTOGRAPH HOTEL OR THE |
| | ADJACENT APARTMENT BUILDING, NOR WILL THEY CAUSE DAMAGE |
| | TO OR DEGRADATION OF THE ROOF SURFACE, OR POTENTIALLY |
| | IMPEDE ROOF DRAINAGE. |
| | |
| | B) THE IN-LINE GREASE EXHAUST FANS WILL BE EQUIPPED |
| | WITH ADEQUATE FILTERS TO MINIMIZE THE GREASE LADEN |
| | EXHAUST VAPOR AND ODORS FROM BEING DISPERSED INTO THE |
| | AIR WHERE THEY MAY BECOME A NUISANCE TO OCCUPANTS OF |
| | THE APARTMENT AND HOTEL BUILDINGS. |
| | |
| | C) A MAINTENANCE PROGRAM AND SCHEDULE FOR PERIODIC |
| | CLEANING AND INSPECTION OF THE EXHAUST FANS AND DUCTS |
| | WILL BE DEVELOPED BY THE OWNERSHIP OF THE AUTOGRAPH |
| | HOTEL, AND AN OUTLINE OF THE PROGRAM SHALL BE SUBMITTED |
| | TO THE BUILDING DEPARTMENT. |
| | |
| | 2) THE 36"X82" CASEMENT WINDOW USED FOR ACCESS TO THE |
| | LOW ROOF FOR SERVICING AND REPLACEMENT OF EQUIPMENT IS |
| | NOT ACCEPTED. IN IT'S PLACE, A MINIMUM 36" WIDE |
| | EXTERIOR DOOR SHALLL BE INSTALLED, ALONG WITH ANY |
| | REQUIRED PERMANENT STEPS OR LADDER NEEDED TO ACCESS THE |
| | ROOF. |
| | |
| | 3) THE FIRE PUMP ROOM SHALL BE VENTILATED PER SECTION |
| | 4.13.6 NFPA-20. |
| | |
| | 4) THE COMBUSTION AIR INTAKE AND EXHAUST SYSTEM FOR THE |
| | GAS-FIRED WATER HEATERS SHALL BE INSTALLED IN |
| | ACCORDANCE WITH MANUFACTURER'S SPECIFICATIONS AND |
| | INSTALLATION INSTRUCTIONS. SHOP DRAWINGS FOR THE PVC |
| | INTAKE AND EXHAUST DUCTS SHOWING TOTAL RUN DISTANCES |
| | AND CLEARANCE DISTANCES FOR THE AIR INTAKE AND EXHAUST |
| | TERMINATION LOCATIONS SHALL BE SUBMITTED WITH AN |
| | APPROVAL STAMP BY THE EOR. |
| | |