| 2018-08-29 12:19:14 | |
| | 4TH REVIEW: FBC 2014 5TH EDITION |
| | |
| | GAS COMMENTS: |
| | |
| | 4. THE INTAKE AND EXHAUST FOR THE BOILERS AND GENERATOR |
| | ARE LOCATED DOWN AT THE BOTTOM OF A SHAFT OR PIT HOW |
| | WILL THE EXHAUST BE KEPT FROM BUILDING UP IF THERE IS |
| | NO VENTILATION OF THE AREA SOME DOCUMENTATION FROM THE |
| | MANUFACTURE WILL BE REQUIRED STATING THAT THIS |
| | CONFIGURATION WILL ALLOW THE EQUIPMENT TO FUNCTION |
| | PROPERLY. PER WPB AMEND TO FBC 107.2.1 THE RESPONSE |
| | LETTER IS NOT A CONSTRUCTION DOCUMENT PLEASE INCLUDE |
| | REQUESTED DOCUMENT A SIGNED AND SEALED LETTER FROM THE |
| | MANUFACTURES AND THE ENGINEER. STATING THAT THIS PIPING |
| | LAYOUT WILL ALLOW BOTH THE GENERATOR AND THE BOILERS TO |
| | FUNCTION PROPERLY SIMULTANEOUSLY. |
| | |
| | PREVIOUS COMMENT NOT COMPLIED 5. SHT. P-407 PLEASE SHOW |
| | ON THE PLAN THE MIN DISTANCE BETWEEN THE INTAKE AND |
| | EXHAUST. . PER WPB AMEND TO FBC 107.2.1 THE RESPONSE |
| | LETTER IS NOT A CONSTRUCTION DOCUMENT PLEASE INCLUDE |
| | REQUESTED DIMENSIONS ON THE PLAN. |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561-805-6711 |
| | [email protected] |
| | |