 3RD REVIEW: FBC 2014 5TH EDITION
 PLUMBING COMMENTS:
 1. SHT. P-902 + P-904 THE SANITARY STACKS ARE NOT
 LABELED THE SAME SHT. P902 IS LABELED WITH AN S THE
 STACKS ON P-904 ARE LABELED WITH AN X PLEASE LABEL THE
 STACKS ON EACH SHT. TO MATCH THE COINCIDING STACKS ON
 ALL SHTS. PER WPB AMEND TO FBC 107.2.1
 2. PREVIOUS COMMENT #3 SHT. A -512 DETAIL # 8 STILL
 SHOWS THE WATERPROOFING MEMBRANE STOPPING AT THE CURB
 AT THE SLIDING BOOKCASE GLASS PLEASE SHOW THE MEMBRANE
 RUNNING UP AND OVER THE CURB. PER FBC PL 417.5.2
 3. SHT. P-905 PLEASE SHOW THE PIPE SIZING ON THE
 PRESSURE RISER LOBBY DETAIL #1. PER WPB AMEND TO FBC
 107.2.1
 4. ON ALL ISOMETRIC DRAWINGS PLEASE LABEL ON THE
 DIAGRAM WHEN A PIPE ENDS WHERE IT CONTINUES AND WITH
 COINCIDING LABEL. PER WPB AMEND TO FBC 107.2.1
 5. SHTS P-901 P-905 THE RISER LABELING DOES NOT MATCH
 SHT. 901 THE STACKS ARE LABELED WITH AN W THE STACKS ON
 SHT. 905 ARE LABELED WITH AN X PLEASE LABEL THEM ALL
 WITH COINCIDING LABELS WITH THE STACK NUMBER. PER WPB
 AMEND TO FBC 107.2.1
 6. SHT. 902 RISER S1 THE BATHROOM GROUP AT THE BOTTOM
 OF THE RISER IS NOT VENTED PROPERLY THE LAVATORY SHALL
 CONNECT UPSTREAM OF THE SOIL STACK IT CANNOT CONNECT TO
 THE SOIL STACK WITHOUT A SEPARATE VENT AND THERE SHALL
 BE A VENT BETWEEN THE SHOWER AND TOILET. PER FBC PL
 901.2.1, 912.1
 7. SHT. P-102 THE OVERFLOW STORM DRAINS THAT ARE
 TERMINATING ON THE WEST SIDE OF THE BUILDING WILL NEED
 TO BE RELOCATED, AS YOU KNOW THIS SIDE OF THE BUILDING
 IS NOT OPEN IT IS CONNECTED TO THE PARKING GARAGE
 APARTMENT BUILDING THE OVER FLOW ON THE NORTH END IS
 DUMPING INTO THE PARKING GARAGE AND THE OVER FLOW ON
 THE SOUTH END IS DUMPING INTO THE GENERATOR AREA AND
 WILL FLOOD THE GENERATOR IF THE OVERFLOW IS BEING USED.
 PER WPB AMEND TO FBC 107.2.1
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  