Plan Review Notes
Plan Review Notes For Permit 17110874
Permit Number 17110874
Review Stop B
Sequence Number 3
Notes
Date Text
2018-07-30 16:08:24****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 27. PENETRATIONS THROUGH 2 HOUR RATED STAIRWAYS
  
 A) PAGE 098-A-701 SHOWS WHAT APPEARS TO BE A 2 HOUR
 DROPPED CEILING.
  
 B) PAGE 048-LS101 AND 050-A101 BOTH SHOW STAIRWAY 3 AS
 A 2HR VERTICAL EXIT STAIRWAY. PENETRATIONS WERE FOUND
 ON PAGE 124-P-101.
  
 SEE FBC-B 1022.5 PENETRATIONS. PENETRATIONS INTO AND
 OPENINGS THROUGH INTERIOR EXIT STAIRWAYS AND RAMPS ARE
 PROHIBITED EXCEPT FOR REQUIRED EXIT DOORS, EQUIPMENT
 AND DUCTWORK NECESSARY FOR INDEPENDENT VENTILATION OR
 PRESSURIZATION, SPRINKLER PIPING, STANDPIPES,
 ELECTRICAL RACEWAY FOR FIRE DEPARTMENT COMMUNICATION
 SYSTEMS AND ELECTRICAL RACEWAY SERVING THE INTERIOR
 EXIT STAIRWAY AND RAMP AND TERMINATING AT A STEEL BOX
 NOT EXCEEDING 16 SQUARE INCHES (0.010 M2). SUCH
 PENETRATIONS SHALL BE PROTECTED IN ACCORDANCE WITH
 SECTION 714. THERE SHALL BE NO PENETRATIONS OR
 COMMUNICATING OPENINGS, WHETHER PROTECTED OR NOT,
 BETWEEN ADJACENT INTERIOR EXIT STAIRWAYS.
  
 A RESPONSE LETTER INDICATING HOW EACH ITEM WAS
 ADDRESSED WILL HELP TO EXPEDITE PLAN REVIEW.
  
 PROVISOS:
  
 A) ONCE THE FIRST FLOOR SLAB IS POURED THE 2ND
 ELEVATION CERTIFICATE IS REQUIRED.
  
 B) BEFORE THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY OR
 A CERTIFICATE OF COMPLETION THE 3RD FLOOD ZONE
 CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL EXTERIOR
 ATTENDANTS A/C PADS OR OTHER SLABS FOR GENERATORS.
  
 C) PRODUCT APPROVALS
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING, EXTERIOR WINDOW, AND
 DOORS, STOREFRONT , OVERHEAD DOORS, ROOF HATCH, LOUVERS
 AND NANA WALLS. DATA SHEET FOR ELEVATOR.
 ALTERNATIVELY YOU CAN SUBMIT THESE LATER AS A DEFERRED
 SUBMITTAL BY LISTING THEM ON THE COVER SHEET.
 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 D) VALET DROP OFF COMPLIANCE TO BE SHOWN ON SEPARATE
 PERMIT.
  
 E) POOL DECK, POOL UNDER A SEPARATE PERMIT.
  
 A) SHEET 049-LS-102, 058-A-104 BOTH SHOW A LINEAR POOL
 DECK DRAIN. NONE OF THE ARCHITECTURAL SHEETS SHOW THE
 ELEVATION OR CROSS SLOPES OF THE POOL DECK. THE
 STRUCTURAL SHEET 012-S-1.04 SHOWS (2) ELEVATIONS ONE AT
 T. O. SLAB AT EL= 83 FEET AND A 2ND ELEVATION AT
 ELEVATION T. O. SLAB 82 FEET. THE STRUCTURAL SHEET
 036-S-4.20 DETAIL # 4 SHOWS 2 HEIGHTS IN THE CONCRETE
 DECK. A FINISHED CONCRETE DECK AND A DROPPED STRUCTURAL
 DECK AROUND THE POOL DECK ASSUMED AT T. O. SLAB AT EL=
 82 FEET.
  
 B) SHEET 037-S-4.21 DETAIL 10 SHOWS THE SUPPORT LIFT BY
 THE EDGE OF THE POOL, BUT THIS SAME DETAIL SHOWS THE
 SIDE WALL OF THE POOL, SECONDARY POOL STRUCTURE BY POOL
 DESIGNER. THERE ARE ONLY THE 2 ELEVATIONS AROUND THE
 POOL. THE STRUCTURAL SHEET 036-S-4.20 DETAIL # 4 HAS A
 NOTE SEE ARCHITECTURAL SHEETS FOR SLOPE.
  
 C) 2014 FBC-B SECTION 454.1.3.1.2. POOL WET DECKS SHALL
 BE UNIFORMLY SLOPED AT A MINIMUM OF 2 PERCENT TO A
 MAXIMUM OF 4 PERCENT AWAY FROM THE POOL OR TO DECK
 DRAINS TO PREVENT STANDING WATER. THE PLANS ONLY SHOW A
 LINEAR POOL DRAIN ON THE WEST SIDE OF THE POOL. PLEASE
 SHOW COMPLIANCE FOR THE OTHER 3 SIDES.
  
 D) THE ACCESSIBILITY CODE SECTION 403.3 CROSS SLOPES
 FOR WALKING SURFACES SHALL BE NOT STEEPER THAN 1:48.
 PLEASE PROVIDE HOW COMPLIANCE WILL BE ACHIEVED FOR BOTH
 SECTIONS OF THE CODE.
  
 E) SHEET 036-S-4.20 DETAIL # 1 AND 037-S-4.21 DETAIL #
 10 SHOWS THE POOL STRUCTURAL WALL LEVEL WITH THE
 STRUCTURAL DECK HOW WILL WATER FROM THE POOL DECK BE
 SLOPED BACK TO THE LINEAR DECK DRAIN. WATER ON THE POOL
 DECK SHALL BE SLOPED AWAY FROM THE POOL EDGE. 2014
 FBC-B SECTION 454.1.3.1.2.
  
 F) NA
  
 G) SHEET 037-S-4.21 DETAIL # 10 SHOWS A STRUCTURAL BASE
 FOR AN ADA CHAIR LIFT. THE ARCHITECTURAL SHEET
 058-A-104 SHOWS THE POSITION OF THE CHAIR LIFT AND THE
 CLEAR 48X30 INCHES PLEASE PROVIDE THE MANUFACTURES SPEC
 ON THE LIFT THE DISTANCE FROM EDGE OF THE WATER TO THE
 CENTERLINE OF THE SEAT IS 4.75 FEET. WILL THE LIFT BE
 ABLE TO LIFT A PERSON INTO THE WATER WITH A SPAN OF 6
 FEET OR MORE? 2014 FBC-ACCESSIBILITY CODE 1009.2. THE
 LOCATION OF THE STRUCTURAL STAND APPEARS CLOSER THAN
 THE ARCHITECTURAL SHEET?
  