| Date |
Text |
| 2018-04-12 14:57:03 | 1ST REVIEW: FBC 2014 5TH EDITION |
| | |
| | PLUMBING COMMENTS: |
| | 1. SHT. A512 DETAIL #5 THE FLUID APPLIED WATER PROOFING |
| | SHALL BE PITCHED TOWARD THE DRAIN AT A MIN OF 1/4" FT. |
| | AND SEALED AT THE DRAIN PLEASE SHOW THIS OR MAKE A NOTE |
| | ON THE PLAN. PER FBC PL 417.5.2 |
| | 2. THE WATER PROOFING MEMBRANE SHALL BE INSTALLED PER |
| | MANUFACTURE SPECIFICATIONS PLEASE PROVIDE MANUFACTURE |
| | SPECIFICATION AND INSTALLATION GUIDE. PER WPB AMEND TO |
| | FBC 107.2.1 |
| | 3. SHT. A512 DETAIL #4 THE WATER PROOFING MEMBRANE |
| | SHALL TURN UP ON ALL SIDES A MIN OF 2" ABOVE THE |
| | FINISHED THRESHOLD LEVEL IT APPEARS THAT THE DETAIL IS |
| | SHOWING IT STOPPING AT THE BOTTOM OF THE GLASS FOR THE |
| | BOOK SHELF WINDOW. PER FBC PL 417.5.2 |
| | 4. SHT. P- 904 PLEASE LABEL THE SOIL STACKS TO MATCH |
| | THE LABELING ON THE STACKS ON SHEET P-902. PER WPB |
| | AMEND TO FBC 107.2.1 |
| | 5. SHT. P-902 + 903 PLEASE SEPARATE THE WATER AND |
| | SANITARY ISOMETRICS AND REMOVE ANYTHING FROM THE |
| | DRAWING THAT IS NOT THE REQUIRED PIPING SUCH AS THE |
| | CARRIERS FOR THE TOILETS AS THE DRAWING ARE SHOWN NOW |
| | IT IS TO DIFFICULT TO DETERMINE CODE COMPLIANCE. PER |
| | WPB AMEND TO FBC 107.2.1 |
| | 6. PLEASE SHOW THE REQUIRED VALVE ON THE DROPS FOR THE |
| | GANG BATHS ON THE LOBBY LEVEL AND ROOF. PER FBC PL |
| | 606.1(5) |
| | 7. SHT. P-904,102, 104, 106 LABEL SANITARY RISER TO |
| | MATCH THE RISERS TAGS ON SHT. P902. PER WPB AMEND TO |
| | FBC 107.2.1 |
| | 8. SHT. P-905,101,103,105,107 PLEASE LABEL THE WATER |
| | RISER TO MATCH THE TAGS ON THE RISERS ON SHT. P-902. |
| | PER WPB AMEND TO FBC 107.2.1 |
| | 9. PLEASE PROVIDE ISOMETRIC DRAWINGS FOR THE ROOF TOP |
| | BAR AND LOUNGE ALSO THE PLUMBING IN THE SERVICE AREA. |
| | PER WPB AMEND TO FBC 107.2.1 |
| | 10. WHAT IS ROOM 800D SERVICE AREA USED FOR IS THIS THE |
| | LAUNDRY? PLEASE CLARIFY AND SHOW ALL PLUMBING ON THE |
| | PLAN. PER WPB AMEND TO FBC 107.2.1 |
| | 11. PLEASE INDICATE ON THE PLAN WHAT SLOPE THE STORM |
| | PIPING IS BEING INSTALLED IF IT IS 1/8" FT. THERE IS |
| | PIPING THAT IS UNDERSIZED. PER FBC PL TABLE 1106.3 |
| | |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561-805-6711 |
| | [email protected] |
| | |