Plan Review Notes
Plan Review Notes For Permit 17110874
Permit Number 17110874
Review Stop G
Sequence Number 4
Notes
Date Text
2018-08-29 12:19:14 
 4TH REVIEW: FBC 2014 5TH EDITION
  
 GAS COMMENTS:
  
 4. THE INTAKE AND EXHAUST FOR THE BOILERS AND GENERATOR
 ARE LOCATED DOWN AT THE BOTTOM OF A SHAFT OR PIT HOW
 WILL THE EXHAUST BE KEPT FROM BUILDING UP IF THERE IS
 NO VENTILATION OF THE AREA SOME DOCUMENTATION FROM THE
 MANUFACTURE WILL BE REQUIRED STATING THAT THIS
 CONFIGURATION WILL ALLOW THE EQUIPMENT TO FUNCTION
 PROPERLY. PER WPB AMEND TO FBC 107.2.1 THE RESPONSE
 LETTER IS NOT A CONSTRUCTION DOCUMENT PLEASE INCLUDE
 REQUESTED DOCUMENT A SIGNED AND SEALED LETTER FROM THE
 MANUFACTURES AND THE ENGINEER. STATING THAT THIS PIPING
 LAYOUT WILL ALLOW BOTH THE GENERATOR AND THE BOILERS TO
 FUNCTION PROPERLY SIMULTANEOUSLY.
  
 PREVIOUS COMMENT NOT COMPLIED 5. SHT. P-407 PLEASE SHOW
 ON THE PLAN THE MIN DISTANCE BETWEEN THE INTAKE AND
 EXHAUST. . PER WPB AMEND TO FBC 107.2.1 THE RESPONSE
 LETTER IS NOT A CONSTRUCTION DOCUMENT PLEASE INCLUDE
 REQUESTED DIMENSIONS ON THE PLAN.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  