| 2018-07-13 16:55:37 | 3RD REVIEW FBC-2014 MECHANICAL, ENERGY CONSERVATION, |
| | BUILDING |
| | PERMIT #17110874 |
| | OLD CITY HALL/MARRIOTT HOTEL |
| | 7/13/18 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEETS M-101, LS-101: FIRE DAMPERS MISSING AT THE |
| | 16X14 DUCT PENETRATING THE EXIT CORRIDOR/VESTIBULE |
| | FIRE-RATED WALL, AND THE TWO14X14 DUCTS PENETRATING THE |
| | CONFERENCE/MECH FIRE-RATED WALL. |
| | |
| | 2) M-101: PROVIDE VENTILATION FOR THE FIRE PUMP ROOM- |
| | SEE SECTION 11.3.2.1 NFPA 20. |
| | |
| | 3) M-101: PROVIDE EXHAUST VENTILATION FOR THE |
| | LINEN/TRASH CHUTE ROOM- TABLE 6-4 ASHRAE 62.1-10. |
| | |
| | 4) M-101 & M600: VENTILATION AND AIR BALANCE |
| | CALCULATIONS FOR THE FUTURE LAUNDRY HAVE NOT BEEN |
| | PROVIDED, AND NO MEANS OF PROVIDING THE REQUIRED O/A |
| | FOR OCCUPANTS IS SHOWN ON THE PLAN. PLEASE CLARIFY IF A |
| | REVISION TO THE PLAN WILL BE PROVIDED FOR THE LAUNDRY, |
| | AND IF SO, PLEASE ADD IT TO THE LIST OF DEFERRED |
| | SUBMITTALS ON SHEET M-001. |
| | |
| | 5) M-102: THE KITCHEN EXHAUST FANS SHALL HAVE A MINIMUM |
| | CLEARANCE OF 10' TO THE ADJACENT BUILDING WALLS AND |
| | PROPERTY LINE- SECTION 506.3.13.3 FBC-14 MECHANICAL. |
| | THE PLAN SHOWS 5'9-13/32 AND 5'4" WHICH IS |
| | NON-COMPLIANT. |
| | |
| | 6) M-102: CLARIFY HOW ACCESS TO THE KSF, KEF'S AND |
| | OTHER APPLIANCES AND EQUIPMENT ON THE ROOF WILL BE |
| | PROVIDED FOR SERVICE AND REPLACEMENT- SECTION 306.1 |
| | FBC-14 MECH. |
| | |
| | 7) M-101,M-105: WHERE REQUIRED BY 606.2.1 FBC-14 |
| | MECHANICAL, THE DUCT SMOKE DETECTORS SHALL BE INSTALLED |
| | IN THE RETURN AIR SYSTEMS OF THE AIR HANDLERS.THE PLANS |
| | ARE SHOWING THEM IN THE SUPPLY SIDES. |
| | |
| | 8) M-101, 102, 103, 104, 105, 705: THE FIRE/SMOKE |
| | DAMPERS AT SHAFT PENETRATIONS AND OTHER PENETRATION |
| | LOCATIONS WILL HAVE TO BE MOTORIZED AS PART OF THE |
| | SMOKE CONTROL SYSTEM. PLEASE PROVIDE THE MOTORIZED |
| | DAMPER SYMBOLS AT THE REQUIRED LOCATIONS. |
| | |
| | 9) M-101, 102, 103, 104, 105, 705: PLEASE PLACE VERY |
| | APPARENT NOTES ON THE MEP PLANS TO INDICATE THE |
| | STAIRWELL VENTILATION CHASES ARE FOR STAIRWELL |
| | PRESSURIZATION ONLY AND NO OTHER PIPES, CONDUITS, |
| | RACEWAYS, WIRING, DUCTS ETC. SHALL BE PERMITTED IN |
| | THOSE CHASES. |
| | |
| | 10) M-105: MORE INFORMATION ABOUT THE POOL ROOMS WILL |
| | BE REQUIRED EITHER UNDER THIS MAIN OR SEPARATE PERMIT. |
| | PLEASE PROVIDE A LIST OF CHEMICALS TO BE STORED IN THE |
| | ROOMS INCLUDING THEIR QUANTITIES AND SUBMIT MSDS |
| | SHEETS. A) PROVIDE EXHAUST VENTILATION CALCULATIONS FOR |
| | THE POOL ROOM AND ADJACENT STORAGE ROOMS. PLEASE NOTE |
| | THAT HAZARDOUS EXHAUST DUCT SYSTEMS SHALL RUN |
| | |
| | INDEPENDENTLY OF OTHER EXHAUST DUCTS. THE CURRENT PLAN |
| | SHOWS INTERCONNECTION OF THE EXHAUST DUCTS FROM EACH |
| | STORAGE ROOM WHICH MAY BE PROHIBITED IF ONLY ONE OF THE |
| | ROOMS IS STORING CHEMICALS. |
| | |
| | 11) M-105: PLEASE INCLUDE THE MAKEUP AND EXHAUST AIR |
| | CALCULATIONS FOR THE POOL ROOMS IN THE AIR BALANCE |
| | SCHEDULE. |
| | |
| | 12) M-001: PLEASE ADD THE FOLLOWING ITEMS TO THE |
| | DEFERRED SUBMITTALS LIST: MANUFACTURER'S SPECIFICATIONS |
| | FOR THE GENERATOR, DUCT SMOKE DETECTORS, C02 SENSORS, |
| | DRYERS, AND FACTORY MADE ACCESS PANELS, |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |